
Table 11A — Wet Coil Pressure Drop — 582A
UNIT SIZE
582A
AIRFLOW
(cfm)
PRESSURE DROP
(in. wg)
018
500
0.049
600
0.070
700
0.095
024
700
0.077
800
0.100
900
0.127
030
900
0.065
1000
0.080
1100
0.097
036
1100
0.084
1200
0.100
1300
0.177
042
1300
0.103
1400
0.120
1500
0.138
048
1500
0.088
1600
0.100
1700
0.113
060
1900
0.108
2000
0.120
2100
0.132
Table 11B — Wet Coil Pressure Drop — 583A
UNIT SIZE
583A
AIRFLOW
(cfm)
PRESSURE DROP
(in. wg)
024
700
0.0535
800
0.067
900
0.123
030
900
0.0687
1000
0.083
1100
0.150
036
1100
0.084
1200
0.100
1300
0.177
042
1300
0.099
1400
0.177
1500
0.204
048
1500
0.199
1600
0.137
1700
0.156
060
1900
0.108
2000
0.120
2100
0.132
D. Cooling Sequence of Operation
With the room thermostat SYSTEM switch in the COOL po-
sition and the FAN switch in the AUTO. position, the cooling
sequence of operation is as follows:
When the room temperature rises to a point that is slightly
above the cooling control setting of the thermostat, the ther-
mostat completes the circuit between thermostat terminal R
to terminals Y and G. These completed circuits through the
thermostat connect contactor coil (C) (through unit wire Y)
and blower relay coil (BR) (through unit wire G) across the
24-v secondary of transformer (TRAN).
The normally open contacts of energized contactor (C) close
and complete the circuit through compressor motor (COMP)
to condenser (outdoor) fan motor (OFM). Both motors start
instantly.
The set of normally open contacts of energized relay BR close
and complete the circuit through evaporator blower (indoor)
fan motor (IFM).
NOTE:
Once the compressor has started and then has stopped,
it should not be started again until 5 minutes have elapsed.
The cooling cycle remains ‘‘on’’ until the room temperature
drops to point that is slightly below the cooling control set-
ting of the room thermostat. At this point, the thermostat
‘‘breaks’’ the circuit between thermostat terminal R to termi-
nals Y and G. These open circuits deenergize contactor coil C
and relay coil BR. The condenser and compressor motors stop.
After a 30-second delay, the blower motor stops. The unit is
in a ‘‘standby’’ condition, waiting for the next ‘‘call for cool-
ing’’ from the room thermostat.
MAINTENANCE
To ensure continuing high performance, and to minimize the
possibility of premature equipment failure, periodic mainte-
nance must be performed on this equipment. This combina-
tion heating/cooling unit should be inspected at least once each
year by a qualified service person. To troubleshoot heating or
cooling of units, refer to tables at the back of the book.
NOTE TO EQUIPMENT OWNER:
Consult your local dealer
about the availability of a maintenance contract.
WARNING:
The ability to properly perform mainte-
nance on this equipment requires certain expertise, me-
chanical skills, tools, and equipment. If you do not pos-
sess these, do not attempt to perform any maintenance
on this equipment other than those procedures recom-
mended in the User’s Manual. FAILURE TO HEED THIS
WARNING COULD RESULT IN SERIOUS PERSONAL
INJURY
AND
POSSIBLE
DAMAGE
TO
THIS
EQUIPMENT.
WARNING:
Failure to follow these warnings could re-
sult in serious personal injury:
1. Turn off gas supply, then turn off electrical power to
the unit before performing any maintenance or serv-
ice on the unit.
2. Use extreme caution when removing panels and parts.
As with any mechanical equipment, personal injury
can result from sharp edges, etc.
3. Never place anything combustible either on, or in con-
tact with, the unit.
4. Should overheating occur, or the gas supply fail to
shut off, shut off the external main manual gas valve
to the unit, then shut off the electrical supply.
CAUTION:
Errors made when reconnecting wires may
cause improper and dangerous operation. Label all wires
prior to disconnection when servicing.
The minimum maintenance requirements for this equipment
are as follows:
1. Inspect air filter(s) each month. Clean or replace when
necessary.
2. Inspect indoor coil, drain pan, and condensate drain each
cooling season for cleanliness. Clean when necessary.
3. Inspect blower motor and wheel for cleanliness and check
lubrication each heating and cooling season. Clean when
necessary. For first heating season, inspect blower wheel
bimonthly to determine proper cleaning frequency.
—29—
Содержание 582A Series
Страница 26: ...Fig 29 Cooling Charging Chart 583A048 Units Fig 30 Cooling Charging Chart 583A060 Units 26 ...
Страница 36: ......
Страница 37: ......
Страница 39: ......