Guide specifications
GENERAL
System Description
Outdoor-mounted, air-cooled, split-system heat pump unit
suitable for ground or rooftop installation. Unit consists of a
hermetic compressor, an air-cooled coil, propeller-type
condenser fan, and a control box. Unit will discharge supply air
upward as shown on contract drawings. Unit will be used in a
refrigeration circuit to match up to a packaged fan coil or coil
unit.
Quality Assurance
Unit will be rated in accordance with the latest edition of ARI
Standard 240.
Unit will be certified for capacity and efficiency, and listed in
the latest ARI directory.
Unit construction will comply with latest edition of ANSI/
ASHRAE and with NEC.
Unit will be constructed in accordance with UL standards and
will carry the UL label of approval. Unit will have C-UL approval.
Unit cabinet will be capable of withstanding Federal Test
Method Standard No. 141 (Method 6061) 500-hr salt spray
test.
Air-cooled condenser coils will be leak tested at 217 psig and
pressure tested at 450 psig.
Delivery, Storage, and Handling
Unit will be shipped as single package only and is stored and
handled per unit manufacturer’s recommendations.
Warranty (for inclusion by specifying engineer)
U.S. and Canada only.
PRODUCTS
Equipment
Factory assembled, single piece, air-cooled heat pump unit.
Contained within the unit enclosure will be all factory wiring,
piping, controls, compressor, refrigerant charge (Puron®), and
special features required prior to field start-up.
Unit Cabinet
Unit cabinet will be constructed of galvanized steel,
bonderized, and coated with a powder coat paint.
Fans
Condenser fan will be direct-drive propeller type, discharging
air upward.
Condenser fan motors will be totally enclosed, 1-phase type
with class B insulation and permanently lubricated bearings.
Shafts will be corrosion resistant.
Fan blades will be statically and dynamically balanced.
Condenser fan openings will be equipped with steel wire
safety guards.
Compressor
Compressor will be hermetically sealed.
Compressor will be mounted on rubber vibration isolators.
Condenser Coil
Condenser coil will be air cooled.
Coil will be constructed of aluminum fins mechanically
bonded to copper tubes which are then cleaned, dehydrated,
and sealed.
Refrigeration Components
Refrigeration circuit components will include liquid tube
shutoff valve with sweat connections, suction tube shutoff
valves with sweat connections, system charge of Puron®
refrigerant, POE compressor oil, accumulator, and reversing
valve.
Operating Characteristics
The capacity of the unit will meet or exceed
Btuh at a
suction temperature of
°F. The power consumption at full
load will not exceed
kW.
Combination of the unit and the evaporator or fan coil unit
will have a total net cooling capacity of
Btuh or greater at
conditions of
CFM entering air temperature at the
evaporator at
°F wet bulb and
°F dry bulb, and air
entering the unit at
°F.
The system will have a SEER of
Btuh/watt or greater at
DOE conditions.
Electrical Requirements
Nominal unit electrical characteristics will be
v,
phase, 60 hz. The unit will be capable of satisfactory
operation within voltage limits of
v to
v.
Unit electrical power will be single point connection.
Control circuit will be 24v.
Special Features
Refer to section of this literature identifying accessories and
descriptions for specific features and available enhancements.
Air-Cooled, Split-System
Heat Pump
698B
2 to 5 Tons Nominal