ELECTRICAL DATA (cont)
581B090-120 HIGH-STATIC MOTOR (Units Without Electrical Convenience Outlet)
581B090-120 HIGH-STATIC MOTOR (Units With Electrical Convenience Outlet)
LEGEND
*Used to determine minimum disconnect per NEC.
†Fuse or HACR circuit breaker per NEC.
NOTES:
1. In compliance with NEC requirements for multimotor and combina-
tion load equipment (refer to NEC Articles 430 and 440), the overcur-
rent protective device for the unit shall be fuse or HACR breaker. The
UL, Canada approved units may be fuse or circuit breaker.
2.
Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is
greater than 2%.
Use the following formula to determine the percent
of voltage imbalance.
% Voltage imbalance
Example: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
= 457
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
= 1.53%
This amount of phase imbalance is satisfactory as it is below the maxi-
mum allowable 2%.
IMPORTANT:
If the supply voltage phase imbalance is more than 2%,
contact your local electric utility company immediately.
UNIT
581B
NOMINAL
VOLTAGE
(V-Ph-Hz)
VOLTAGE
RANGE
COMPRESSOR
(each)
OFM
IFM
COMBUSTION
FAN MOTOR
POWER
SUPPLY
MINIMUM UNIT
DISCONNECT
SIZE*
Min
Max
RLA
LRA
FLA
FLA
RLA
MCA
MOCP
FLA
LRA
090
208/230-3-60
187
254
12.4
88.0
1.4
10.6
0.6
41.3
45†
44
267
460-3-60
414
508
6.4
44.0
0.7
4.8
0.3
20.6
25†
22
134
575-3-60
518
632
4.8
34.0
0.7
4.8
0.3
15.8
20†
17
95
102
208/230-3-60
187
254
15.0
99.0
1.4
10.6
0.6
47.2
60†
50
264
460-3-60
414
508
8.2
49.5
0.7
4.8
0.3
24.7
30†
26
132
575-3-60
518
632
5.8
40.0
0.7
4.8
0.3
18.0
20†
19
107
120
208/230-3-60
187
254
17.3
125.0
1.4
15.0
0.6
56.7
70
61
360
460-3-60
414
508
9.0
62.0
0.7
7.4
0.3
29.1
35†
29
181
575-3-60
518
632
7.1
50.0
0.7
7.4
0.3
23.0
25†
23
136
UNIT
581B
NOMINAL
VOLTAGE
(V-Ph-Hz)
VOLTAGE
RANGE
COMPRESSOR
(each)
OFM
IFM
COMBUSTION
FAN MOTOR
POWER
SUPPLY
MINIMUM UNIT
DISCONNECT
SIZE*
Min
Max
RLA
LRA
FLA
FLA
RLA
MCA
MOCP
FLA
LRA
090
208/230-3-60
187
254
12.4
88.0
1.4
10.6
0.6
47.3
50†
49
267
460-3-60
414
508
6.4
44.0
0.7
4.8
0.3
23.3
25†
24
134
575-3-60
518
632
4.8
34.0
0.7
4.8
0.3
18.5
20†
19
95
102
208/230-3-60
187
254
15.0
99.0
1.4
10.6
0.6
53.2
60†
55
264
460-3-60
414
508
8.2
49.5
0.7
4.8
0.3
27.4
30†
28
132
575-3-60
518
632
5.8
40.0
0.7
4.8
0.3
20.7
25†
21
107
120
208/230-3-60
187
254
17.3
125.0
1.4
15.0
0.6
62.7
70
66
360
460-3-60
414
508
9.0
62.0
0.7
7.4
0.3
31.8
35†
32
181
575-3-60
518
632
7.1
50.0
0.7
7.4
0.3
25.7
30†
25
147
FLA
—
Full Load Amps
HACR —
Heating, Air Conditioning and Refrigeration
IFM
—
Indoor (Evaporator) Fan Motor
LRA
—
Locked Rotor Amps
MCA —
Minimum Circuit Amps
MOCP—
Maximum Overcurrent Protection
NEC —
National Electrical Code
OFM —
Outdoor (Condenser) Fan Motor
RLA
—
Rated Load Amps
UL
—
Underwriters’ Laboratories
= 100 x
max voltage deviation from average voltage
average voltage
Average Voltage =
452 + 464 + 455
3
=
1371
3
7
457