background image

ICM QUICK REFERENCE GUIDE

c01034

EASY SELECT

HEATER/MOTOR

AUX HEAT KW/CFM

0-30

1075

SEC1

SEC2

J1

AC/HP SIZE

036

030

024

018

AC

HP-COMFORT

HP-EFF

NOM

HI

ENH

LO

SYSTEM TYPE

AC/HP CFM ADJUST

ON/OFF DELAY

CONTINUOUS FAN

MED

HI

YEL

LO

AUX1

HUM1

AUX2

24VAC

GRY

HUM2

YEL

WHT

BLK

ORN

BLU

VIO

0-20

875

0-10

725

0

90

30
90

0
0

0-5

625

TM

J2

D

H

R
W

1

W

2

Y

1

Y/Y

2

G
O
C

QUICK REFERENCE GUIDE

SET-UP INSTRUCTIONS FOR WARMER HEATING TEMPERATURES

AND SUPER HUMIDITY CONTROL IN COOLING

     A.  AUX HEAT - Set for heater size (Ex: 0-10 for 10 kw)
     B.  AC/HP SIZE - Set for size of outdoor unit
     C.  SYSTEM TYPE - Select "HP COMFORT"
     D.  AC/HP CFM ADJUST - Select "LO"
     E.  ON/OFF DELAY - Select "ENH"
     F.  CONTINUOUS FAN - Select desired speed
2.  Remove Jumper J1 to activate all dehumidify modes.
3.  Complete wiring and install outdoor temperature sensor

     according to Installation Instructions.

1.  Configuration Taps

     (See Installation Instructions, for detailed description.)

     •  Option 5 (Variable Speed Motors) - set to ON
     •  Option 7 (Super Dehumidify) - set to ON
     •  Option 12 (Heaters during Defrost) - setting "2" is
         suggested for all heaters
     •  Option 16 - Heat pump systems set to ON for warmer heat
         below 40

°

 F.

     •  Option 17 - Select programmable or non-programmable mode.

2.  Thermidistat Control Configurations

     (See Thermidistat™ Control Installation Instructions for

     detailed description.)

3.  Set desired humidity level on front of Thermidistat
     (50 to 55% RH recommended).  For dehumidification in
     cooling, both "dhu" and "cool" must be displayed.

1.  Set "DIP Switches" - Set the dip switches (back of Thermidistat

     Control Board) appropriately for specific system being installed.

EASY SELECT BOARD

THERMIDISTAT™ CONTROL SETTINGS

9 PIN CONNECTOR

ICM PRINTED CIRCUIT BOARD

12 PIN CONNECTOR

A

B

C

D

E

F

TABLE 24—TROUBLESHOOTING CHART

SYSTEM

CAUSE

REMEDY

IFM does not run

Blower wheel not secured to shaft

Inspect and properly tighten blower wheel to shaft

Insufficient voltage at motor

Determine cause and correct

Power connectors not properly seated

Connectors should snap easily; do not force

IFM operation is intermittent

Connectors not firmly seated

Gently pull wires individually

to be sure they are inserted

into the connectors

—28—

Содержание 602B

Страница 1: ...or all brazing operations WARNING Improper installation adjustment alter ation service maintenance or use can cause explosion fire electric shock or other occurrences which could cause serious injury...

Страница 2: ...from the installer s packet included with unit and install grommet in the knockout opening Provide a drip loop before running wire through panel Run the low voltage leads from the thermostat through...

Страница 3: ...t is desirable to allow system coils time to cool down in conjunction with the airflow in heating mode 3 A no delay option used for servicing unit or when a thermostat is utilized to perform delay fun...

Страница 4: ...energized If the installation includes the use of this operating mode do not use these terminals to control accessories See Electronic Air Cleaner and Humidifier sections for further information b EL...

Страница 5: ...onents used See Fig 8 a GAS HEAT CFM SELECT GAS HEAT INPUT SIZE Factory selected gas heat size should correspond to unit label b AC HP SIZE SELECT SYSTEM SIZE INSTALLED Factory selected air conditione...

Страница 6: ...stem size please verify 3 SYSTEM TYPE Factory selected on 683B system for HP EFF 4 AC HP CFM ADJUST Select NOM Lo for 060 5 ON OFF DELAY Select ENH profile 6 CONTINUOUS FAN Select desired fan speed wh...

Страница 7: ...Occurs if outdoor temperature is above outdoor temperature change over setpoint 1 Thermidistat closes circuit R to G and R to Y Y2 The unit delivers selected heat pump heating airflow g HEATING MODE...

Страница 8: ...rt This will minimize cold blow in heat pump operation 602B only and could enhance system efficiency f CONTINUOUS FAN SELECT DESIRED FAN SPEED WHEN THERMOSTAT IS SET ON CONTINUOUS FAN 1 LO speed Facto...

Страница 9: ...it board provides connection terminals for use of a standard humidistat The unit will detect the humidistat contacts opening on increasing humidity and reduce its airflow to approximately 80 percent o...

Страница 10: ...y minimal If a substantial adjustment is indicated an abnormal condition exists somewhere in the cooling system such as insuf ficient airflow across either one or both coils I 583B START UP ICM FIOP C...

Страница 11: ...switches in AUTO positions Observe that unit operates in heating mode when tempera ture control is set to call for heating above room temperature and operates in cooling mode when tempera ture contro...

Страница 12: ...ide assembly out Be careful not to tear insulation in blower compartment e Ensure proper reassembly by marking blower wheel and motor in relation to blower housing before disassembly TABLE 1 ICM FIOP...

Страница 13: ...Quantity lb 9 5 9 5 9 5 10 0 10 0 10 0 REFRIGERANT METERING DEVICE Orifice ID in Check Flo Rater Piston 073 073 073 086 086 086 CONDENSER COIL Rows Fins in Face Area sq ft 2 17 12 3 2 17 12 3 2 17 12...

Страница 14: ...Fig 14 ICM FIOP Electric Schematic Unit 583B C01035 14...

Страница 15: ...OUTDOOR FAN Nominal Cfm Diameter in Motor Hp Rpm 2350 22 1 8 825 2350 22 1 8 825 2350 22 1 8 825 2500 22 1 4 1100 2500 22 1 4 1100 2350 22 1 8 825 2350 22 1 8 825 INDOOR COIL Rows Fins in Face Area sq...

Страница 16: ...7 INDOOR BLOWER Nominal Airflow Cfm Size in Motor HP 1600 11 X 10 3 4 1600 11 X 10 3 4 1600 11 X 10 3 4 1750 11 X 10 1 0 1750 11 X 10 1 0 1750 11 X 10 1 0 FURNACE SECTION Burner Orifice No Qty Drill S...

Страница 17: ...Fig 15 ICM FIOP Electric Schematic Unit 683B C01101 17...

Страница 18: ...7 12 3 2 17 12 3 2 17 16 4 CONDENSER FAN Nominal Cfm Diameter in Motor Hp Rpm 2350 22 1 8 825 2350 22 1 8 825 2350 22 1 8 825 2350 22 1 8 825 3300 22 1 4 1100 3300 22 1 4 1100 EVAPORATOR COIL Rows Fin...

Страница 19: ...50 50 60 70 80 90 042 208 230 1 60 187 253 18 6 105 0 0 9 6 8 3 8 5 0 5 4 7 2 7 5 10 0 11 3 15 0 15 0 20 0 18 1 20 8 25 9 30 0 36 1 41 7 54 2 62 5 72 2 83 3 31 0 31 0 31 1 34 5 40 9 46 0 53 6 60 6 76...

Страница 20: ...Fig 16 ICM FIOP Electrical Schematic 702B C01037 20...

Страница 21: ...IL Rows Fins in face area sq ft 2 17 8 5 2 17 10 3 2 17 10 3 2 17 13 5 2 17 13 5 2 17 15 4 OUTDOOR FAN Nominal Airflow CFM Diameter Motor HP RPM 2350 22 1 8 825 2350 22 1 8 825 2800 22 1 4 1100 2500 2...

Страница 22: ...40 40 60 60 70 80 80 90 100 110 042 208 230 1 60 187 253 22 4 105 0 0 9 6 8 3 8 5 0 5 4 7 2 7 5 10 0 11 3 15 0 15 0 20 0 18 1 20 8 25 9 30 0 36 1 41 7 54 2 62 5 72 2 83 3 35 7 35 7 58 3 61 7 68 1 73 2...

Страница 23: ...Fig 17 ICM FIOP Electrical Schematic 602B c01036 23...

Страница 24: ...n selections deliver equal airflow TABLE 12 583B 683B COOLING AND HEAT PUMP HEATING 683B ONLY DRY COIL ICM AIRFLOW LARGE CABINET UNIT SIZE CFM ADJUST PIN SELECT LO PIN NOM PIN HI PIN EXTERNAL STATIC P...

Страница 25: ...1600 53 35 65 170 130 1750 54 40 70 175 060 90 1600 41 25 55 155 115 1600 53 35 65 170 130 1800 53 40 70 175 TABLE 16 702B 602B COOLING HEATING DRY COIL ICM AIRFLOW SMALL CABINET UNIT SIZE CFM ADJUST...

Страница 26: ...N WG SMALL CABINET STATIC CFM 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 5 kW 0 00 0 00 0 00 0 00 0 00 0 00 0 00 0 00 0 02 0 04 0 06 0 07 7 5 kW 0 00 0 00 0 00 0 00 0 00 0 00 0 02 0 03 0 0...

Страница 27: ...60 0 029 0 032 0 036 0 040 0 045 0 049 0 053 TABLE 22 FILTER PRESSURE DROP TABLE IN WG FILTER SIZE CFM 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 20 X 20...

Страница 28: ...Super Dehumidify set to ON Option 12 Heaters during Defrost setting 2 is suggested for all heaters Option 16 Heat pump systems set to ON for warmer heat below 40 F Option 17 Select programmable or no...

Страница 29: ...TDOOR CONDENSER AIR TEMPERATURE ___________DB RETURN AIR TEMPERATURE ___________DB ___________WB COOLING SUPPLY AIR ___________DB ___________WB HEAT PUMP SUPPLY AIR ___________ GAS HEAT SUPPLY AIR ___...

Страница 30: ...2001 Bryant Heating Cooling Systems 7310 W Morris St Indianapolis IN 46231 30 Printed in U S A ii583b243 Catalog No 5358 308...

Отзывы: