Table 26 — LEDs
(The LEDs on the RTU Open show the status of certain functions)
NOTE: Refer to the RTU Open Multi-Protocol Controller
Controls, Start-Up, Operation and Troubleshooting manual
for complete configuration of RTU Open, operating se-
quences and troubleshooting information. Contact your
Bryant applications engineer for details on configuration
and troubleshooting of connected networks.
OUTDOOR AIR ENTHALPY CONTROL
(PN: 33CSENTHSW) —
The enthalpy control is avail-
able as a field-installed accessory to be used with the
EconoMi$er
®
2 damper system. The outdoor air enthalpy
sensor is part of the enthalpy control. (The separate field-in-
stalled accessory return air enthalpy sensor (33CSENTSEN)
is required for differential enthalpy control (see Fig. 61).
Locate the enthalpy control in the economizer next to the
Actuator Motor. Locate two GRA leads in the factory harness
and connect the gray lead labeled “ESL” to the terminal labeled
“LOW”. See Fig. 61. Connect the enthalpy control power input
terminals to economizer actuator power leads RED (connect to
24V) and BLK (connect to GND).
Fig. 61 — Enthalpy Switch (33CSENTHSW)
Connections
The outdoor enthalpy changeover setpoint is set at the en-
thalpy controller.
Differential Enthalpy Control — Control is provided by sens-
ing and comparing the outside air and return air enthalpy con-
ditions. Install the outdoor air enthalpy control as described
above. Add and install a return air enthalpy sensor.
Return Air Enthalpy Sensor (33SENTSEN) — The sensor is
mounted in the return-air section of the economizer. The return
air sensor is wired to the enthalpy controller (33CSENTHSW).
Fig. 62 — Outside and Return Air Enthalpy Sensor
Wiring
SMOKE DETECTORS —
Smoke detectors are available as
factory-installed options on 580J models. Smoke detectors may
be specified for Supply Air only or for Return Air without or
with economizer or in combination of Supply Air and Return
Air. All components necessary for operation are factory-pro-
vided and mounted. The unit is factory-configured for immedi-
ate smoke detector shutdown operation; additional wiring or
modifications to unit terminal board may be necessary to com-
plete the unit and smoke detector configuration to meet project
requirements.
Units equipped with factory-optional Return Air smoke de-
tectors require a relocation of the sensor module at unit installa-
tion. See Fig. 63 for the as shipped location.
IF THIS LED IS ON...
THE STATUS IS...
Power
RTU Open has power
Rx
RTU Open is receiving data from the network segment
Tx
RTU Open is transmitting data over the network segment
DO#
The digital output is active
The
Run
and
Error
LEDs indicate control module and network status
IF THIS LED IS ON...
THE STATUS IS...
Status is...
2 Flashes Per Second
Off
Normal
2 Flashes Per Second
2 flashes, alternating with
Run
LED
Five minute auto-restart delay after system error
2 Flashes Per Second
3 flashes, then off
Control module has just been formatted
2 Flashes Per Second
4 flashes, then pause
Two or more devices on this network have the same
ARC156
2 Flashes Per Second
On
Network address
5 Flashes Per Second
On
Exec start-up aborted, Boot is running
5 Flashes Per Second
Off
Firmware transfer in progress, Boot is running
7 Flashes Per Second
7 flashes per second, alternating with
Run
LED
Ten second recovery period after brownout
14 Flashes Per Second
14 flashes per second, alternating with
Run
LED
Brownout
On
On
Failure. Try the following solutions:
•
Turn RTU Open off, then on
•
Format RTU Open
•
Download memory to RTU Open
•
Replace RTU Open
7
CTB ECON
(P
’
LINK: to J4-2) or
(RTU Open: to J2-6)
LOW
GND
24V
Enth
a
lpy
S
witch
GRA
BLK
RED
FACTORY WIRING HARNE
SS
PL6-1 (24-V)
PL6-4 (COM)
48TC
GRA
BLK
RED
–
4-20
MAIN
+
VDC
OUT
–
4-20 MAIN
OUT
+
24-
3
6
VDC IN
LOW
GND
24V
7
PL6-1 (24-V)
PL6-4 (COM)
OUT
S
IDE AIR
ENTHALPY
S
WITCH
RETURN AIR
ENTHALPY
S
EN
S
OR
CTB ECON
(P
’
LINK: to J4-2) or
(RTU Open: to J2-6)
Содержание 580J*04A
Страница 4: ...4 Fig 2 Unit Dimensional Drawing ...
Страница 5: ...5 Fig 2 Unit Dimensional Drawing cont ...
Страница 21: ...21 Fig 34 580J Size 07 Unit with Perfect Humidity Dehumidification System Humidistat Wiring ...
Страница 37: ...37 Fig 43 Typical RTU Open System Control Wiring Diagram ...
Страница 38: ...38 Fig 44 Typical RTU Open System Control Wiring Diagram with Perfect Humidity ...
Страница 49: ......