background image

8

the reversing valve will be energized. A few seconds later, the
compressor will be re--energized and the normal defrost cycle

starts.
Once defrost termination conditions have been met, the following

sequence will occur: The compressor will be de--energized for

approximately 1 minute, then the reversing valve will be
de--energized. A few seconds later, the compressor will be

re--energized and the normal heating cycle starts.

Defrost

The defrost control is a time/temperature control which has field

selectable settings of 30, 60, 90, or 120 minutes, factory set to 90
minutes. These settings represent the amount of time that must pass

after closure of the defrost thermostat before the defrost sequence
begins.
The defrost thermostat senses coil temperature throughout the

heating cycle. When the coil temperature reaches the defrost
thermostat setting of approximately 32

_

F (0

_

C), it will close,

which energizes the DFT terminal and begins the defrost timing
sequence. When the DFT has been energized for the selected time,

the defrost cycle begins. Defrost cycle is terminated when defrost
thermostat opens, or automatically after 10 minutes.

Defrost Speedup

To initiate a forced defrost, speedup pins (J1) must be shorted with
a flat head screwdriver for 5 seconds and

RELEASED

. If the

defrost thermostat is open, a short defrost cycle will be observed
(actual length depends on Quiet Shift--2 switch position). When

Quiet Shift--2 is off, only a short 30 second defrost cycle is

observed. With Quiet Shift--2 ON, the speedup sequence is
approximately 3 minutes; 1 minute compressor off period followed

by 30 seconds of defrost with compressor operation. When
returning to heating mode, the compressor will turn off for an

additional 1 minute.
If the defrost thermostat is closed, a complete defrost cycle is
initiated. If the Quiet Shift--2 switch is turned on, the compressor

will be turned off for two 1 minute intervals as explained
previously.

OF2

O

F1

ON

QUIET

SHIFT

120

30

60

60

30

90

INTER

V

AL  

TIMER

OFF

P3

DFT

O   R   

W

2

   

Y   C

T2 C  C  O

DFT

T1

Y

P1

J1

SPEEDUP

Speedup
Pins

Defrost interval
DIP switches

Quiet
Shift

A05378

Fig. 11 -- Defrost Control

Check Charge

NOTE

:

CHARGE IN HIGH STAGE ONLY.

Factory charge amount and desired subcooling are shown on unit

rating plate. Charging method is shown on information plate inside
unit. To properly check or adjust charge, conditions must be

favorable for subcooling charging. Favorable conditions exist
when the outdoor temperature is between 70

_

F and 100

_

F

(21.11

_

C and 37.78

_

C), and the indoor temperature is between

70

_

F and 80

_

F (21.11

_

C and 26.67

_

C). Follow the procedure

below:
Unit is factory charged for 15ft (4.57 m) of lineset. Adjust charge
by adding or removing 0.6 oz/ft (.018 kg/m) of 3/8 liquid line

above or below 15ft (4.57 m) respectively.
For standard refrigerant line lengths (80 ft/24.38 m or less), allow
system to operate in cooling mode at least 15 minutes. If conditions

are favorable, check system charge by subcooling method. If any
adjustment is necessary, adjust charge slowly and allow system to

operate for 15 minutes to stabilize before declaring a properly

charged system.
If the indoor temperature is above 80

_

F (26.67

_

C), and the

outdoor temperature is in the favorable range, adjust system charge
by weight based on line length and allow the indoor temperature to

drop to 80

_

F (26.67

_

C) before attempting to check system charge

by subcooling method as described above.
If the indoor temperature is below 70

_

F (21.11

_

C), or the outdoor

temperature is not in the favorable range, adjust charge for line set
length above or below 15ft (4.57 m) only. Charge level should then

be appropriate for the system to achieve rated capacity. The charge
level could then be checked at another time when the both indoor

and outdoor temperatures are in a more favorable range.

NOTE

: If line length is beyond 80 ft (24.38 m) or greater than 20

ft (6.10 m) vertical separation, See Long Line Guideline for
special charging requirements.

Heating Check Chart Procedure

To check system operation during heating cycle, refer to the
Heating Check Chart on outdoor unit. This chart indicates whether

a correct relationship exists between system operating pressure and

air temperature entering indoor and outdoor units. If pressure and
temperature do not match on chart, system refrigerant charge may

not be correct. Do not use chart to adjust refrigerant charge.

Verify units for proper switching between low & high

stages

Check the suction pressures at the service valves. Suction pressure
should be reduced by 3--10% when switching from low to high

capacity.
Compressor current should increase 20--45% when switching from

low to high stage. The compressor solenoid when energized in

high stage, should measure 24vac at leads inside control box.
When the compressor is operating in low stage the 24v DC

compressor solenoid coil is de--energized. When the compressor is
operating in high stage, the 24v DC solenoid coil is energized. The

solenoid plug harness that is connected to the compressor HAS an

internal rectifier that converts the 24v AC signal to 24v DC.

DO

NOT INSTALL A PLUG WITHOUT AN INTERNAL

RECTIFIER.

Содержание BH17NA

Страница 1: ...a suitable warning label EXPLOSION HAZARD Failure to follow this warning could result in death serious personal injury and or property damage Never use air or gases containing oxygen for leak testing...

Страница 2: ...including adverse weather conditions Clearance Requirements When installing allow sufficient space for airflow clearance wiring refrigerant piping and service Allow 24 in 609 6 mm clearance to service...

Страница 3: ...ried without further special consideration Do not bury lines longer than 36 in 914 4 mm Outdoor units may be connected to indoor section using accessory tubing package or field supplied refrigerant gr...

Страница 4: ...OTE Some outdoor units contain a mechanical fitting at the liquid distributor This connection is not field serviceable and should not be disturbed NOTE For Liquid Service Valve Braze lineset to adapte...

Страница 5: ...ssible from unit per Section 440 14 of NEC Route Ground and Power Wires Remove access panel to gain access to unit wiring Extend wires from disconnect through power wiring hole provided and into unit...

Страница 6: ...nfigurations 1 The Y2 call for high stage cooling energizes the Cool tap on the control board The grey wire from cool tap is connec ted to tap 5 on the motor Refer to the furnace Product Data to find...

Страница 7: ...ssor has been off for 5 minutes or power has not been cycled for 5 minutes the OF2 relay and T2 terminal will energize This will close the contactor and start the outdoor fan motor and compressor When...

Страница 8: ...s between 70_F and 100_F 21 11_C and 37 78_C and the indoor temperature is between 70_F and 80_F 21 11_C and 26 67_C Follow the procedure below Unit is factory charged for 15ft 4 57 m of lineset Adjus...

Страница 9: ...and covers 3 Tighten service valve stem caps to 1 12 turn past finger tight 4 Leave Owner s Manual with owner Explain system opera tion and periodic maintenance requirements outlined in manual 5 Fill...

Страница 10: ...Do not install a suction line filter drier in liquid line S POE oils absorb moisture rapidly Do not expose oil to atmosphere S POE oils may cause damage to certain plastics and roofing materials S Wr...

Отзывы: