VI. BURNER IGNITION
Unit is equipped with a direct spark ignition 100% lockout
system. Ignition module is located in the control box. Module
contains a self-diagnostic LED. During servicing, refer to la-
bel diagram for LED interpretation.
If lockout occurs, unit may be reset by either momentarily
interrupting power supply to unit, or turning selector switch
to OFF position at the thermostat.
VII. MAIN BURNERS
At the beginning of each heating season, inspect for deterio-
ration or blockage due to corrosion or other causes. Observe
the main burner flames and adjust if necessary.
CAUTION:
When servicing gas train, do not hit or
plug orifice spuds.
A. Removal of Gas Train
1. Shut off manual gas valve.
2. Shut off power to unit.
3. Remove unit access panel. (See Fig. 32.)
4. Disconnect gas piping at unit gas valve.
5. Remove wires connected to gas valve. Mark each wire.
6. Remove ignitor and sensor wires at the ignitor module.
7. Remove the mounting screw that attaches the burner
rack to the basepan. (See Fig. 31.)
8. Slide the burner rack out of the unit. (See Fig. 31
and 34.)
9. To reinstall, reverse the procedure outlined above.
VIII. CONDENSER COIL, EVAPORATOR COIL, AND
CONDENSATE DRAIN PAN
Inspect the condenser coil, evaporator coil, and condensate
drain pan at least once each year.
The coils are easily cleaned when dry; therefore, inspect and
clean the coils either before or after each cooling season.
Remove all obstructions, including weeds and shrubs, that
interfere with the airflow through the condenser coil.
Straighten bent fins with a fin comb. If coated with dirt or
lint, clean the coils with a vacuum cleaner, using the soft brush
Fig. 32 — Unit Access Panel
BLOWER
HOUSING
2 SETSCREWS
(HIDDEN)
Fig. 33 — Removal of Motor and Blower Wheel
Fig. 34 — Burner Rack Removed
—31—