DESCRIPTION

Model 542F is a high-efficiency, single-package heat pump that
has an energy efficiency ratio (EER) of 8.5 and a coefficient of
performance (COP) of 3.0 at 47 F outdoor temperature rating
point.

The 542F has supply- and return-air openings on the bottom of
the unit and is designed primarily for rooftop installation on a
factory-supplied 14- or 24-in. high roof curb. The air ducts con-
nect to the curb only; therefore, the curb and ductwork may be
installed before the unit arrives at the jobsite.

A 24-in. high factory-supplied adapter for horizontal supply/
return duct connections to an over-and-under duct configuration
is also available for grade level or rooftop installation.

‘‘Variable circuited’’ indoor and outdoor coils allow both coils to
operate with parallel circuits when they are performing as
evaporators, and with a series of circuits when they are perform-
ing as condensers.

STANDARD FEATURES

FACTORY-ASSEMBLED PACKAGE is a compact, fully self-
contained heating/cooling unit that is prewired, prepiped, and
precharged for minimum installation time and expense.

TWO RUGGED, SERVICEABLE, SEMI-HERMETIC COM-
PRESSORS 
provide two stages of heating and cooling. These
compressors are electrically and mechanically independent.

COMPRESSOR ISOLATION MOUNTING minimizes vibration
(noise) transmission to building.

TWO SUCTION-TUBE ACCUMULATORS protect compres-
sors against liquid slugging — permitting operation over wide
range of temperatures.

CRANKCASE HEATERS AND FILTER DRIERS are standard.

HIGH- AND LOW-PRESSURE SAFETY DEVICES are included
to prevent major component breakdown when abnormal refrig-
erant operating conditions occur.

INTERNAL AND EXTERNAL PROTECTION is provided
against compressor overload and overheat conditions.

HIGH-STATIC, BELT-DRIVEN BLOWER with an adjustable
motor pulley permits variable airflow rates. An optional motor
pulley adjusts the airflow range to meet most applications.

WEATHERIZED CABINET of heavy-duty phosphated and zinc-
coated steel is standard. Baked-on finish is corrosion and fade
resistant.

VERTICAL CONDENSER AIR DISCHARGE prevents recircu-
lation of hot condenser air and reduces the operating sound
level.

MANUAL OUTDOOR-AIR DAMPER (standard equipment on
units without optional economizer) provides up to 25% outdoor
air for ventilation.

SUPPLEMENTAL ELECTRIC HEATERS are available as ac-
cessory equipment for operation on 208, 230, and 460 v, and
are modular in design for easy installation.

SINGLE-POINT POWER CONNECTION is provided on units
with field-installed electric heaters. Only one power supply with
one disconnect switch is required.

PROTECTION AS REQUIRED BY NEC (National Electrical
Code) 
for fan motors is factory supplied.

TWO-IN. FILTERS are standard.

RIGGING HOLES are provided in unit base rails for a 4-point lift
to facilitate lifting and moving operations.

THERMALLY AND ACOUSTICALLY INSULATED air-handling
section provides quieter and more efficient operation.

FACTORY-INSTALLED OPTIONS

DESCRIPTION AND USAGE

Economizer — The economizer will allow a fixed percentage
(between 0 and 100%) outdoor ventilation air into the unit any
time the indoor fan is running. A dry-bulb changeover thermostat
allows up to 100% outdoor air whenever the temperature of the
outdoor air alone will adequately provide cooling. If the econo-
mizer alone cannot provide enough cooling, then simultaneous
economizer and compressor operation will provide the most
economical operation.

SUGGESTED USE:

• To allow a fixed percentage of outdoor air any time the indoor

fan is on, or operates in economizer mode if outdoor air can
provide cooling, but closes when the indoor fan is off to pre-
vent cold backdrafts and wasted energy.

• To reduce energy usage. Use whenever the number of hours

of operation at below 55 F is significant.

• The damper may be used on either vertical or horizontal

applications.

Alternate Indoor-Fan Drive — Alternate drive allows operation
of the indoor fan at conditions outside the range of the standard
factory motor and drive combination.

SUGGESTED USE:

• When higher static/airflow is required to meet job conditions.

MODEL 542F

Bryant

Air Conditioning

COMMERCIAL ROOFTOP
PACKAGED HEAT PUMP

Model 542F

Size 180

15 Tons

Form No. PDS 542F.180.2B

Содержание 542F

Страница 1: ... on finish is corrosion and fade resistant VERTICAL CONDENSER AIR DISCHARGE prevents recircu lation of hot condenser air and reduces the operating sound level MANUAL OUTDOOR AIR DAMPER standard equipment on units without optional economizer provides up to 25 outdoor air for ventilation SUPPLEMENTAL ELECTRIC HEATERS are available as ac cessory equipment for operation on 208 230 and 460 v and are mo...

Страница 2: ... the ability to relieve internal building pressure and pressure losses through the return air ductwork are greater than 0 20 in wg When the job requires the ability to move large quantities of air to relieve pressure in the conditioned space Head Pressure Control Kit consists of an outdoor air ther mostat that permits adequate head pressure control during cooling operation at low outdoor ambient t...

Страница 3: ...Bulb Air Conditioning and Refrigeration Institute NOTE 542F180 units are rated in accordance with ARI Standard 340 Cooling ratings are net values reflecting the effects of circulating fan heat Ratings are based on ESP 35 in wg Cooling Standard 80 F db 67 F wb indoor coil entering air tempera ture and 95 F outdoor coil entering air temperature High Temp Heating Standard 70 F db indoor coil entering...

Страница 4: ...DIMENSIONAL DRAWING BASE UNIT NOTE Space required for service clearance and airflow Allow 68 09 above the unit 78 09 on filter access panel end and 48 09 on remaining sides of unit 4 ...

Страница 5: ...18 69 457 389210 201 18 119 584 Pre Assembled High Static Horizontal Adapter 68 29 1880 08 61 49 159 18 25 89 371 LEGEND COMP SECT Compressor Section NOTES 1 Roof curb accessory is shipped unassembled 2 Insulated panels 1 2 in thick neoprene coated 2 lb density 3 Dimensions in are in millimeters 4 Direction of airflow 5 Roof curb 18 gage steel 6 Attach all ductwork to roof curb NOTE To prevent the...

Страница 6: ...ING HORIZONTAL ADAPTER INSTALLATION NOTE 389210 201 is a fully factory preassembled horizontal adapter which includes an insulated high static regain transition duct and substantially improves fan static performance 6 ...

Страница 7: ...nge Std 916 1186 Alt 1158 1428 Max Allowable Rpm 1550 Fan Pulley Pitch Diameter in 6 4 Motor Pulley Pitch Diameter in Std 3 4 4 4 Alt 4 3 5 3 Motor Frame Size Std 56 Alt Belt Quantity Type Std 1 A44 Alt 1 B45 Speed Change per Full Turn of 54 Moveable Pulley Flange Rpm Moveable Pulley Maximum Full 5 Turns from Closed Position Factory Setting Full Turns Open 5 Factory Speed Setting Rpm Std 916 Alt 1...

Страница 8: ...d heating capacity is 170 000 Btuh Therefore 103 000 Btuh 170 000 67 000 Btuh additional electric heat is required Determine additional electric heat capacity in kW 103 000 Btuh 30 2 kW of heat required 3413 Btuh kW Enter the Electric Resistance Heater Data table on page 11 for 542F at 230 3 60 The 31 0 kW heater at 230 v most closely satisfies the heating required 31 0 kW x 3413 Btuh kW 105 800 B...

Страница 9: ...8 77 76 75 Under 75 Over 85 81 82 83 84 85 Correction Factor 03 1 06 2 11 3 17 4 33 5 28 use formula shown below 10 98 1 96 2 94 3 92 4 91 15 93 1 85 2 78 3 71 4 63 20 87 1 74 2 62 3 49 4 36 Interpolation is permissible Do not extrapolate Correction Factor 1 10 x 1 BF x edb 80 INTEGRATED HEATING CAPACITIES OUTDOOR AIR TEMP F db at 70 RH INTEGRATED CAPACITY MBtuh TOTAL POWER INPUT kW INTEGRATED CAP...

Страница 10: ...ance is based on wet coil and clean 2 in filters Casing losses have been deducted 5 Electric heater pressure drop must be accounted for in fan rpm and bhp section see Static Pressure Losses table on page 11 6 Minimum cfm for units with electric resistance heat 5650 cfm Converting Bhp to Watts Bhp x 746 Watts input Motor Efficiency Approximate Motor Efficiency 81 AIR DELIVERY USING ACCESSORY POWER ...

Страница 11: ...32 04 05 06 07 08 09 11 12 55 05 06 07 08 10 12 14 16 80 06 07 08 10 12 15 17 20 Economizer All 02 03 04 05 06 07 08 09 FIOP Factory Installed Option Static pressure losses must be added to external static pressure before entering Air Delivery table ELECTRICAL DATA V PH HZ VOLTAGE RANGE COMPRESSOR each OUTDOOR FAN MOTOR INDOOR FAN MOTOR ELECTRIC HEAT POWER SUPPLY Min Max RLA LRA Qty FLA Hp FLA kW ...

Страница 12: ...ses time delay relay energizes closing compressor contactor no 2 Both compressors now operate from W1 and W2 controls electric heat Cooling Units With Economizer Outdoor Air Enthalpy Above Set Point Indoor and outdoor fans and compressors energize when there is a call for cooling The economizer damper moves to VENT position Outdoor Air Enthalpy Below Set Point Indoor fan starts and economizer damp...

Страница 13: ... designed to operate at outdoor temperatures down to 40 F At temperatures below 40 F accessory head pressure control device will permit operation at outdoor temperatures as low as 20 F 8 All roof curb and adapter installations must be counter flashed to prevent water leakage 9 Select unit based on cooling only Do not select heat pumps on heating capacity Add auxiliary resistance heat if required 1...

Страница 14: ...TYPICAL FIELD WIRING 14 ...

Страница 15: ...tactor HPS High Pressure Switch HR Heater Relay IFC Indoor Fan Contactor IP Internal Protector L Light LOR Lockout Relay LPS Low Pressure Switch MAT Mixed Air Thermostat PL Plug Assembly PRI Primary RVR Reversing Valve Relay SW Switch TB Terminal Block TC Thermostat Cooling TH Thermostat Heating TRAN Transformer Terminal Marked Terminal Unmarked Terminal Block Splice Splice Marked Factory Wiring F...

Страница 16: ...required by NEC and be supplied with rainshields INDOOR SECTION Indoor coil shall be constructed of alumi num plate fins mechanically bonded to seamless copper tubes Indoor blower shall be of centrifugal type forward curved The blower shall be belt driven by means of an adjustable pitch pul ley permitting a variation of airflow by means of blower speed adjustment Blower motor shall be electrically...

Отзывы: