5. Mix Totaline environmentally sound coil cleaner in a
2
1
/
2
gallon garden sprayer according to the instruc-
tions included with the cleaner. The optimum solution
temperature is 100
F (38
C).
NOTE
: Do NOT USE water in excess of 130
F (54
C),
as the enzymatic activity will be destroyed.
6. Thoroughly apply Totaline
environmentally sound
coil cleaner solution to all coil surfaces including the
finned area, tube sheets and coil headers.
7. Hold garden sprayer nozzle close to finned areas and
apply cleaner with a vertical, up-and-down motion.
Avoid spraying in horizontal pattern to minimize po-
tential for fin damage.
8. Ensure cleaner thoroughly penetrates deep into finned
areas.
9. Interior and exterior finned areas must be thoroughly
cleaned.
10. Finned surfaces should remain wet with cleaning
solution for 10 minutes.
11. Ensure surfaces are not allowed to dry before rinsing.
Reapply cleaner as needed to ensure 10-minute satur-
ation is achieved.
12. Thoroughly rinse all surfaces with low velocity clean
water using downward rinsing motion of water spray
nozzle. Protect fins from damage from the spray
nozzle.
13. Replace top cover and rear corner posts.
Service Parts
Listings of service parts for all units are available from the
Replacement Components Division’s Electronic Parts
Information Catalog (EPIC). EPIC is available at Totaline
stores, distributor and service office parts departments and
on-line at HVACPartners.com.
When entering EPIC, the full unit model number is
required. The model number includes the Design Revision
reference value (see Fig. 1, Position 13). The unit model
number is available from the unit’s information data plate.
(Do not use the “catalog number” when using EPIC. The
“catalog number” suppresses the Design Revision value;
failure to include Design Revision value may cause an
incorrect unit parts list to be displayed.) When using
EPIC, enter first four digits of the model number only.
Find appropriate model from sales packages listed. Be
sure to choose correct voltage and Design Revision.
EPIC is a product of RCD. To comment of the EPIC
program, use the “Comment” button inside the EPIC
program.
FASTENER TORQUE VALUES
Table 13 – Torque Values
Compressor mounting bolts
65---75 in–lbs
(734–847 N–cm)
Condenser fan motor mounting bolts
20
2 in–lbs
(226
23 N–cm)
Condenser fan hub setscrew
84
2 in–lbs
(949
136 N–cm)
High-flow service port
96
10 in–lbs
(1085
23 N–cm)
Schrader-type service check valve
2–3 in–lbs
(23–34 N–cm)
Compressor oil sightglass thread
330
31 in–lbs
(23–34 N–cm)
Compressor to Compressor rail torque 120–168 in–lbs
(1356–1898 N–cm)
Compressor rail to base pan torque
70
5 in–lbs
(791
57 N–cm)
575J
*08G/
H
Содержание 575Jx08G/H Series
Страница 18: ...18 C14303 Fig 17 Typical 575J 08G H Wiring Diagram 208 230V 3PH 60Hz Unit Shown 575J 08G H...
Страница 26: ...26 Fans Service Valves C14305 Fig 23 575J 08G H Exterior 575J 08G H...
Страница 36: ...36 D K J H G F E C B A C10800 Fig 29 Wind Baffles 575J 08G H...
Страница 37: ...37 575J 08G H...