background image

707C--C, 707C--F: Installation Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

12

attached  to  the  inside  of  the  compressor  access  panel.  (See 

Fig. 20

Subcool  chart  for  units  with TXV  and  superheat  chart  for  units  with

fixed orifice.) The chart  includes the required liquid line temperature at

given discharge line pressures and outdoor ambient temperatures.
A superheat chart is attached to the inside of the compressor access panel

for the unit with fixed metering device. Refer to the charging procedure

on the label.
An accurate  thermocouple- or thermistor-type thermometer, and a gauge

manifold are required when using the subcooling charging method for

evaluating  the  unit  charge.  Do  not  use  mercury  or  small  dial-type

thermometers  because  they  are  not  adequate  for  this  type  of

measurement.

NOTE: 

 Allow system to operate for a minimum of 15 minutes before

checking or adjusting refrigerant charge.

IMPORTANT: 

 When  evaluating  the  refrigerant  charge,  an  indicated

adjustment to the specified factory charge must always be very minimal.

If  a  substantial  adjustment  is  indicated,  an  abnormal  condition  exists

somewhere  in  the  cooling  system,  such  as  insufficient  airflow  across

either coil or both coils.
Proceed as follows:

1. Remove caps from low- and high-pressure service fittings.
2. Using  hoses  with  valve  core  depressors,  attach  low-  and

high-pressure  gauge  hoses  to  low-  and  high-pressure  service

fittings, respectively.

3. Start unit and let run until system pressures stabilize.
4. Measure and record the following:

a.

Outdoor ambient-air temperature (

°F [°C] db).

b. Liquid line temperature (°F [°C]) at TXV.

c. Discharge (high-side) pressure (psig). 

d. Suction (low-side) pressure (psig) (for reference only).

5. Using  Cooling  Charging  Charts  compare  outdoor-air  temperature

(°F  [°C] db) with the discharge line pressure (psig) to determine

desired system operating liquid line temperature (See 

Fig. 20

).

6. Compare  actual  liquid  line  temperature  with  desired  liquid  line

temperature. Using a tolerance of ±2°F (±1.1°C), add refrigerant if

actual  temperature  is  more  than  2°F  (1.1°C)  higher  than  proper

liquid line temperature, or remove refrigerant if actual temperature

is  more  than  2°F  (1.1°C)  lower  than  required  liquid  line

temperature.

NOTE: 

 If the problem causing the inaccurate readings is a refrigerant

leak, refer to Check for Refrigerant Leaks section.

Indoor Airflow and Airflow Adjustments

NOTE: 

Be sure that all supply-and return-air grilles are open, free from

obstructions, and adjusted properly. 

This unit is factory-set up for use with a  single cooling fan  speed.  In

addition, this unit has the field-selectable capability to run two different

cooling  fan  speeds: The  rated  cooling  fan  speed  (350~400  CFM/Ton)

and an enhanced dehumidification fan speed (As low as 320 CFM/Ton)

for  use  with  either  a  dehumidistat  or  a  thermostat  that  supports

dehumidification.
The cooling speed is marked “LOW” on the interface fan board (IFB)

(See 

Fig. 11

) .  The factory-shipped settings are noted in 

Table 4

.  There

are  4  additional  speed  tap  wires  available  for  use  in  either  electric

heating or cooling (For color coding on the indoor fan motor leads, see

Table 3

). The additional 4 speed tap wires are shipped loose with vinyl

caps  and  are  located  in  the  control  box,  near  the  interface  fan  board

(IFB) (See 

Fig. 11

).

Single Cooling Fan Speed Set-up (Dehumidification 

feature not used)

To change cooling speed:

1. Remove the vinyl cap off of the desired speed tap wire (Refer to

Table 3

 for color coding). Add the wet coil pressure drop in 

Table 7

to the system static to determine the correct cooling airflow speed

in 

Table

 that will deliver the nominal cooling airflow as listed in

Table

 for each size.

2. Remove the current speed tap wire from the “LOW” terminal on the

interface fan board (IFB) (See 

Fig. 11

) and place vinyl cap over the

connector on the wire.

3. Connect the desired speed tap wire to the “LOW” terminal on the

interface fan board (IFB).

NOTE: 

If accessory electric heat is installed, and the electric heat fan

speed is chosen to be the same as the normal cooling fan speed, the dry

airflow  must  meet  or  exceed  the  minimum  airflow  speed  specified  in

Table 2

 for the specific size unit.

Two Cooling Fan Speeds Set-up (Dehumidification 

feature used)

IMPORTANT: 

Dehumidification control must open control circuit on

humidity rise above set point.
Use of the dehumidification cooling fan speed requires use of either a 24

VAC dehumidistat or a thermostat which includes control of a 24 VAC

dehumidistat  connection.    In  either  case,  the  dehumidification  control

must  open  the  control  circuit  on  humidity  rise  above  the

dehumidification set point. 

1. Using 

Fig. 11

, move the two pin DEHUM jumper from the “STD”

position to the “DEHUM” position.

2. Remove  fan  speed  tap  wire  from  the  “LOW”  terminal  on  the

interface fan board (IFB) (See 

Fig. 11

).

3. Determine  correct  normal  cooling  fan  speed  for  unit  and

application.  Add the wet coil pressure drop in 

Table 7

 to the system

static to determine the correct cooling airflow speed in 

Table 5

 that

will deliver the nominal cooling airflow as listed in 

Table 1

 for each

size.

NOTE: 

If accessory electric heat is installed, the dry airflow must meet

or  exceed  the  minimum  airflow  speed  specified  in 

Table 2

  for  the

specific size unit.  The electric heat fan speed will be the same as the

normal cooling fan speed.

4. Remove the vinyl cap off of the desired speed tap wire (Refer to

Table 3

 for color coding) for the normal cooling fan speed and place

desired speed tap wire on “HIGH” on the interface board. 

5. Refer  to  airflow  tables  (

Table 4

-

Table 6

)  to  determine  allowable

speeds  for  the  dehumidification  cooling  fan  speed.    In 

Table 4

,

speeds  that  are  not  allowed  for  dehumidification  cooling  are

shaded.

6. Remove the vinyl cap off of the desired speed tap wire (Refer to

Table 3

 for color coding) for the dehumidification cooling fan speed

and place desired speed tap wire on the “LOW” connection on the

CAUTION

!

UNIT OPERATION HAZARD

Failure to follow this caution may result in unit damage.
For cooling operation, the recommended airflow is 350 to 450 cfm for

each 12,000 Btuh of rated cooling capacity. For heating operation, the

airflow  must  produce  a  temperature  rise  that  falls  within  the  range

stamped on the unit rating plate.

WARNING

!

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

Disconnect electrical power to the unit and install lockout tag before

changing blower speed.

Содержание 707C Series

Страница 1: ...refer to the current editions of the Canadian electrical Code CSA C22 1 Recognize safety information This is the safety alert symbol When you see this symbol on the unit and in instructions or manual...

Страница 2: ...stributor for details and PE Professional Engineering Certificate if required Roof Curb Install accessory roof curb in accordance with instructions shipped with curb See Fig 4 Install insulation cant...

Страница 3: ...707C C 707C F Installation Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 3 A200003 Fig 2 24 36 Unit Dimensions...

Страница 4: ...707C C 707C F Installation Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 4 A150541 Fig 3 42 60 Unit Dimensions...

Страница 5: ...1 lb density Fig 4 Roof Curb Dimensions UNIT SIZE CATALOG NUMBER A IN mm B small common base IN mm B large base IN mm Part Number CPRCURB011B00 can be used on both small and large basepan units The cr...

Страница 6: ...des Ducts passing through an unconditioned space must be insulated and covered with a vapor barrier If a plenum return is used on a vertical unit the return should be ducted through the roof deck to c...

Страница 7: ...When using a gravel apron make sure it slopes away from the unit Connect a drain tube using a minimum of 3 4 in PVC or 3 4 in copper pipe all field supplied at the outlet end of the 2 in 51 mm trap D...

Страница 8: ...nances Adhere to the following criteria when selecting sizing and installing the duct system 1 Units are shipped for side shot installation 2 Select and size ductwork supply air registers and return a...

Страница 9: ...they do not interfere with operation of unit If an accessory electric heater is installed low voltage leads from heater must be connected to factory supplied control leads from Indoor Fan Board P4 con...

Страница 10: ...7 3 17 4 7 3 17 4 7 3 17 5 6 INDOOR BLOWER Nominal Cooling Airflow Cfm Size in Size mm Motor HP RPM 800 10x10 254x254 1 2 1050 1000 10x10 254x254 1 2 1050 1150 11x10 279 4x254 3 4 1000 1350 11x10 279...

Страница 11: ...rs start Observe that compressor and outdoor fan shut down when control setting is satisfied and that indoor blower shuts down after 90 second fan time delay expires IMPORTANT Three phase scroll compr...

Страница 12: ...lor coding on the indoor fan motor leads see Table 3 The additional 4 speed tap wires are shipped loose with vinyl caps and are located in the control box near the interface fan board IFB See Fig 11 S...

Страница 13: ...Y and G These completed circuits through the thermostat connect contactor coil C through unit wire Y and time delay relay TDR through unit wire G across the 24 V secondary of transformer TRAN The nor...

Страница 14: ...d Low Pink CFM 1174 1107 1045 985 914 890 825 760 673 572 BHP 0 32 0 32 0 33 0 33 0 34 0 35 0 36 0 37 0 37 0 37 Medium1 Red CFM 1246 1195 1148 1081 1019 953 884 859 795 690 BHP 0 38 0 39 0 39 0 40 0 4...

Страница 15: ...ation speed Table 5 Dry Coil Air Delivery Horizontal Discharge Sizes 36 60 3 Phase Models Only Unit Motor Speed Wire Color External Static Pressure IN W C 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 36 Low Bl...

Страница 16: ...20 0 21 Med Low Pink CFM 1002 936 875 821 748 687 613 554 565 518 WATTS 144 155 161 171 176 187 193 203 209 220 BHP 0 15 0 17 0 17 0 18 0 19 0 20 0 21 0 22 0 22 0 24 Medium Red CFM 1255 1210 1145 1074...

Страница 17: ...Black CFM 2480 2432 2375 2322 2236 2161 2085 2006 1917 1808 WATTS 1029 1012 995 975 941 908 869 836 796 751 BHP 1 10 1 09 1 07 1 05 1 01 0 97 0 93 0 90 0 85 0 81 Shaded areas indicate speed static co...

Страница 18: ...Table IN W C Small Cabinet 24 36 STATIC STANDARD CFM SCFM 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 5 kW 0 00 0 00 0 00 0 00 0 00 0 00 0 00 0 00 0 02 0 04 0 06 0 07 10 kW 0 00 0 00 0 00...

Страница 19: ...nstallation Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 19 A150503 Fig 12 Connection Wiring Diagram 24 36 60 Si...

Страница 20: ...Installation Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 20 A150513 Fig 13 Ladder Wiring Diagram 24 36 60 Size...

Страница 21: ...F Installation Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 21 A200013 Fig 14 Connection Wiring Diagram 30 Size...

Страница 22: ...C F Installation Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 22 A200014 Fig 15 Ladder Wiring Diagram 30 Size 20...

Страница 23: ...07C F Installation Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 23 A150504 Fig 16 Connection Wiring Diagram 208...

Страница 24: ...707C F Installation Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 24 A150514 Fig 17 Ladder Wiring Diagram 208 23...

Страница 25: ...707C F Installation Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 25 A150505 Fig 18 Connection Wiring Diagram 46...

Страница 26: ...C 707C F Installation Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 26 A150515 Fig 19 Ladder Wiring Diagram 460...

Страница 27: ...bulb indoor condition Where a dash appears do not attempt to check charge or charge unit under these conditions using the superheat method Weigh in method should be used A150625 To properly check or...

Страница 28: ...ation in blower compartment d Ensure proper reassembly by marking blower wheel and motor in relation to blower housing before disassembly e Loosen setscrew s that secures wheel to motor shaft remove s...

Страница 29: ...pose the fan blade 3 Inspect the fan blades for cracks or bends 4 If fan needs to be removed loosen the setscrew and slide the fan off the motor shaft 5 When replacing fan blade position blade as show...

Страница 30: ...ditional safety hazards For models that have a scroll compressor the compressor pumps refrigerant throughout the system by the interaction of a stationary and an orbiting scroll The scroll compressor...

Страница 31: ...rough the louvered openings in the unit base 4 Perform required service 5 Remove and dispose of any oil contaminated material per local codes Liquid Line Filter Drier The filter drier is specifically...

Страница 32: ...rigerant evacuate system and recharge to capacities shown on rating plate Defective compressor Replace and determine cause Insufficient line voltage Determine cause and correct Blocked outdoor coil De...

Страница 33: ...ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS CHECK THAT INDOOR EVAPORATOR AIR FILTER IS CLEAN AND IN PLACE VERIFY THAT UNIT INSTALLATION IS LEVEL CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN H...

Страница 34: ...Street Indianapolis IN 46231 Edition Date 01 20 Catalog No II707C 17 Replaces II707C 16I 707C C 707C F Installation Instructions Manufacturer reserves the right to change at any time specifications an...

Отзывы: