background image

8

c. Inspect all field-- and factory--wiring connections. Be

sure that connections are completed and tight.

d. Ensure wires do not touch refrigerant tubing or sharp

sheet metal edges.

e. Inspect coil fins. If damaged during shipping and

handling, carefully straighten fins with a fin comb.

4. Verify the following conditions:

a. Make sure that outdoor--fan blade is correctly positioned

in fan orifice. Top edge of blade should be 3.125 in.(79
mm) down from outdoor coil outlet grille (size

024--048, See Fig. 19) or hub should be 0.708--in. (18
mm) away from motor end bell (size 060, See Fig. 19).

See Outdoor Fan Adjustment section.

b. Make sure that air filter is in place.

c. Make sure that condensate drain pan and trap are filled

with water to ensure proper drainage.

d. Make sure that all tools and miscellaneous loose parts

have been removed.

START--UP

Step 1 — Check for Refrigerant Leaks

Proceed as follows to locate and repair a refrigerant leak and to
charge the unit:

1. Locate leak and make sure that refrigerant system pressure

has been relieved and reclaimed from both high-- and

low--pressure ports.

2. Repair leak following accepted practices.

NOTE

: Install a filter drier whenever the system has been opened

for repair.

Step 2 — Start--Up Cooling and Make Adjust-

ments

Complete the required procedures given in the Pre--Start--Up

section before starting the unit. Do not jumper any safety devices
when operating the unit. Do not operate the unit in cooling mode

when the outdoor temperature is below 40

°

F (4.4

°

C) (unless

accessory low--ambient kit is installed). Do not rapid cycle the

compressor. Allow 5 min. between “on” cycles to prevent

compressor damage.
CHECKING

COOLING

AND

HEATING

CONTROL

OPERATION
Start and check the unit for proper cooling control operation as

follows:

1. Place room thermostat SYSTEM switch in OFF position.

Observe that blower motor starts when FAN switch is
placed in ON position and shuts down within 60 sec. (for

024--042) or 90 seconds (for 048 and 060) when FAN
switch is placed in AUTO position.

2. Place SYSTEM switch in COOL position and FAN switch

in AUTO position. Set control below room temperature.
Observe that compressor, outdoor fan, and indoor blower

motors start and that reversing valve shifts. Observe that
cooling cycle shuts down when control setting is satisfied.

Reversing valve (RV) remains energized.

3. Place system switch in HEAT position. Observe that

compressor, indoor fan and outdoor fan energize (Reversing
Valve is deenergized in heat pump heating mode). Set
control above room temperature. Observe that heating cycle

shuts down when control setting is satisfied.

4. When using an automatic changeover room thermostat,

place both SYSTEM and FAN switches in AUTO positions.

Observe that unit operates in Cooling mode when
temperature control is set to call for Cooling (below room
temperature), and unit operates in Heating mode when

temperature control is set to call for Heating (above room
temperature).

Step 3 — Refrigerant Charge

Refrigerant Charge — Amount of refrigerant charge is listed on
unit nameplate and in Table 1. Refer to Bryant Refrigerant Service

Techniques Manual, Refrigerants section. Unit panels must be in
place when unit is operating during charging procedure. Unit must

operate a minimum of 15 minutes before checking charge.
NO CHARGE
Refer to Bryant Refrigerant Service Techniques. Use standard

evacuating techniques. After evacuating system, weigh in the
specified amount of refrigerant (refer to Table 1).
LOW CHARGE COOLING
024--042 units:

1. Measure suction line pressure by attaching a gauge to the

service port.

2. Measure the suction line temperature by attaching a

temperature sensing device to it.

3. Insulate the temperature sensing device so that the outdoor

ambient doesn’t affect the reading.

4. Locate the measured suction line pressure in the top row of

Table 5 and the measured outdoor ambient temperature in
the left column of the table. Based on the two values,

determine the required suction line temperature.

5. If the measured suction line temperature is greater than the

tabulated temperature, add charge in the system.

048 and 060 units:

1. Measure discharge line pressure by attaching a gauge to the

service port.

2. Measure the liquid line temperature by attaching a

temperature sensing device to it.

3. Insulate the temperature sensing device so that the outdoor

ambient doesn’t affect the reading.

4. Refer to the required subcooling in Tables 3 to find the

required subcooling based on the model size and the
outdoor ambient temperature.

5. Interpolate if the outdoor temperature lies in between the

table values. Extrapolate if the temperature lies beyond the
table range.

6. Find the pressure value corresponding to the measured

pressure on the compressor discharge line.

7. Read across from the pressure reading to obtain the Liquid

line temperature for a required subcooling.

8. Add charge if the measured temperature is higher than the

liquid line temperature value in the table.

9. Add charge using the service connection on the suction line

of the compressor.

HEATING MODE CHARGE
Do not attempt to adjust charge by cooling methods while in heat

pump heating mode. Recover refrigerant and weigh in according to

unit data plate refrigerant data.

664B

Содержание 664B

Страница 1: ...ires 6 Accessory Electric Heat Wiring 6 PRE START UP 7 START UP 8 17 Check for Refrigerant Leaks 8 Start Up Cooling and Make Adjustments 8 Checking Cooling and Heating Control Operation 8 Refrigerant...

Страница 2: ...iginal packages until installation Step 2 Provide Unit Support For hurricane tie downs contact distributor for details and PE Professional Engineering Certificate if required SLAB MOUNT Place the unit...

Страница 3: ...CONFIGURING UNITS FOR DOWNFLOW VERTICAL DISCHARGE ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death Before performing service or maintenance operations on...

Страница 4: ...4 A08414 Fig 5 Unit Base Dimensions 664B024 060 664B...

Страница 5: ...2 21 2 21 Face Area sq ft 11 1 12 7 15 8 15 8 13 3 15 8 CONDENSER FAN Propeller Nominal Cfm 2600 2600 3200 3200 3200 3300 Diameter in mm 20 508 20 508 20 508 20 508 20 508 20 508 Motor HP RPM 1 8 825...

Страница 6: ...e unit must have a separate electrical service with a field supplied waterproof disconnect switch mounted at or within sight from the unit Refer to the unit rating plate NEC and local codes for maximu...

Страница 7: ...erant system is under pressure 4 Do not use torch to remove any component System contains oil and refrigerant under pressure 5 To remove a component wear protective goggles and proceed as follows a Sh...

Страница 8: ...mperature Observe that heating cycle shuts down when control setting is satisfied 4 When using an automatic changeover room thermostat place both SYSTEM and FAN switches in AUTO positions Observe that...

Страница 9: ...change motor speeds reposition wire at fan motor speed terminals labeled 1 2 3 4 refer to Fig 12 Remove the speed tap connector labeled 1 through 5 on the motor While looking at the connector end that...

Страница 10: ...r a 5 minute time delay in case of an initial start up starting the compressor low stage and the outdoor fan motor If the low stage operation cannot satisfy the cooling demand the second stage cooling...

Страница 11: ...11 A08209 Fig 13 Typical Single Phase Unit Electrical Diagram Sizes 024 042 664B...

Страница 12: ...12 A06405 Fig 14 Typical Single Phase Unit Electrical Diagram Sizes 048 060 664B...

Страница 13: ...13 A06325 Fig 15 Typical Three Phase Unit Electrical Diagram Sizes 030 042 664B...

Страница 14: ...14 A06326 Fig 16 Typical Three Phase Unit Electrical Diagram Sizes 048 060 664B...

Страница 15: ...15 A05209 Fig 17 Single Phase Accessory Electric Heater Wiring A06327 Fig 18 Three Phase Accessory Electric Heater Wiring 664B...

Страница 16: ...6 289 CFM 1164 1122 1066 1025 954 906 3 Watts 386 398 409 418 425 435 438 441 451 CFM 1680 1652 1625 1583 1555 1515 1477 1444 1403 4 Watts 440 448 457 462 469 477 480 485 486 CFM 1745 1717 1684 1651 1...

Страница 17: ...ter s each month Clean or replace when necessary 2 Inspect indoor coil drain pan and condensate drain each cooling season for cleanliness Clean when necessary 3 Inspect blower motor and wheel for clea...

Страница 18: ...from the hub of the wheel d Remove the filler panel at the discharge end of the blower housing by removing the two screws that fasten it to the housing e Remove the wheel form the housing 3 Remove the...

Страница 19: ...ned connections are noticed disassemble the connection clean all the parts re strip the wire end and reassemble the connection properly and securely Check to ensure no wires are touching refrigerant t...

Страница 20: ...back to the compressor C95045 Fig 20 Typical Heat Pump Operation Heating Mode STRAINER ACCUMULATOR COMPRESSOR STRAINER LCS OUTDOOR COIL INDOOR COIL A B D C Check Valves A Closed B Open C Closed D Ope...

Страница 21: ...line voltage Determine cause and correct Blocked outdoor coil Determine cause and correct Defective run start capacitor overload or start relay Determine cause and replace Faulty outdoor fan motor or...

Страница 22: ...r Temperature __________ DB ____________WB Return Air Temperature __________ DB __________ WB Cooling Supply Air __________DB___________WB PRESSURES Cooling Mode Refrigerant Suction __________ psig Su...

Отзывы: