Bryant 538J-18-1 Скачать руководство пользователя страница 7

7

Table 2 — American/European Wire Conversions

LEGEND

START-UP

I. PRELIMINARY CHECKS

1. Check that all internal wiring connections are tight

and that barriers, covers, and panels are in place.

2. Make certain field electrical power source agrees

with unit nameplate rating.

3. Open all service valves.

II. LEAK TEST

Field piping and fan coil must be leak tested by the pressure
method. Use R-22 at approximately 25 psig (172 kPa) backed
up with an inert gas to a total pressure not to exceed
245 psig (1690 kPa).

III. EVACUATE AND DEHYDRATE

Field piping and fan coil must be evacuated and dehydrated.

IV. CHARGE SYSTEM

Release factory charge into system by opening (backseating)
liquid and suction line service valves. Add charge amount as
required for the total system. Refer to separate indoor unit
installation instructions for the required total system charge
when connected to the indoor unit.

V. TO START UNIT

NOTE: 

When using 538J unit in conjunction with 619 series

fan coils, refer to start-up instructions included with fan coil
for correct start-up procedures.

Be sure that field disconnect is closed. Set room thermostat
below ambient temperature. Operate unit for 15 minutes,
then check system refrigerant charge. See Refrigerant
Charging section on page 8.

Unit compressor starts after a 5-minute delay if equipped
with accessory Time Guard® II device.

SERVICE

I. OUTDOOR FAN

A reinforced wire mount holds the outdoor fan assembly in
place. See Fig. 7 for proper mounting positions.

II. HIGH-PRESSURE RELIEF VALVE

Valve is located in compressor. Relief valve opens at a
pressure differential of approximately 450 ± 50 psig (3100 ±
345 kPa) between suction (low side) and discharge (high
side) to allow pressure equalization.

III. INTERNAL CURRENT AND TEMPERATURE SENSITIVE
OVERLOAD

Control resets automatically when internal compressor
motor temperature drops to a safe level (overloads may
require up to 45 minutes to reset). When an internal over-
load is suspected of being open, check by using an ohmmeter
or continuity tester.

IV. PUMPDOWN PROCEDURE

The system may be pumped down in order to make repairs
on low side without losing complete refrigerant charge.

To pump down:

1. Attach pressure gage to suction service valve gage

port.

2. Frontseat the liquid line valve.

3. Start unit and run until suction pressure reaches

5 psig (34 kPa).

4. Shut unit off and frontseat suction valve.

5. Depressurize low side of unit and recover refrigerant

following accepted practice.

AMERICAN

EUROPEAN

Industry

Standard Size

American Conversion

(mm)

Industry Standard

Size (mm

2

)

18 AWG

0.82

1.0

16 AWG

1.30

1.5

14 AWG

2.08

2.5

12 AWG

3.30

4.0

10 AWG

5.25

6.0

8 AWG

6.36

10.0

6 AWG

13.29

16.0

4 AWG

21.14

25.0

3 AWG

26.65

2 AWG

33.61

35.0

1 AWG

42.39

50.0

1/0 AWG

53.49

2/0 AWG

67.42

70.0

3/0 AWG

85.00

95.0

4/0 AWG

107.19

120.0

250 kcmil

126.64

150.0

300 kcmil

151.97

350 kcmil

177.90

185.0

400 kcmil

202.63

240.0

500 kcmil

253.29

300.0

600 kcmil

303.95

AWG

American Wire Gage

kcmil —

Thousand Circular Mils

WARNING: 

 Before performing recommended main-

tenance, be sure unit main power switch is off. Failure to
do so may result in electrical shock or injury from rotat-
ing fan blade.

CAUTION: 

 

The 538J unit coils hold only the

factory-designated amount of refrigerant. Additional
refrigerant may cause units to relieve pressure
through compressor internal pressure relief valve
(indicated by sudden rise of suction pressure) before
suction pressure reaches 5 psig (34 kPa). If this occurs,
shut off unit immediately, then frontseat the suction
valve and remove and reclaim excess refrigerant fol-
lowing accepted practice.

Fig. 7 — Condenser Fan Mounting Positions

UNIT 538J DIMENSIONS — in. (mm)

018

024-036

048-060

0.433 (11)

0.709 (18)

0.16 (4)

Содержание 538J-18-1

Страница 1: ... a fire extin guisher available Read these instructions thoroughly Con sult local building codes and National Electrical Code NEC U S A Standard for special installation requirements INSTALLATION I COMPLETE PRE INSTALLATION CHECKS A Unpack Unit Move unit to final location Remove unit packaging being careful not to damage service valves or grilles B Inspect Shipment File claim with shipping company...

Страница 2: ...0 15 16 938 2 1 2 9 16 369 9 1 4 406 4 1 11 7 16 595 3 1 5 3 16 436 6 1 5 1 2 444 5 1 8 1 8 511 2 1 1 330 2 0 6 5 8 168 3 0 11 1 4 285 8 0 0 5 8 15 88 130 58 9 024 2 1 1 8 638 2 3 0 15 16 938 2 1 2 9 16 369 9 1 4 406 4 1 11 7 16 595 3 1 5 3 16 436 6 1 5 1 2 444 5 1 8 1 8 511 2 1 1 330 2 0 6 3 4 171 5 0 11 5 8 295 3 0 0 5 8 15 88 136 61 6 030 2 1 1 8 638 2 3 0 15 16 938 2 1 2 9 16 369 9 1 4 406 4 1...

Страница 3: ...to the structure Also when passing refrigerant tubes through the wall seal opening so that vibration is not transmitted to structure Leave some slack in refrigerant tubes between structure and outdoor unit to absorb vibration Refer to separate indoor unit installation instructions for additional information A Check AccuRater Control The AccuRater refrigerant control is required for cooling sys tem...

Страница 4: ...ssible limits See Table 3 for recommended fuse sizes When making elec trical connections provide clearance at unit for refrigerant piping connections Use indoor unit transformer as 24 v 40 va minimum supply for system as shown in Fig 5 or use accessory transformer C Connections to Duct Free Fan Coil Units The 538J units are designed for easy match up to 619C 619F 619ENX018 and 619ENX024 duct free ...

Страница 5: ...ows 6 1 1 6 1 1 5 6 1 2 6 1 2 12 3 1 5 12 3 1 75 Fins per in 20 20 20 20 20 20 CONTROLS PRESSURESTAT SETTINGS Low Pressure Cutout psig 7 3 Cut In psig 22 5 Fusible Plug 210 F UNIT 538J 018 024 030 036 048 060 NOMINAL CAPACITY kW 5 3 7 0 8 8 10 5 14 1 17 6 UNIT OPERATING WEIGHT kg 58 9 61 6 73 0 83 9 100 6 112 9 COMPRESSOR Hermetic Type Copeland Scroll Copeland Scroll Copeland Scroll Copeland Scrol...

Страница 6: ... If accessory IFR is required for cooling only applications locate IFR in fan coil NOTES 1 Refer to unit wiring label for wire colors BRN to BLU and C to Y connections 2 Arrangement A B and C are for use with residential fan coils Fig 5 Typical Control Circuit Connections Fig 6 Line Power Connections LEGEND NEC National Electrical Code U S A Standard TB Terminal Board Transformer Field Wiring Fact...

Страница 7: ... SENSITIVE OVERLOAD Control resets automatically when internal compressor motor temperature drops to a safe level overloads may require up to 45 minutes to reset When an internal over load is suspected of being open check by using an ohmmeter or continuity tester IV PUMPDOWN PROCEDURE The system may be pumped down in order to make repairs on low side without losing complete refrigerant charge To p...

Страница 8: ...liquid line flare connection from AccuRater device 4 Pull retainer out of body being careful not to scratch flare sealing surface If retainer does not pull out easily carefully use locking pliers to remove retainer 5 Slide piston out by inserting a small soft wire with small kinks through metering hole Ensure metering hole sealing surface around piston cones and fluted portion of piston are not da...

Страница 9: ...80 5 8 12 15 18 21 25 28 31 35 85 8 11 15 19 22 26 30 33 90 5 9 13 16 20 24 27 31 95 6 10 14 18 22 25 29 100 8 12 15 20 23 27 105 5 9 13 17 22 26 110 6 11 15 20 25 115 8 14 18 23 OUTDOOR TEMP C INDOOR COIL ENTERING AIR C WB 10 11 12 13 14 16 17 18 19 20 21 22 23 24 13 5 7 8 9 11 13 14 16 18 19 21 22 23 25 16 4 6 7 8 10 12 13 15 17 18 19 21 22 24 18 3 6 7 9 11 12 13 15 17 18 20 21 23 21 4 6 7 9 11 ...

Страница 10: ...lectrical shock or injury from rotating fan blades REQUIRED SUBCOOLING F LIQUID PRESSURE AT SERVICE VALVE PSIG 134 141 148 156 163 171 179 187 196 205 214 223 233 243 253 264 274 285 297 309 321 331 346 359 0 76 79 82 85 88 91 94 97 100 103 106 109 112 115 118 121 124 127 130 133 136 139 142 145 5 71 74 77 80 83 86 89 92 95 98 101 104 107 110 113 116 119 122 125 128 131 134 137 140 10 66 69 72 75 ...

Страница 11: ... 11 TROUBLESHOOTING TROUBLESHOOTING CHART COOLING CYCLE ...

Страница 12: ...Copyright 2002 Bryant Heating Cooling Systems Printed in Mexico CATALOG NO 5353 802 ...

Отзывы: