TABLE 17—702B/602B COOLING & HEATING DRY COIL ICM AIRFLOW

LARGE CABINET

UNIT

SIZE

CFM ADJUST

PIN SELECT

LO PIN

NOM PIN

HI PIN

EXTERNAL STATIC

PRESSURE RANGE

0.1–1.0

0.1–1.0

0.1–1.0

042

COOLING †

1100

1225

1410

COOLING

DEHUMIDIFY

980

980

1125

HEAT PUMP

COMFORT (602B Only)

990

1100

1265

048

COOLING †

1260

1400

1610

COOLING

DEHUMIDIFY

1120

1120

1290

HEAT PUMP

COMFORT (602B Only)

1135

1260

1450

060

COOLING †

1575

1750

2010

COOLING

DEHUMIDIFY

1400

1400

1610

HEAT PUMP

COMFORT (602B Only)

1415

1575

1810

Heat Pump Efficiency and Cooling pin selections deliver equal airflow

TABLE 18—MINIMUM AIRFLOW FOR RELIABLE ELECTRIC HEATER OPERATION (CFM)

UNIT

SIZE

024

030

036

042

048

060

602B

750

1025

1250

1285

1710

1800

702B

750

750

1250

1205

1500

1800

TABLE 19—ELECTRIC HEAT PRESSURE DROP TABLE (IN. WG)

SMALL CABINET

STATIC

CFM

500

600

700

800

900

1000

1100

1200

1300

1400

1500

1600

5 kW

0.00

0.00

0.00

0.00

0.00

0.00

0.00

0.00

0.02

0.04

0.06

0.07

7.5 kW

0.00

0.00

0.00

0.00

0.00

0.00

0.02

0.03

0.05

0.07

0.08

0.09

10 kW

0.00

0.00

0.00

0.00

0.00

0.02

0.04

0.06

0.07

0.09

0.10

0.11

15 kW

0.00

0.00

0.00

0.02

0.04

0.06

0.08

0.10

0.12

0.14

0.16

0.18

20 kW

0.00

0.00

0.02

0.04

0.06

0.08

0.09

0.11

0.13

0.15

0.17

0.19

TABLE 20— ELECTRIC HEAT PRESSURE DROP TABLE (IN. WG)

LARGE CABINET

STATIC

CFM

1100

1200

1300

1400

1500

1600

1700

1800

1900

2000

2100

2200

2300

2400

2500

5 kW

0.00

0.00

0.00

0.01

0.02

0.03

0.04

0.05

0.06

0.07

0.08

0.09

0.10

0.11

0.12

7.5 kW

0.00

0.00

0.01

0.02

0.03

0.04

0.05

0.06

0.07

0.08

0.09

0.10

0.11

0.12

0.13

10 kW

0.00

0.00

0.01

0.02

0.03

0.04

0.05

0.06

0.07

0.08

0.09

0.10

0.11

0.12

0.13

15 kW

0.00

0.02

0.03

0.04

0.05

0.06

0.07

0.08

0.09

0.10

0.11

0.12

0.13

0.14

0.15

20 kW

0.02

0.03

0.04

0.05

0.06

0.07

0.08

0.09

0.10

0.11

0.12

0.13

0.14

0.15

0.16

—26—

Содержание 602B

Страница 1: ...or all brazing operations WARNING Improper installation adjustment alter ation service maintenance or use can cause explosion fire electric shock or other occurrences which could cause serious injury...

Страница 2: ...from the installer s packet included with unit and install grommet in the knockout opening Provide a drip loop before running wire through panel Run the low voltage leads from the thermostat through...

Страница 3: ...t is desirable to allow system coils time to cool down in conjunction with the airflow in heating mode 3 A no delay option used for servicing unit or when a thermostat is utilized to perform delay fun...

Страница 4: ...energized If the installation includes the use of this operating mode do not use these terminals to control accessories See Electronic Air Cleaner and Humidifier sections for further information b EL...

Страница 5: ...onents used See Fig 8 a GAS HEAT CFM SELECT GAS HEAT INPUT SIZE Factory selected gas heat size should correspond to unit label b AC HP SIZE SELECT SYSTEM SIZE INSTALLED Factory selected air conditione...

Страница 6: ...stem size please verify 3 SYSTEM TYPE Factory selected on 683B system for HP EFF 4 AC HP CFM ADJUST Select NOM Lo for 060 5 ON OFF DELAY Select ENH profile 6 CONTINUOUS FAN Select desired fan speed wh...

Страница 7: ...Occurs if outdoor temperature is above outdoor temperature change over setpoint 1 Thermidistat closes circuit R to G and R to Y Y2 The unit delivers selected heat pump heating airflow g HEATING MODE...

Страница 8: ...rt This will minimize cold blow in heat pump operation 602B only and could enhance system efficiency f CONTINUOUS FAN SELECT DESIRED FAN SPEED WHEN THERMOSTAT IS SET ON CONTINUOUS FAN 1 LO speed Facto...

Страница 9: ...it board provides connection terminals for use of a standard humidistat The unit will detect the humidistat contacts opening on increasing humidity and reduce its airflow to approximately 80 percent o...

Страница 10: ...y minimal If a substantial adjustment is indicated an abnormal condition exists somewhere in the cooling system such as insuf ficient airflow across either one or both coils I 583B START UP ICM FIOP C...

Страница 11: ...switches in AUTO positions Observe that unit operates in heating mode when tempera ture control is set to call for heating above room temperature and operates in cooling mode when tempera ture contro...

Страница 12: ...ide assembly out Be careful not to tear insulation in blower compartment e Ensure proper reassembly by marking blower wheel and motor in relation to blower housing before disassembly TABLE 1 ICM FIOP...

Страница 13: ...Quantity lb 9 5 9 5 9 5 10 0 10 0 10 0 REFRIGERANT METERING DEVICE Orifice ID in Check Flo Rater Piston 073 073 073 086 086 086 CONDENSER COIL Rows Fins in Face Area sq ft 2 17 12 3 2 17 12 3 2 17 12...

Страница 14: ...Fig 14 ICM FIOP Electric Schematic Unit 583B C01035 14...

Страница 15: ...OUTDOOR FAN Nominal Cfm Diameter in Motor Hp Rpm 2350 22 1 8 825 2350 22 1 8 825 2350 22 1 8 825 2500 22 1 4 1100 2500 22 1 4 1100 2350 22 1 8 825 2350 22 1 8 825 INDOOR COIL Rows Fins in Face Area sq...

Страница 16: ...7 INDOOR BLOWER Nominal Airflow Cfm Size in Motor HP 1600 11 X 10 3 4 1600 11 X 10 3 4 1600 11 X 10 3 4 1750 11 X 10 1 0 1750 11 X 10 1 0 1750 11 X 10 1 0 FURNACE SECTION Burner Orifice No Qty Drill S...

Страница 17: ...Fig 15 ICM FIOP Electric Schematic Unit 683B C01101 17...

Страница 18: ...7 12 3 2 17 12 3 2 17 16 4 CONDENSER FAN Nominal Cfm Diameter in Motor Hp Rpm 2350 22 1 8 825 2350 22 1 8 825 2350 22 1 8 825 2350 22 1 8 825 3300 22 1 4 1100 3300 22 1 4 1100 EVAPORATOR COIL Rows Fin...

Страница 19: ...50 50 60 70 80 90 042 208 230 1 60 187 253 18 6 105 0 0 9 6 8 3 8 5 0 5 4 7 2 7 5 10 0 11 3 15 0 15 0 20 0 18 1 20 8 25 9 30 0 36 1 41 7 54 2 62 5 72 2 83 3 31 0 31 0 31 1 34 5 40 9 46 0 53 6 60 6 76...

Страница 20: ...Fig 16 ICM FIOP Electrical Schematic 702B C01037 20...

Страница 21: ...IL Rows Fins in face area sq ft 2 17 8 5 2 17 10 3 2 17 10 3 2 17 13 5 2 17 13 5 2 17 15 4 OUTDOOR FAN Nominal Airflow CFM Diameter Motor HP RPM 2350 22 1 8 825 2350 22 1 8 825 2800 22 1 4 1100 2500 2...

Страница 22: ...40 40 60 60 70 80 80 90 100 110 042 208 230 1 60 187 253 22 4 105 0 0 9 6 8 3 8 5 0 5 4 7 2 7 5 10 0 11 3 15 0 15 0 20 0 18 1 20 8 25 9 30 0 36 1 41 7 54 2 62 5 72 2 83 3 35 7 35 7 58 3 61 7 68 1 73 2...

Страница 23: ...Fig 17 ICM FIOP Electrical Schematic 602B c01036 23...

Страница 24: ...n selections deliver equal airflow TABLE 12 583B 683B COOLING AND HEAT PUMP HEATING 683B ONLY DRY COIL ICM AIRFLOW LARGE CABINET UNIT SIZE CFM ADJUST PIN SELECT LO PIN NOM PIN HI PIN EXTERNAL STATIC P...

Страница 25: ...1600 53 35 65 170 130 1750 54 40 70 175 060 90 1600 41 25 55 155 115 1600 53 35 65 170 130 1800 53 40 70 175 TABLE 16 702B 602B COOLING HEATING DRY COIL ICM AIRFLOW SMALL CABINET UNIT SIZE CFM ADJUST...

Страница 26: ...N WG SMALL CABINET STATIC CFM 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 5 kW 0 00 0 00 0 00 0 00 0 00 0 00 0 00 0 00 0 02 0 04 0 06 0 07 7 5 kW 0 00 0 00 0 00 0 00 0 00 0 00 0 02 0 03 0 0...

Страница 27: ...60 0 029 0 032 0 036 0 040 0 045 0 049 0 053 TABLE 22 FILTER PRESSURE DROP TABLE IN WG FILTER SIZE CFM 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 20 X 20...

Страница 28: ...Super Dehumidify set to ON Option 12 Heaters during Defrost setting 2 is suggested for all heaters Option 16 Heat pump systems set to ON for warmer heat below 40 F Option 17 Select programmable or no...

Страница 29: ...TDOOR CONDENSER AIR TEMPERATURE ___________DB RETURN AIR TEMPERATURE ___________DB ___________WB COOLING SUPPLY AIR ___________DB ___________WB HEAT PUMP SUPPLY AIR ___________ GAS HEAT SUPPLY AIR ___...