IX. STEP 9 — ADJUST EVAPORATOR-FAN SPEED
Adjust evaporator-fan speed to meet jobsite conditions.
Tables 6A and 6B show fan rpm at motor pulley settings for
standard and alternate motors. Tables 7 and 8 show evapora-
tor fan motor data. Table 9 shows EconoMi$er IV pressure
drop. Table 10 shows sound data. Refer to Tables 11-28 for
fan performance data. See Fig. 38 for Perfect Humidity™ sys-
tem static pressure drop.
NOTE:
Before adjusting fan speed, make sure the new fan
speed will provide an acceptable air temperature rise range
on heating as shown in Table 1.
To change fan speed:
1. Shut off unit power supply.
2. Loosen belt by loosening fan motor mounting nuts.
See Fig. 39.
3. Loosen movable pulley flange setscrew (see Fig. 40).
4. Screw movable flange toward fixed flange to increase
fan speed and away from fixed flange to decrease fan
speed. Increasing fan speed increases load on motor.
Do not exceed maximum speed specified in Table 1.
5. Set movable flange at nearest keyway of pulley hub
and tighten setscrew. (See Table 1 for speed change
for each full turn of pulley flange.)
To align fan and motor pulleys:
1. Loosen fan pulley setscrews.
2. Slide fan pulley along fan shaft.
3. Make angular alignment by loosening motor from
mounting plate.
To adjust belt tension:
1. Loosen fan motor mounting nuts.
2. Slide motor mounting plate away from fan scroll for
proper belt tension (
1
/
2
-in. deflection with 8 to 10 lb of
force) and tighten mounting nuts (see Fig. 39).
3. Adjust bolt and nut on mounting plate to secure
motor in fixed position.
Table 6A — 581B Fan Rpm at Motor Pulley Setting With Standard Motor*
*Approximate fan rpm shown (standard motor/drive).
Table 6B — 581B Fan Rpm at Motor Pulley Setting With High-Static Motor*
*Approximate fan rpm shown (high-static motor/drive).
SETTING
EQUIPMENT
OUTPUT
VENTILATION
RATE
(cfm/Person)
ANALOG
OUTPUT
CO
2
CONTROL RANGE
(ppm)
OPTIONAL
RELAY SETPOINT
(ppm)
RELAY
HYSTERESIS
(ppm)
1
Interface w/Standard
Building Control System
Proportional
Any
0-10V
4-20 mA
0-2000
1000
50
2
Proportional
Any
2-10V
7-20 mA
0-2000
1000
50
3
Exponential
Any
0-10V
4-20 mA
0-2000
1100
50
4
Economizer
Proportional
15
0-10V
4-20 mA
0-1100
1100
50
5
Proportional
20
0-10V
4-20 mA
0- 900
900
50
6
Exponential
15
0-10V
4-20 mA
0-1100
1100
50
7
Exponential
20
0-10V
4-20 mA
0- 900
900
50
8
Health & Safety
Proportional
—
0-10V
4-20 mA
0-9999
5000
500
9
Parking/Air Intakes/
Loading Docks
Proportional
—
0-10V
4-20 mA
0-2000
700
50
UNIT
581B
MOTOR PULLEY TURNS OPEN
0
1
/
2
1
1
1
/
2
2
2
1
/
2
3
3
1
/
2
4
4
1
/
2
5
5
1
/
2
6
036
1044
1008
971
935
898
862
826
789
753
716
680
—
—
048
1185
1144
1102
1061
1019
978
936
895
853
812
770
—
—
060 (single and 3-phase)
1460
1425
1389
1354
1318
1283
1248
1212
1177
1141
1106
1070
1035
072
1585
1538
1492
1445
1399
1352
1305
1259
1212
1166
1119
—
—
UNIT
581B
MOTOR PULLEY TURNS OPEN
0
1
/
2
1
1
1
/
2
2
2
1
/
2
3
3
1
/
2
4
4
1
/
2
5
5
1
/
2
6
036
1455
1423
1392
1360
1328
1297
1265
1233
1202
1170
1138
1107
1075
048
1455
1423
1392
1360
1328
1297
1265
1233
1202
1170
1138
1107
1075
060
1685
1589
1557
1525
1493
1460
1428
1396
1364
1332
1300
—
—
072
1685
1589
1557
1525
1493
1460
1428
1396
1364
1332
1300
—
—
Содержание DURAPAC PLUS 581B
Страница 8: ...8 Fig 7 Base Unit Dimensions 581B036 072...
Страница 51: ......