background image

9

Unloader Test Procedure

The unloader is the compressor internal mechanism, controlled by

the DC solenoid, that modulates between high and low stage. If it
is suspected that the unloader is not working, the following

methods may be used to verify operation.

1. Operate the system and measure compressor amperage.

Cycle the unloader on and off at 30 second plus intervals at
the thermostat (from low to high stage and back to low

stage). Wait 5 seconds after staging to high before taking a
reading. The compressor amperage should go up or down
at least 20 percent.

2. If the expected result is not achieved, remove the solenoid

plug from the compressor and with the unit running and the

thermostat calling for high stage, test the voltage output at
the plug with a DC voltmeter. The reading should be 24
volts DC.

3. If the correct DC voltage is at the control circuit molded

plug, measure the compressor unloader coil resistance. The

resistance should be approximately 330 or 1640 ohms de-
pending on unloader coil supplier. If the coil resistance is
infinite or is grounded, the compressor must be replaced.

Final Checks

IMPORTANT

: Before leaving job, be sure to do the following:

1. Ensure that all wiring is routed away from tubing and sheet

metal edges to prevent rub--through or wire pinching.

2. Ensure that all wiring and tubing is secure in unit before

adding panels and covers. Securely fasten all panels and

covers.

3. Tighten service valve stem caps to 1/12--turn past finger

tight.

4. Leave Owner’s Manual with owner. Explain system opera-

tion and periodic maintenance requirements outlined in
manual.

5. Fill out Dealer Installation Checklist and place in customer

file.

TROUBLESHOOTING

If the compressor fails to operate with a cooling call, the table
below (Resistance table) can be used to verify if there is any

damage to the compressor windings causing system malfunction.

Table 3 – Winding Resistance

Winding

Winding resistance at 70

_

F +/--- 20

_

F

(21.11

_

C +/--- 11.11

_

C)

Unit Size

024

036

048

060

Start

(S---C)

1.64

1.54

1.86

1.63

Run

(R---C)

1.30

0.88

0.52

0.39

MAJOR COMPONENTS

2--Stage Compressor

The 2--stage compressor contains motor windings that provide
2--pole (3500 RPM) operation.

Compressor Internal Relief

The compressor is protected by an internal pressure relief (IPR)

which relieves discharge gas into compressor shell when
differential between suction and discharge pressures exceeds and

550 -- 625 psi. The compressor is also protected by an internal
overload attached to motor windings.

Compressor Control Contactor

The contactor has a 24 volt coil and is controlled by Y input from

the thermostat

High and Low Pressure Switches

High and low pressure switches are provided in line with the Y
signal to the contactor for protection.

CARE AND MAINTENANCE

For continuing high performance and to minimize possible

equipment failure, periodic maintenance must be performed on this
equipment.
Frequency of maintenance may vary depending upon geographic

areas, such as coastal applications. See Users Manual for
information.

Содержание BH17NA

Страница 1: ...a suitable warning label EXPLOSION HAZARD Failure to follow this warning could result in death serious personal injury and or property damage Never use air or gases containing oxygen for leak testing...

Страница 2: ...including adverse weather conditions Clearance Requirements When installing allow sufficient space for airflow clearance wiring refrigerant piping and service Allow 24 in 609 6 mm clearance to service...

Страница 3: ...ried without further special consideration Do not bury lines longer than 36 in 914 4 mm Outdoor units may be connected to indoor section using accessory tubing package or field supplied refrigerant gr...

Страница 4: ...OTE Some outdoor units contain a mechanical fitting at the liquid distributor This connection is not field serviceable and should not be disturbed NOTE For Liquid Service Valve Braze lineset to adapte...

Страница 5: ...ssible from unit per Section 440 14 of NEC Route Ground and Power Wires Remove access panel to gain access to unit wiring Extend wires from disconnect through power wiring hole provided and into unit...

Страница 6: ...nfigurations 1 The Y2 call for high stage cooling energizes the Cool tap on the control board The grey wire from cool tap is connec ted to tap 5 on the motor Refer to the furnace Product Data to find...

Страница 7: ...ssor has been off for 5 minutes or power has not been cycled for 5 minutes the OF2 relay and T2 terminal will energize This will close the contactor and start the outdoor fan motor and compressor When...

Страница 8: ...s between 70_F and 100_F 21 11_C and 37 78_C and the indoor temperature is between 70_F and 80_F 21 11_C and 26 67_C Follow the procedure below Unit is factory charged for 15ft 4 57 m of lineset Adjus...

Страница 9: ...and covers 3 Tighten service valve stem caps to 1 12 turn past finger tight 4 Leave Owner s Manual with owner Explain system opera tion and periodic maintenance requirements outlined in manual 5 Fill...

Страница 10: ...Do not install a suction line filter drier in liquid line S POE oils absorb moisture rapidly Do not expose oil to atmosphere S POE oils may cause damage to certain plastics and roofing materials S Wr...

Отзывы: