18
—
Indoor Air Quality (IAQ) Sensor Input
The IAQ input can be used for demand control ventilation
control based on the level of CO
2
measured in the space or
return air duct.
Mount the accessory IAQ sensor according to manufacturer
specifications. The IAQ sensor should be wired to the AQ and
AQ1 terminals of the controller. Adjust the DCV potentiome-
ters to correspond to the DCV voltage output of the indoor air
quality sensor at the user-determined set point. See Fig. 35.
If a separate field-supplied transformer is used to power the
IAQ sensor, the sensor must not be grounded or the
EconoMi$er IV control board will be damaged.
CONTROL
CURVE
A
B
C
D
CONTROL POINT
APPROX. °F (°C)
AT 50% RH
73 (23)
70 (21)
67 (19)
63 (17)
12
14
1
6
18
20
2
2
24
26
28
30
32
34
36
38
40
42
44
46
90
10
0
80
70
60
50
40
30
20
10
ENT
HA
LP
Y—
BTU
P
ER
PO
UN
D DR
Y A
IR
85
(29)
90
(32)
95
(35)
100
(38)
105
(41)
110
(43)
35
(2)
35
(2)
40
(4)
40
(4)
105
(41)
110
(43)
45
(7)
45
(7)
50
(10)
50
(10)
55
(13)
55
(13)
60
(16)
60
(16)
65
(18)
65
(18)
70
(21)
70
(21)
75
(24)
75
(24)
80
(27)
80
(27)
85
(29)
90
(32)
95
(35)
100
(38)
APPROXIMATE DRY BULB TEMPERATURE— °F (°C)
A
A
B
B
C
C
D
D
RELA
TIVE HUM
IDITY
(%
)
HIGH LIMIT
CURVE
Fig. 33 — Enthalpy Changeover Set Points
TR1
24 Vac
COM
TR
24
Vac
HOT
1
2
3
4
5
EF
EF1
+
_
P1
T1
P
T
N
EXH
2V
10V
EXH
Set
Set
2V
10V
2V
10V
DCV
DCV
Free
Cool
B
C
A
D
SO+
SR+
SR
SO
AQ1
AQ
DCV
Min
Pos
Open
Max
N1
0
1000
2000
3000
4000
5000
6000
2
3
4
5
6
7
8
800 ppm
900 ppm
1000 ppm
1100 ppm
RANGE CONFIGURA
TION (ppm)
DAMPER VOLTAGE FOR MAX VENTILATION RATE
CO SENSOR MAX RANGE SETTING
2
Fig. 34 — EconoMi$er IV Control
Fig. 35 — CO
2
Sensor Maximum Range Setting