PRESSURES (CONT.)
j
VERIFY REFRIGERANT CHARGE USING CHARGING CHARTS
GENERAL
j
ECONOMIZER MINIMUM VENT AND CHANGEOVER SETTINGS TO JOB REQUIREMENTS (IF EQUIPPED)
j
VERIFY SMOKE DETECTOR UNIT SHUTDOWN BY UTILIZING MAGNET TEST
III. PERFECT HUMIDITY
t
SYSTEM START-UP
STEPS
j
1. CHECK CTB FOR JUMPER 5, 6, 7
JUMPER 5, 6, 7 MUST BE CUT AND OPEN
j
2. OPEN HUMIDISTAT CONTACTS
j
3. START UNIT IN COOLING (CLOSE Y1)
OBSERVE AND RECORD
A. SUCTION PRESSURE
PSIG
B. DISCHARGE PRESSURE
PSIG
C. ENTERING AIR TEMPERATURE
_
F
D. LIQUID LINE TEMPERATURE
AT OUTLET OR REHEAT COIL
_
F
E. CONFIRM CORRECT ROTATION FOR COMPRESSOR
F. CHECK FOR CORRECT RAMP−UP OF OUTDOOR FAN MOTOR AS CONDENSER COIL WARMS
j
4. CHECK UNIT CHARGE PER CHARGING CHART
j
5. SWITCH UNIT TO HIGH−LATENT MODE (SUBCOOLER) BY CLOSING HUMIDISTAT WITH Y1 CLOSED
OBSERVE
j
A. REDUCTION IN SUCTION PRESSURE (5 TO 7 PSI EXPECTED)
j
B. DISCHARGE PRESSURE UNCHANGED
j
C. LIQUID TEMPERATURE DROPS TO 50 TO 55
_
F RANGE
j
D. LIQUID SOLENOID VALVE (LSV) ENERGIZED (VALVE CLOSES)
j
6. SWITCH UNIT TO DEHUMID (REHEAT) BY OPENING Y1
OBSERVE
j
A. SUCTION PRESSURE INCREASES TO NORMAL COOLING LEVEL
j
B. DISCHARGE PRESSURE DECREASES (35 TO 50 PSI)
j
C. LIQUID TEMPERATURE RETURNS TO NORMAL COOLING LEVEL
j
D. LIQUID SOLENOID VALVE (LSV) ENERGIZED (VALVE CLOSES)
j
E.
DISCHARGE SOLENOID VALVE (DSV) ENERGIZED, VALVE OPENS
j
7. WITH UNIT IN DEHUMID MODE CLOSE W1
COMPRESSOR AND OUTDOOR FAN STOP; LSV AND DSV SOLENOIDS DE−ENERGIZED
j
8. OPEN W1 RESTORE UNIT TO DEHUMID MODE
j
9. OPEN HUMIDISTAT INPUT
COMPRESSOR AND OUTDOOR FAN STOP; LSV AND DSV SOLENOIDS DE−ENERGIZED
j
10. RESTORE SETPOINTS FOR THERMOSTAT AND HUMIDISTAT
REPEAT PROCESS FOR 2 COMPRESSOR SYSTEMS
Copyright 2016 Bryant Heating & Cooling Systems
Edition Date: 09/16 11-16A
Printed in U.S.A.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Catalog No: II581J-7-12-02
Replaces: II581J-7-12-01
581J
Содержание 581J series
Страница 4: ...4 C160140 Fig 2 Unit Dimensional Drawing Sizes 07 09 581J ...
Страница 5: ...5 C160141 Fig 2 Unit Dimensional Drawing Sizes 07 09 cont 581J ...
Страница 6: ...6 C13300A Fig 3 Unit Dimensional Drawing Sizes 11 and 12 581J ...
Страница 7: ...7 C13301A Fig 3 Unit Dimensional Drawing Sizes 11 and 12 cont 581J ...
Страница 25: ...25 C160113 Fig 36 Typical RTU Open Controller Wiring Diagram 581J ...
Страница 26: ...26 C160114 Fig 37 Typical RTU Open Controller Wiring Diagram Wiring Diagram with Perfect Humidityt System 581J ...