background image

9

POWER
SUPPLY

FIELD-SUPPLIED
FUSED DISCONNECT

HIGH VOLTAGE
POWER LEADS
(SEE UNIT WIRING
LABEL

)

)

EQUIP GR

CONTROL BOX

LOW-VOLTAGE
POWER LEADS
(SEE UNIT
WIRING LABEL)

W1

Y

G

R

C

WHT(W1)

YEL(Y)

GRN(G)

RED(R)

BRN(C)

THERMOSTAT
(TYPICAL)

ORN(O)

3-PHASE SHOWN
1-PHASE USES 
TWO POWER 
LEADS

 

W2

VIO (W2)

O

SPLICE BOX

A08186

Fig. 8 -- High-- and Control--Voltage Connections

Single phase units:

1. Run the high--voltage (L1, L2) and ground lead into the

control box.

2. Connect ground lead to chassis ground connection.
3. Locate the black and yellow wires connected to the line side

of the contactor.

4. Connect field L1 to black wire on connection 11 of the

compressor contactor.

5. Connect field wire L2 to yellow wire on connection 23 of

the compressor contactor.

Three--phase units:

1. Run the high--voltage (L1, L2, L3) and ground lead into the

control box.

2. Connect ground lead to chassis ground connection.
3. Locate the black and yellow wires connected to the line side

of the contactor.

4. Connect field L1 to black wire on connection 11 of the

compressor contactor.

5. Connect field wire L3 to yellow wire on connection 13 of

the compressor contactor.

6. Connect field wire L2 to blue wire from compressor.

Special Procedures for 208--V Operation

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal

injury or death.
Before installing or servicing system, always turn off main

power to system. Tag the disconnect switch with a suitable

warning label. With disconnect switch open, move black

wire from transformer (3/16 in.) terminal marked 230 to

terminal marked 208. This retaps transformer to primary

voltage of 208 vac.

!

WARNING

Control Voltage Connections

NOTE

: Do not use any type of power--stealing thermostat. Unit

control problems may result.
Use no. 18 American Wire Gage (AWG) color--coded, insulated

(35

°

C minimum) wires to make the control voltage connections

between the thermostat and the unit. If the thermostat is located

more than 100 ft (30.5 m) from the unit (as measured along the

control voltage wires), use no. 16 AWG color--coded, insulated
(35

°

C minimum) wires.

Standard Connections

Locate the seven low voltage thermostat leads in 24 volt splice

box. See Fig. 8 for connection diagram. Run the low--voltage leads
from the thermostat, through the control wiring inlet hole grommet

(Fig. 2 and 3), and into the low--voltage splice box. Provide a drip
loop before running wires through panel. Secure and strain relief

all wires so that they do not interfere with operation of unit.
If an accessory electric heater is installed, low voltage leads from

heater must be connected to factory supplied control leads from

Indoor Fan Board P4 connector. Factory wires are provided for
electric heat staging W1 and W2 (W2 and W3 on IFB). If room

thermostat has only one stage of supplemental heat, connect white
and violet wires shown in Fig. 8 to second stage heat field wire.
Some electric heaters have four control wires (plus common wire).

Consult unit wiring diagram and electric heater wiring diagram for
additional details.

Transformer Protection

The transformer is of the energy--limiting type. It is set to withstand

a 30--second overload or shorted secondary condition. If an
overload or short is present, correct overload condition and check

for blower fuse on control board. Replace fuse as required with
correct size and rating.

Accessory Electric Heaters Installation

Electric heaters may be installed with the 607C units per

instructions supplied with electric heater package. See unit rating
plate for factory--approved electric heater kits.

607C Sequence of Operation

a. CONTINUOUS FAN

(1.) Thermostat closes circuit R to G energizing the

blower motor for continuous fan.

b. COOLING MODE

(1.) If indoor temperature is above temperature set

point, thermostat closes circuits R to G, R to Y and
R to O--The unit delivers cooling airflow.

c. ELECTRIC HEATING MODE

(1.) Thermostat closes circuit R to W/W1, or W2 and R

to G. There are no on or off delays.

d. HEAT PUMP HEATING MODE

(1.) Thermostat closes circuits R to G and R to Y. The

compressor, indoor and outdoor fans are energized.

e. HEAT PUMP HEATING WITH AUXILIARY

ELECTRIC HEAT

(1.) Thermostat closes circuits R to G, R to Y and R to

W/W1 or W2. The compressor, indoor and outdoor
fans are energized, as well as the electric heat
relays.

f. DEFROST MODE

The defrost mode is automatically energized by the

defrost board during heating mode. The defrost board
energizes “O” (reversing valve) and “W2” (electric
heat). It also de--energizes the outdoor fan. When defrost

is complete, unit will return to heating mode. If room
thermostat is satisfied during defrost, unit will shut

down and restart in defrost on next call for heat.

607C

Содержание 607C024

Страница 1: ...Piston 21 Pressure Switches 22 Loss of Charge Switch 22 High Pressure Switch 22 Copeland Scroll compressor Puron Refrigerant 22 C99062 Fig 1 Unit 607C Refrigerant System 22 Refrigerant 22 Compressor...

Страница 2: ...The slab should extend approximately 2 in 51 mm beyond the casing on all 4 sides of the unit Do not secure the unit to the slab except when required by local codes Ground Mount The unit may be install...

Страница 3: ...he brackets to the unit PROPERTY DAMAGE HAZARD Failure to follow this warning could result in personal injury death or property damage Rigging bracket MUST be under the rain lip to provide adequate li...

Страница 4: ...4 A08084 Fig 2 607C024 030 Unit Dimensions 607C...

Страница 5: ...5 A08085 Fig 3 607C036 060 Unit Dimensions 607C...

Страница 6: ...c heaters require 90 degree elbow in supply duct WARNING When designing and installing ductwork consider the following 1 All units should have field supplied filters or accessory filter rack installed...

Страница 7: ...BTyp Supply opening B x C Long Support D 445 16 Return opening B X C Insulated deck pan Short Support CTyp bracket 1126 mm C00076 UNIT SIZE CATALOG NUMBER A IN MM B IN MM C IN MM D IN MM 607C024 030...

Страница 8: ...ield supplied 3 4 in PVC or field supplied 3 4 in copper pipe at outlet end of the 2 in 51 mm trap See Fig 11 Do not undersize the tube Pitch the drain trough downward at a slope of at least 1 in 25 m...

Страница 9: ...rmostat through the control wiring inlet hole grommet Fig 2 and 3 and into the low voltage splice box Provide a drip loop before running wires through panel Secure and strain relief all wires so that...

Страница 10: ...0 11x10 279x254 3 4 1400 11x10 279x254 3 4 1600 11x10 279x254 1 0 1750 11x10 279x254 1 0 HIGH PRESSURE SWITCH psig Cutout Reset Auto 650 15 420 25 LOSS OF CHARGE LOW PRESSURE SWITCH Liquid Line psig C...

Страница 11: ...11 Duct Covers C00092 Fig 10 607C with Duct Covers On Shown with optional louvers 1 25 mm MIN 2 51 mm MIN TRAP OUTLET A08001 Fig 11 Condensate Trap 607C...

Страница 12: ...12 A08024 Fig 12 Wiring Schematics 208 230 1 60 607C...

Страница 13: ...13 A08025 Fig 13 Wiring Schematics 208 230 3 60 607C...

Страница 14: ...14 A08026 Fig 14 Wiring Diagram 460 3 60 607C...

Страница 15: ...the unit for proper control operation as follows 1 Place room thermostat SYSTEM switch or MODE control in OFF position Observe that blower motor starts when FAN mode is placed in FAN ON position and s...

Страница 16: ...efrigerant leak refer to Check for Refrigerant Leaks section Indoor Airflow and Airflow Adjustments All 607C blower motors are factory wired for nominal cooling airflow operation at minimum external s...

Страница 17: ...control which includes a field selectable time period DIP switch 1 and 2 on the board between defrost cycles of 30 60 90 or 120 minutes factory set at 60 minutes To initiate a forced defrost two optio...

Страница 18: ...eplace the filter with the same dimensional size and type as originally installed See Table 1 for recommended filter sizes Inspect air filter s at least once each month and replace throwaway type or c...

Страница 19: ...2292 2238 2158 2049 1935 1840 1732 1635 1513 Air delivery values are without air filter and are for dry coil See 607C Wet Coil Pressure Drop Table 1 Factory shipped cooling heat pump heating speed NOT...

Страница 20: ...ith a mild detergent and water solution Rinse coils with clear water using a garden hose Be careful not to splash water on motors insulation wiring or air filter s For best results spray condenser coi...

Страница 21: ...ontrols and wiring replace all the panels Start the unit and observe at least one complete cooling cycle to ensure proper operation If discrepancies are observed in operating cycle or if a suspected m...

Страница 22: ...amic suction or discharge valves and it is more tolerant of stresses caused by debris liquid slugging and flooded starts The compressor is equipped with an internal pressure relief port The pressure r...

Страница 23: ...evice wired into control circuit low voltage It shuts off the compressor if abnormally low pressures are present in the refrigeration circuit NOTE Because these switches are attached to refrigeration...

Страница 24: ...driers with rated working pressures less than 600 psig S Do not leave Puron suction line filter driers in line longer than 72 hours S Do not install a suction line filter drier in liquid line S POE o...

Страница 25: ...Defective run start capacitor overload or start relay Determine cause and replace Defective thermostat Replace thermostat Faulty condenser fan motor or capacitor Replace Restriction in refrigerant sys...

Страница 26: ...OLTAGE __________________________________ COMPRESSOR AMPS_________________________________ INDOOR EVAPORATOR FAN AMPS___________ TEMPERATURES OUTDOOR CONDENSER AIR TEMPERATURE ___________DB RETURN AIR...

Отзывы: