Table 9 – Unit Wire/Fuse or HACR Breaker Sizing Data − Two Speed Indoor Fan Motor
UNIT
NOM.V-Ph-Hz
IFM
TYPE
NO C.O. or UNPWR C.O.
w/ PWRD C.O.
NO P.E.
w/ P.E. (pwrd fr/ unit)
NO P.E.
w/ P.E. (pwrd fr/ unit)
MCA
MAX FUSE
or HACR
BRKR
DISC. SIZE
MCA
MAX FUSE
or HACR
BRKR
DISC. SIZE
MCA
MAX FUSE
or HACR
BRKR
DISC. SIZE
MCA
MAX FUSE
or HACR
BRKR
DISC. SIZE
FLA
LRA
FLA
LRA
FLA
LRA
FLA
LRA
581J*07D
(2-stage cool)
208/230-3-60
STD
31/31
45/45
30/30
165
35/35
50/50
35/34
169
36/36
50/50
36/36
170
40/40
50/50
40/40
174
MED
34/33
50/50
33/33
195
38/37
50/50
38/37
199
39/38
50/50
39/38
200
43/42
50/50
43/42
204
HIGH
39/38
50/50
39/38
230
43/42
50/50
44/43
234
45/44
60/50
45/44
235
48/47
60/60
49/48
239
460-3-60
STD
15
20
15
81
17
25
17
83
18
25
17
83
19
25
19
85
MED
16
20
16
97
18
25
18
99
19
25
18
99
20
25
20
101
HIGH
19
25
19
114
21
25
21
116
21
25
21
116
23
30
23
118
575-3-60
STD
12
15
12
68
16
20
16
72
14
20
14
70
18
20
18
74
MED
14
20
14
81
18
20
18
85
16
20
16
83
20
25
201
87
HIGH
16
20
16
95
20
25
20
99
17
20
18
97
21
25
22
101
581J*08D
(2-stage cool)
208/230-3-60
STD
40/40
50/50
41/41
195
44/43
50/50
46/46
199
45/44
50/50
47/47
200
48/48
60/60
51/51
204
MED
41/41
50/50
43/43
199
45/45
50/50
47/47
203
46/46
50/50
48/48
204
50/49
60/60
53/52
208
HIGH
45/44
50/50
47/46
249
49/48
60/60
52/50
253
50/49
60/60
53/52
254
53/52
60/60
57/56
258
460-3-60
STD
19
20
19
97
20
25
21
99
21
25
22
99
23
25
24
101
MED
19
25
20
100
21
25
22
102
22
25
23
102
23
25
25
104
HIGH
21
25
22
125
22
25
24
127
23
25
24
127
25
30
26
129
575-3-60
STD
14
15
14
79
18
20
19
83
16
20
16
81
19
25
21
85
MED
15
20
15
83
18
20
19
87
16
20
17
85
20
25
21
89
HIGH
16
20
16
92
19
25
21
96
17
20
18
94
21
25
23
98
581J*09D
(2-stage cool)
208/230-3-60
STD
40/40
50/50
42/41
195
44/44
50/50
46/46
199
45/45
50/50
47/47
200
49/48
60/60
52/51
204
MED
41/41
50/50
43/43
199
45/45
50/50
47/47
203
46/46
50/50
49/48
204
50/50
60/60
53/53
208
HIGH
45/44
50/50
47/46
249
49/48
60/60
52/51
253
50/49
60/60
53/52
254
54/53
60/60
57/56
258
460-3-60
STD
19
25
19
97
21
25
22
99
21
25
22
99
23
25
24
101
MED
19
25
20
100
21
25
22
102
22
25
23
102
23
25
25
104
HIGH
21
25
22
125
23
25
24
127
23
25
24
127
25
30
26
129
575-3-60
STD
15
20
16
79
19
20
20
83
17
20
18
81
21
25
22
85
MED
16
20
16
83
20
25
21
87
18
20
18
85
21
25
23
89
HIGH
17
20
18
92
21
25
22
96
19
20
20
94
22
25
24
98
581J*11D
(2-stage cool)
208/230-3-60
STD
51/50
60/60
53/53
254
55/54
60/60
58/57
258
56/55
60/60
59/58
259
59/59
70/70
63/63
263
MED
54/53
60/60
58/56
304
58/57
70/70
62/61
308
59/58
70/70
63/62
309
63/62
70/70
67/66
313
HIGH
57/56
70/60
61/60
315
61/60
70/70
65/64
319
62/61
70/70
66/65
320
66/65
80/80
71/70
324
460-3-60
STD
23
25
24
122
25
30
26
124
25
30
27
124
27
30
29
126
MED
25
30
26
147
27
30
28
149
27
30
28
149
29
35
30
151
HIGH
26
30
28
152
28
30
30
154
28
30
30
154
30
35
32
156
575-3-60
STD
19
20
20
97
23
25
24
101
21
25
22
99
25
30
26
103
MED
20
25
21
106
24
25
25
110
22
25
23
108
26
30
27
112
HIGH
22
25
23
120
26
30
27
124
24
25
25
122
28
30
29
126
See “Legend and Notes for Tables 8 and 9” on page 36.
48HC
581J
Содержание 581J series
Страница 4: ...4 C160140 Fig 2 Unit Dimensional Drawing Sizes 07 09 581J ...
Страница 5: ...5 C160141 Fig 2 Unit Dimensional Drawing Sizes 07 09 cont 581J ...
Страница 6: ...6 C13300A Fig 3 Unit Dimensional Drawing Sizes 11 and 12 581J ...
Страница 7: ...7 C13301A Fig 3 Unit Dimensional Drawing Sizes 11 and 12 cont 581J ...
Страница 25: ...25 C160113 Fig 36 Typical RTU Open Controller Wiring Diagram 581J ...
Страница 26: ...26 C160114 Fig 37 Typical RTU Open Controller Wiring Diagram Wiring Diagram with Perfect Humidityt System 581J ...