Bryant 538J-18-1 Скачать руководство пользователя страница 8

8

Table 3 — Electrical Data

LEGEND

*Permissible limits of the voltage range at which unit will operate

satisfactorily.

†Time-delay fuse.

NOTES:

1. Control circuit is 24 v on all units and requires an external power source.

2. All motors and compressors contain internal overload protection.
3. In compliance with NEC (U.S.A. Standard) requirements for multimotor

and combination load equipment (refer to NEC Articles 430 and 440), the
overcurrent protective device for the unit shall be fuse or HACR breaker.

4. Motor RLA values are established in accordance with UL (Underwriters’

Laboratories) Standard 465 (U.S.A. Standard).

V. LOW PRESSURE SWITCH

This switch, mounted on the suction line, has fixed non-
adjustable settings. To check pressure switch, attach pres-
sure gage to suction service valve gage port. Slowly close
liquid shutoff valve and allow compressor to pump down. Do
not allow compressor to pump down below 2 psig (14 kPa).
Compressor should shut down when suction pressure drops
to cutout pressure in Tables 1A and 1B, and should restart
when  pressure  builds  up  to  cut-in  pressure  shown  after
accessory CLO (compressor lockout) switch has been reset
and accessory Time Guard® II device has completed its tim-
ing cycle.

VI. SERVICE VALVES

The service valves in the outdoor unit come from the factory
frontseated. This means the refrigerant charge is isolated
from the line-set connection ports. To prevent damage to the
valve, use a wet cloth or other acceptable heat sink material
on the valve before brazing.

The service valves must be backseated (turned counterclock-
wise until seated) before the service port caps can be
removed and the hoses of the gage manifold connected. In
this position, refrigerant has access from the through out-
door and indoor unit. The service valve cannot be field
repaired; only a complete valve or valve stem seal and
service port caps are available for replacement.

VII. ACCURATER® (BYPASS TYPE) DEVICE

See Fig. 4 for bypass type AccuRater device components. The
piston has a refrigerant metering hole through it. The
retainer forms a stop for the piston in the refrigerant bypass
mode and a sealing surface for liquid line flare connection.
To check, clean or replace piston:

1. Shut off power to unit.
2. Pump down using Pumpdown Procedure section on

page 7.

3. Remove liquid line flare connection from AccuRater

device.

4. Pull retainer out of body, being careful not to scratch

flare sealing surface. If retainer does not pull out
easily, carefully use locking pliers to remove retainer.

5. Slide piston out by inserting a small soft wire, with

small kinks, through metering hole. Ensure metering

hole, sealing surface around piston cones, and fluted
portion of piston are not damaged.

6. Clean piston refrigerant metering hole.
7. Replace retainer O-ring before reassembling Accu-

Rater device (O-ring part no. 99CC501052).

VIII. REFRIGERANT CHARGING

NOTE:

 Do not vent or depressurize unit refrigerant to atmo-

sphere. Remove and recover refrigerant following practice.

A. Superheat Method (Cooling, Non-TXV)

To check and adjust charge during cooling season, use
Tables 4A-5B and the following procedure:

1. Operate unit a minimum of 15 minutes before check-

ing charge.

2. Measure suction pressure by attaching a gage to suc-

tion valve service port.

3. Measure suction line temperature by attaching a ser-

vice thermometer to unit suction line near suction
valve. Insulate thermometer for accurate readings.

4. Measure outdoor coil inlet-air dry bulb temperature

with a second thermometer.

5. Measure indoor coil inlet-air wet bulb temperature

with a sling psychrometer.

6. Refer to Tables 4A and 4B. Find air temperature enter-

ing outdoor coil and wet-bulb temperature entering
indoor coil. At this intersection, note the superheat
temperature.

7. Refer to Tables 5A and 5B. Find superheat tempera-

ture and suction pressure and note suction line
temperature.

8. If unit has higher suction line temperature than

charted temperature, add refrigerant until charted
temperature is reached.

9. If unit has lower suction line temperature than

charted temperature, remove and recover refrigerant
until charted temperature is reached.

538J

V-PH-Hz

OPERATIONAL

VOLTAGE*

COMPRESSOR

POWER SUPPLY

Min

Max

RLA

LRA

Fan FLA

MCA

Max Fuse† or HACR-Type

Ckt Bkr Amps

018

208/230-1-60

187

254

10.7

47.0

.70

14.1

25

024

13.2

59.0

.70

17.2

30

030

15.7

73.0

.70

20.3

35

036

15.7

93.0

.70

20.3

35

048

24.3

131.0

.45

31.8

50

060

28.6

170.0

.45

37.2

65

FLA

Full Load Amps

HACR —

Heating, Air Conditioning, Refrigeration

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps per NEC Section 430-24

NEC

National Electrical Code (U.S.A. Standard)

RLA

Rated Load Amps (Compressor)

WARNING: 

 

To prevent personal injury, wear

safety glasses and gloves when handling refrigerant.
Do not overcharge system — this can cause compressor
flooding.

Содержание 538J-18-1

Страница 1: ... a fire extin guisher available Read these instructions thoroughly Con sult local building codes and National Electrical Code NEC U S A Standard for special installation requirements INSTALLATION I COMPLETE PRE INSTALLATION CHECKS A Unpack Unit Move unit to final location Remove unit packaging being careful not to damage service valves or grilles B Inspect Shipment File claim with shipping company...

Страница 2: ...0 15 16 938 2 1 2 9 16 369 9 1 4 406 4 1 11 7 16 595 3 1 5 3 16 436 6 1 5 1 2 444 5 1 8 1 8 511 2 1 1 330 2 0 6 5 8 168 3 0 11 1 4 285 8 0 0 5 8 15 88 130 58 9 024 2 1 1 8 638 2 3 0 15 16 938 2 1 2 9 16 369 9 1 4 406 4 1 11 7 16 595 3 1 5 3 16 436 6 1 5 1 2 444 5 1 8 1 8 511 2 1 1 330 2 0 6 3 4 171 5 0 11 5 8 295 3 0 0 5 8 15 88 136 61 6 030 2 1 1 8 638 2 3 0 15 16 938 2 1 2 9 16 369 9 1 4 406 4 1...

Страница 3: ...to the structure Also when passing refrigerant tubes through the wall seal opening so that vibration is not transmitted to structure Leave some slack in refrigerant tubes between structure and outdoor unit to absorb vibration Refer to separate indoor unit installation instructions for additional information A Check AccuRater Control The AccuRater refrigerant control is required for cooling sys tem...

Страница 4: ...ssible limits See Table 3 for recommended fuse sizes When making elec trical connections provide clearance at unit for refrigerant piping connections Use indoor unit transformer as 24 v 40 va minimum supply for system as shown in Fig 5 or use accessory transformer C Connections to Duct Free Fan Coil Units The 538J units are designed for easy match up to 619C 619F 619ENX018 and 619ENX024 duct free ...

Страница 5: ...ows 6 1 1 6 1 1 5 6 1 2 6 1 2 12 3 1 5 12 3 1 75 Fins per in 20 20 20 20 20 20 CONTROLS PRESSURESTAT SETTINGS Low Pressure Cutout psig 7 3 Cut In psig 22 5 Fusible Plug 210 F UNIT 538J 018 024 030 036 048 060 NOMINAL CAPACITY kW 5 3 7 0 8 8 10 5 14 1 17 6 UNIT OPERATING WEIGHT kg 58 9 61 6 73 0 83 9 100 6 112 9 COMPRESSOR Hermetic Type Copeland Scroll Copeland Scroll Copeland Scroll Copeland Scrol...

Страница 6: ... If accessory IFR is required for cooling only applications locate IFR in fan coil NOTES 1 Refer to unit wiring label for wire colors BRN to BLU and C to Y connections 2 Arrangement A B and C are for use with residential fan coils Fig 5 Typical Control Circuit Connections Fig 6 Line Power Connections LEGEND NEC National Electrical Code U S A Standard TB Terminal Board Transformer Field Wiring Fact...

Страница 7: ... SENSITIVE OVERLOAD Control resets automatically when internal compressor motor temperature drops to a safe level overloads may require up to 45 minutes to reset When an internal over load is suspected of being open check by using an ohmmeter or continuity tester IV PUMPDOWN PROCEDURE The system may be pumped down in order to make repairs on low side without losing complete refrigerant charge To p...

Страница 8: ...liquid line flare connection from AccuRater device 4 Pull retainer out of body being careful not to scratch flare sealing surface If retainer does not pull out easily carefully use locking pliers to remove retainer 5 Slide piston out by inserting a small soft wire with small kinks through metering hole Ensure metering hole sealing surface around piston cones and fluted portion of piston are not da...

Страница 9: ...80 5 8 12 15 18 21 25 28 31 35 85 8 11 15 19 22 26 30 33 90 5 9 13 16 20 24 27 31 95 6 10 14 18 22 25 29 100 8 12 15 20 23 27 105 5 9 13 17 22 26 110 6 11 15 20 25 115 8 14 18 23 OUTDOOR TEMP C INDOOR COIL ENTERING AIR C WB 10 11 12 13 14 16 17 18 19 20 21 22 23 24 13 5 7 8 9 11 13 14 16 18 19 21 22 23 25 16 4 6 7 8 10 12 13 15 17 18 19 21 22 24 18 3 6 7 9 11 12 13 15 17 18 20 21 23 21 4 6 7 9 11 ...

Страница 10: ...lectrical shock or injury from rotating fan blades REQUIRED SUBCOOLING F LIQUID PRESSURE AT SERVICE VALVE PSIG 134 141 148 156 163 171 179 187 196 205 214 223 233 243 253 264 274 285 297 309 321 331 346 359 0 76 79 82 85 88 91 94 97 100 103 106 109 112 115 118 121 124 127 130 133 136 139 142 145 5 71 74 77 80 83 86 89 92 95 98 101 104 107 110 113 116 119 122 125 128 131 134 137 140 10 66 69 72 75 ...

Страница 11: ... 11 TROUBLESHOOTING TROUBLESHOOTING CHART COOLING CYCLE ...

Страница 12: ...Copyright 2002 Bryant Heating Cooling Systems Printed in Mexico CATALOG NO 5353 802 ...

Отзывы: