background image

26

If no refrigerant leaks are found and low cooling performance is
suspected, refer to the Checking and Adjusting Refrigerant

Charge section.

GAS INPUT

The gas input does not require checking unless improper heating
performance is suspected. If a problem exists, refer to the

Start--Up section.

EVAPORATOR AIRFLOW

The heating and/or cooling airflow does not require checking

unless improper performance is suspected. If a problem exists, be
sure that all supply-- and return--air grilles are open and free from

obstructions, and that the air filter is clean. When necessary, refer
to the Indoor Airflow and Airflow Adjustments section to check

the system airflow.

PURON ITEMS

METERING DEVICE -- Thermostatic Expansion Valve This
metering device is a hard shutoff, balance port TXV. The TXV

maintains a constant superheat at the evaporator exit resulting in

higher overall system efficiency.

PRESSURE SWITCHES

Pressure switches are protective devices wired into control circuit

(low voltage). They shut off compressor if abnormally high or

low pressures are present in the refrigeration circuit. These
pressure switches are specifically designed to operate with Puron

(R--410A) systems. R--22 pressure switches must not be used as
replacements for the Puron (R--410A) system.

LOSS OF CHARGE SWITCH

This switch is located on the liquid line and protects against low

suction pressures caused by such events as loss of charge, low

airflow across indoor coil, dirty filters, etc. It opens on a pressure
drop at about 20 psig. If system pressure is above this, switch

should be closed. To check switch:

1. Turn off all power to unit.
2. Disconnect leads on switch.
3. Apply ohm meter leads across switch. You should have

continuity on a good switch.

NOTE

: Because these switches are attached to refrigeration

system under pressure, it is not advisable to remove this device
for troubleshooting unless you are reasonably certain that a
problem exists. If switch must be removed, remove and recover
all system charge so that pressure gauges read 0 psi. Never open
system without breaking vacuum with dry nitrogen.

HIGH--PRESSURE SWITCH

The high--pressure switch is located in the discharge line and

protects against excessive condenser coil pressure. It opens at 610
psig.
High pressure may be caused by a dirty outdoor coil, failed fan

motor, or outdoor air recirculation. To check switch:

1. Turn off all power to unit.
2. Disconnect leads on switch.
3. Apply ohm meter leads across switch. You should have

continuity on a good switch.

COPELAND SCROLL COMPRESSOR (PURON
REFRIGERANT)

The compressor used in this product is specifically designed to

operate with Puron (R--410A) refrigerant and cannot be
interchanged.
The compressor is an electrical (as well as mechanical) device.
Exercise extreme caution when working near compressors. Power

should be shut off, if possible, for most troubleshooting

techniques. Refrigerants present additional safety hazards.

FIRE/EXPLOSION HAZARD

Failure to follow this warning could result in personal injury,

death or property damage.
Wear safety glasses and gloves when handling refrigerants.

Keep torches and other ignition sources away from

refrigerants and oils.

!

WARNING

The scroll compressor pumps refrigerant throughout the system

by the interaction of a stationary and an orbiting scroll. The scroll
compressor has no dynamic suction or discharge valves, and it is

more tolerant of stresses caused by debris, liquid slugging, and
flooded starts. The compressor is equipped with an

anti--rotational device and an internal pressure relief port. The
anti--rotational device prevents the scroll from turning backwards

and replaces the need for a cycle protector. The pressure relief

port is a safety device, designed to protect against extreme high
pressure. The relief port has an operating range between 550 and

625 psi differential pressure.
The Copeland scroll compressor uses Mobil 3MA POE oil. This

is the only oil allowed for oil recharge.

UNIT OPERATION AND SAFETY HAZARD

Failure to follow this warning could result in personal injury

or equipment damage.
This system uses Puron (R--410A) refrigerant which has

higher operating pressures than R--22 and other refrigerants.

No other refrigerant may be used in this system. Gauge set,

hoses, and recovery system must be designed to handle Puron.

If you are unsure, consult the equipment manufacturer.

WARNING

!

REFRIGERANT SYSTEM

This information covers the refrigerant system of the 574B,
including the compressor oil needed, servicing systems on roofs

containing synthetic materials, the filter drier and refrigerant
charging.
Compressor Oil
The compressor in this system uses a polyolester (POE) oil,
Mobil 3MA POE. This oil is extremely hygroscopic, meaning it

absorbs water readily. POE oils can absorb 15 times as much
water as other oils designed for HCFC and CFC refrigerants.

Take all necessary precautions to avoid exposure of the oil to the
atmosphere.

SERVICING SYSTEMS ON ROOFS WITH SYNTHETIC-
MATERIALS

POE (polyolester) compressor lubricants are known to cause long
term damage to some synthetic roofing materials.
Exposure, even if immediately cleaned up, may cause

embrittlement (leading to cracking) to occur in one year or more.
When performing any service that may risk exposure of

compressor oil to the roof, take appropriate precautions to protect
roofing. Procedures which risk oil leakage include, but are not

limited to, compressor replacement, repairing refrigerant leaks,
replacing refrigerant components such as filter drier, pressure

switch, metering device, coil, accumulator, or reversing valve.

Synthetic Roof Precautionary Procedure

1. Cover extended roof working area with an impermeable

polyethylene (plastic) drip cloth or tarp. Cover an

approximate 10 X 10 ft. area.

2. Cover area in front of the unit service panel with a terry

cloth shop towel to absorb lubricant spills and prevent

574B

Содержание 574B

Страница 1: ...y Limit Switch Rollout 19 Start Up Cooling Make Adjustments 19 Checking Cooling Control Operation 19 Checking and Adjusting Refrigerant Charge 22 Indoor Airflow and Airflow Adjustments 22 MAINTENANCE 22 26 Air Filter 23 Evaporator Blower and Motor 23 Flue Gas Passageways 23 Induced Draft Combustion Air Blower 23 C99088B Fig 1 Unit 574B Limit Switch 23 Burner Ignition 23 Main Burners 23 Condenser C...

Страница 2: ...IPMENT Inspect for shipping damage while unit is still on shipping pallet If unit appears to be damaged or is torn loose from its anchorage have it examined by transportation inspectors before removal Forward claim papers directly to transportation company Manufacturer is not responsible for any damage incurred in transit Check all items against shipping list Immediately notify the nearest equipme...

Страница 3: ...S in mm Between units power entry side 42 1066 8 Unit and ungrounded surfaces power entry side 36 914 Unit and block or concrete walls and other grounded surfaces control box side 42 1066 8 LEGEND CG Center of Gravity COND Condenser EVAP Evaporator NEC National Electrical Code REQ D Required Note Dimensions are in in mm C99017 UNIT ELECTRICAL CHARACTERISTICS UNIT WEIGHT UNIT HEIGHT IN MM A CENTER ...

Страница 4: ...and Ventilation of the National Fuel Gas Code ANSI American National Standards Institute Z223 1 or applicable provisions of local building code In Canada follow sections 7 2 7 3 or 7 4 or Can CGA Canadian Gas Association B149 Installation Codes or applicable provisions of local building code IMPORTANT Do not restrict outdoor airflow An air restriction at either the outdoor air inlet or the fan dis...

Страница 5: ... A BTyp Supply opening B x C Long Support D 445 16 Return opening B X C Insulate d deck pan Short Support CTyp C00076 UNIT SIZE ODS CATALOG NUMBER A IN MM B IN MM C IN MM D IN MM 574B024 036 CPRFCURB006A00 8 203 11 279 16 1 2 419 28 3 4 730 CPRFCURB007A00 14 356 11 279 16 1 2 419 28 3 4 730 574B042 060 CPRFCURB008A00 8 203 16 3 16 411 17 3 8 441 40 1 4 1022 CPRFCURB009A00 14 356 16 3 16 411 17 3 8...

Страница 6: ...41 156 Corner Weight 4 177 188 201 Fig 5 574B Corner Weights A 1226 3 48 28 914 1371 36 54 927 57 36 52 PLACE RIGGING STRAPS IN BASEPAN SLOT BELOW HANDHOLDS BEFORE RIGGING SEAL STRIP MUST BE IN PLACE BEFORE PLACING UNIT ON ROOF CURB DUCTS B C99015 UNIT 574B MAXIMUM SHIPPING WEIGHT A B lb kg in mm in mm 024 372 169 22 0 558 5 14 50 368 3 030 372 169 22 0 558 5 14 50 368 3 036 410 186 22 0 558 5 15 ...

Страница 7: ...ution to prevent damage when moving the unit Unit must remain in an upright position during all rigging and moving operations The unit must be level for proper condensate drainage therefore the ground level pad or accessory roof curb must be level before setting the unit in place When a field fabricated support is used be sure that the support is level and properly supports the unit Lifting point ...

Страница 8: ...nect a drain tube using a minimum of 3 4 in PVC or 3 4 in copper pipe all field supplied at the outlet end of the 2 in trap Do not undersize the tube Pitch the drain tube downward at a slope of at least 1 in for every 10 ft of horizontal run Be sure to check the drain tube for leaks 1 MIN 2 MIN TRAP OUTLET C99013 Fig 7 Condensate Trap Step 7 INSTALL FLUE HOOD The flue hood assembly is shipped in t...

Страница 9: ...n 1 2 in follow recommendations of national codes 3 Apply joint compound pipe dope sparingly and only to male threads of joint when making pipe connections Use only pipe dope that is resistant to action of liquefied petroleum gases as specified by local and or national codes Never use Teflon tape 4 Install sediment trap in riser leading to heating section See Fig 8 This drip leg functions as a tra...

Страница 10: ...afety checks and power up unit NOTE The design and installation of the duct system must be in accordance with the standards of the NFPA for installation of nonresidence type air conditioning and ventilating systems NFPA 90A or residence type NFPA 90B and or local codes and ordinances Adhere to the following criteria when selecting sizing and installing the duct system 1 Units are shipped for horiz...

Страница 11: ...ate for maximum fuse circuit breaker size and minimum circuit amps ampacity for wire sizing The field supplied disconnect switch box may be mounted on the unit over the high voltage inlet hole when the standard power and low voltage entry points are used See Fig 2 and 3 for acceptable location See unit wiring label and Fig 11 for reference when making high voltage connections Proceed as follows to...

Страница 12: ... AC HP SIZE SELECT SYSTEM SIZE INSTALLED Factory selected air conditioner size should correspond to capacity of unit installed Installer should verify air conditioner size to ensure that airflow delivered falls within proper range for the size unit installed This applies to all operational modes c SYSTEM TYPE SELECT SYSTEM TYPE INSTALLED Factory selected on 574B for AC Air conditioner For Gas Heat...

Страница 13: ...on ACCESSORY INSTALLATION a AUXILIARY TERMINALS The AUX and HUM terminals on the Easy Select Board are tied directly to the G terminal and provide a 24 v signal whenever the G terminal is energized See Fig 12 During Super dehumidify mode the G signal is not present and the auxiliary terminals are not energized If the installation includes the use of this operating mode do not use these terminals t...

Страница 14: ...ing tubing stubs when necessary Oil can ignite when exposed to torch flame WARNING Proceed as follows to inspect and prepare the unit for initial startup 1 Remove access panel 2 Read and follow instructions on all WARNING CAUTION and INFORMATION labels attached to or shipped with unit 3 Make the following inspections a Inspect for shipping and handling damages such as broken lines loose parts disc...

Страница 15: ...rcuit R to W W1 The unit delivers the selected gas heat airflow The IGC will control a 45 sec blower On delay and a 45 sec Off delay Step 3 START UP HEATING AND MAKE ADJUSTMENTS UNIT COMPONENT DAMAGE HAZARD Failure to follow this caution may result in damage to the unit being installed Complete the required procedures given in the Pre Start Up section before starting the unit Do not jumper any saf...

Страница 16: ...just gas input 1 Remove cover screw over regulator adjustment screw on gas valve 2 Turn regulator adjustment screw clockwise to increase gas input or turn regulator adjustment screw counterclockwise to decrease input Manifold pressure must be between 3 4 and 3 6 in wc Unsafe operation of the unit may result if manifold pressure is outside this range Personal injury or unit damage may result FIRE A...

Страница 17: ...17 A07012 Fig 18 208 230 1 60 Wiring Diagram Unit 574B 574B ...

Страница 18: ...18 A07013 Fig 19 208 230 3 60 Wiring Diagram Unit 574B 574B ...

Страница 19: ...ners and pilot The blower motor continues to run until LS resets When the air temperature at the limit switch drops to the low temperature setting of the limit switch the switch closes and completes the R control circuit The electric spark ignition system cycles and the unit returns to normal heating operation AUXILIARY LIMIT SWITCH ROLLOUT The function of the switch is to close the main gas valve...

Страница 20: ...52 49 46 44 524 132 127 122 117 112 3612 56 53 50 47 45 534 134 129 124 119 114 3681 56 54 51 48 45 8 Add Charge if the measured temperature is higher than the table value 5 Interpolate if the Outdoor ambient temperature lies in between the table values Extrapolate if the temperature lies beyond the table range 2 Measure the Liquid line temperature by attaching a temperature sensing device to it 3...

Страница 21: ...1610 Table 9 574B Gas Heating ECM Airflow Small Cabinet EASY SELECTt BOARD SETTING CFM 700 800 1100 1250 Unit Size External Static Pressure in wc 0 0 0 4 0 4 0 7 0 7 1 0 0 0 0 4 0 4 0 7 0 7 1 0 0 0 0 4 0 4 0 7 0 7 1 0 0 0 0 4 0 4 0 7 0 7 1 0 Gas Heat Size 024 040 855 770 710 060 1020 890 835 030 040 880 840 805 060 1030 970 910 036 060 1035 995 955 090 1170 1110 1025 Table 10 574B Gas Heating ECM ...

Страница 22: ...usted properly ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death Before making any indoor wiring adjustments shut off gas supply Then disconnect electrical power to the unit WARNING Airflow can be changed by changing the selection pins on the Easy Select circuit board MAINTENANCE To ensure continuing high performance and to minimize the possibility of ...

Страница 23: ...r Blower section 2 Remove the 3 screws holding the blower housing to the flue collector box cover See Fig 23 3 Remove the 12 screws holding the flue collector box cover See Fig 24 to the heat exchanger assembly Inspect the heat exchangers 4 Clean all surfaces as required using a wire brush COMBUSTION AIR BLOWER Clean periodically to assure proper airflow and heating efficiency Inspect blower wheel...

Страница 24: ...and condensate drain line when inspecting the coils Clean the drain pan and condensate drain by removing all foreign matter from the pan Flush the pan and drain tube with clear water Do not splash water on the insulation motor wiring or air filter s If the drain tube is restricted clear it with a plumbers snake or similar probe device Ensure that the auxiliary drain port above the drain tube is al...

Страница 25: ...y from the motor end 1 8 in of motor shaft will be visible See Fig 15 6 Ensure that setscrew engages the flat area on the motor shaft when tightening 7 Replace grille ELECTRICAL CONTROLS AND WIRING Inspect and check the electrical controls and wiring annually Be sure to turn off the gas supply and then the electrical power to the unit Remove access panel to locate all the electrical controls and w...

Страница 26: ...f possible for most troubleshooting techniques Refrigerants present additional safety hazards FIRE EXPLOSION HAZARD Failure to follow this warning could result in personal injury death or property damage Wear safety glasses and gloves when handling refrigerants Keep torches and other ignition sources away from refrigerants and oils WARNING The scroll compressor pumps refrigerant throughout the sys...

Страница 27: ...ate with Puron S Puron refrigerant cylinders are rose colored S Recovery cylinder service pressure rating must be 400 psig DOT 4BA400 or DOT BW400 S Puron systems should be charged with liquid refrigerant Use a commercial type metering device in the manifold hose when charging into suction line with compressor operating S Manifold sets should be 700 psig high side and 180 psig low side with 550 ps...

Страница 28: ...etermine cause and correct Defective run start capacitor overload or start relay Determine cause and replace Defective thermostat Replace thermostat Faulty condenser fan motor or capacitor Replace Restriction in refrigerant system Locate restriction and remove Compressor operates continuously Dirty air filter Replace filter Unit undersized for load Decrease load or increase unit size Thermostat se...

Страница 29: ...in three minutes after blower off delay timing in heat ing mode Ensure unit is fired on rate ensure temperature rise is correct Ensure unit s external static pressure is within application guide lines Limit switch faults LED 2 flashes High temperature limit switch is open Check the operation of the indoor evaporator fan motor Ensure that the supply air temperature rise is in accordance with the ra...

Страница 30: ...MP SUPPLY AIR ___________ GAS HEAT SUPPLY AIR ___________ ELECTRIC HEAT SUPPLY AIR ___________ PRESSURES GAS INLET PRESSURE ___________IN WG GAS MANIFOLD PRESSURE ___________IN WG REFRIGERANT SUCTION ___________PSIG SUCTION LINE TEMP ___________ REFRIGERANT DISCHARGE ___________PSIG DISCHARGE TEMP ___________ VERIFY REFRIGERANT CHARGE USING CHARGING CHARTS GAS HEAT TEMPERATURE RISE TEMPERATURE RIS...

Отзывы: