AIR DELIVERY -- CFM (BOTTOM RETURN WITH FILTER)*

Unit Size

Operating Mode

CFM Airflow

Setting

External Static

Pressure Range*

External Static Pressure (ESP) In. W.C.

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

042060

††

Low Heat

635†

0---0.50

635

635

625

615

615

High Heat

1070†

0---1.0

1070 1070 1070 1070 1070 1070 1070 1070 1065 1045

††

1---1/2---Ton A/C Cooling

525

0---0.50‡

525

525

510

495

465

††

2---Ton A/C Cooling

700

0---0.50‡

700

700

695

680

680

2---1/2---Ton A/C Cooling

875

0---1.0‡

850

870

875

875

870

860

845

825

810

805

3---Ton A/C Cooling

1050

0---1.0

1050 1050 1050 1050 1050 1050 1050 1050 1050 1045

3---1/2---Ton A/C Cooling

1225

0---1.0

1225 1225 1225 1225 1225 1225 1225 1225 1225 1205

Maximum

1400

0---1.0

1400 1400 1400 1400 1400 1400 1400 1400 1380 1325

042080***

††

Low Heat

900†

0---0.50

860

870

880

885

885

880

870

855

850

845

High Heat

1245†

0---1.0

1245 1245 1245 1245 1245 1245 1245 1235 1190 1145

††

1---1/2---Ton A/C Cooling

525

0---0.50‡

515

495

490

475

465

††

2---Ton A/C Cooling

700

0---0.50‡

685

680

670

665

665

2---1/2---Ton A/C Cooling

875

0---1.0‡

830

840

850

860

860

855

840

830

825

820

3---Ton A/C Cooling

1050

0---1.0‡

1050 1050 1050 1050 1050 1045 1040 1025 1015 1000

3---1/2---Ton A/C Cooling

1225

0---1.0‡

1225 1225 1225 1225 1225 1225 1225 1225 1185 1140

Maximum

1400

0---1.0‡

1400 1400 1400 1400 1375 1325 1280 1235 1190 1145

060080***

††

Low Heat

880†

0---0.50

880

880

880

875

880

High Heat

1500†

0---1.0

1485 1495 1500 1500 1500 1500 1500 1485 1475 1465

††

2---Ton A/C Cooling

700

0---0.50‡

670

640

635

630

630

††

2---1/2---Ton A/C Cooling

875

0---0.50‡

870

875

865

865

865

3---Ton A/C Cooling

1050

0---1.0‡

1050 1045 1040 1045 1045 1050 1050 1050 1045 1040

3---1/2---Ton A/C Cooling

1225

0---1.0‡

1225 1225 1225 1225 1225 1225 1225 1225 1225 1225

4---Ton A/C Cooling

1400

0---1.0‡

1330 1345 1360 1375 1380 1380 1380 1370 1365 1355

5---Ton A/C Cooling

1750

0---1.0

1750 1750 1750 1750 1750 1750 1745 1725 1700 1685

Maximum

2000

0---1.0

2000 2000 2000 2000 1975 1955 1920 1870 1820 1770

060100***

††

Low Heat

1110†

0---0.50

1105 1110 1110 1110 1110 1110 1110 1110 1110 1110

High Heat

1525†

0---1.0

1525 1525 1525 1525 1525 1525 1525 1510 1495 1470

††

2---Ton A/C Cooling

700

0---0.50‡

700

690

690

690

690

††

2---1/2---Ton A/C Cooling

875

0---0.50‡

835

845

855

860

865

3---Ton A/C Cooling

1050

0---1.0‡

1050 1050 1050 1050 1050 1050 1050 1050 1050 1050

3---1/2---Ton A/C Cooling

1225

0---1.0‡

1170 1190 1205 1220 1225 1225 1225 1225 1225 1225

4---Ton A/C Cooling

1400

0---1.0‡

1400 1400 1400 1400 1400 1400 1400 1400 1400 1375

5---Ton A/C Cooling

1750

0---1.0

1735 1740 1735 1735 1725 1720 1710 1695 1680 1660

Maximum

2000

0---1.0

1995 1985 1980 1965 1950 1935 1910 1885 1860 1815

060120

Low Heat

1330†

0---1.0

1325 1330 1330 1330 1330 1330 1330 1330 1330 1325

High Heat

1900†

0---1.0

1900 1900 1900 1900 1900 1885 1875 1860 1840 1815

††

2---Ton A/C Cooling

700

0---0.50‡

700

700

700

700

695

††

2---1/2---Ton A/C Cooling

875

0---0.50‡

870

875

875

865

870

3---Ton A/C Cooling

1050

0---1.0‡

1025 1035 1045 1050 1050 1050 1050 1050 1040 1025

3---1/2---Ton A/C Cooling

1225

0---1.0‡

1210 1210 1210 1225 1225 1225 1225 1225 1225 1225

4---Ton A/C Cooling

1400

0---1.0‡

1385 1400 1400 1400 1400 1400 1400 1395 1375 1370

5---Ton A/C Cooling

1750

0---1.0‡

1745 1730 1735 1735 1740 1735 1730 1725 1710 1685

6---Ton A/C Cooling

2100

0---1.0

2100 2100 2080 2065 2060 2045 2030 2000 1960 1895

Maximum

2100

0---1.0

2100 2100 2080 2065 2060 2045 2030 2000 1960 1895

* Actual external static pressure (ESP) can be determined by using the fan laws (CFM

2

proportional to ESP); such as, a system with 1750 CFM at 0.5 ESP

would operate at high---heating airflow of 1500 CFM at 0.37 ESP and low---heating airflow of 880 CFM at 0.13 ESP.

{

All heating CFMs are when low---heat rise adjustment switch (SW1---3) and comfort/efficiency adjustment switch (SW1---4) are OFF.

}

Ductwork must be sized for high---heating CFM within the operational range of ESP.

** Wattage data provided is for the circulating blower with bottom return and does not include draft inducer, accessories, or gas controls.

{{

Operation within the blank areas of the chart is not recommended because high---heat operation will be above 1.0 ESP.

*** All airflows on 21 in. casing size furnaces are 5% less on side return only installations.

355B

A

V

Содержание 355BAV Plus 95i

Страница 1: ...ic air cleaner and humidifier S adjustable blower off time S LED fault code display to aid in servicing S selectable airflow to match cooling unit S emergency heat setting S setting to increase airflo...

Страница 2: ...quiet heating Motors and electronic controls are covered by a 5 year limited warranty Sealed Combustion System This furnace brings in combustion air from outside the furnace which results in especial...

Страница 3: ...DIA 13 mm THERMOST AT ENTRY 2 IN 51 mm VENT CONN DIMPLE LOCATORS FOR HORIZONTAL HANGING 14 1 2 TYP SIDE INLET 9 7 16 TYP 26 15 16 TYP CONDENSATE DRAIN LOCATION UPFLOW 30 1 2 9 16 TYP CONDENSATE DRAIN...

Страница 4: ...0 70 High 35 65 40 70 35 65 45 75 45 75 Certified Ext Static Pressure ESP in wc Heating 0 12 0 15 0 15 0 20 0 20 Cooling 0 50 0 50 0 50 0 50 0 50 Airflow CFM Heating Low 635 700 860 945 880 970 1105 1...

Страница 5: ...Kit KGAHT0101CFP X X X X X Germicidal Air Purifier Model GAPA X X X X X Condensate Neutralizer Kit obtained thru RCD P908 0001 X X X X X Electronic Air Cleaner Model EACA X X X X X Mechanical Air Cle...

Страница 6: ...HK52EA123 X X X Gas Orifice Kit Size 42 Qty 50 KGAHA0150N42 See Installation Instructions for model altitude and heat value usages Gas Orifice Kit Size 43 Qty 50 KGAHA0250N43 Gas Orifice Kit Size 44...

Страница 7: ...ogrammable T2 PAC For use with 1 speed Air Conditioner _F _C Auto Changeover 5 2 Programmable T2 PRH For use with two stage applications _F _C Auto Changeover 7 Day Programmable T2 PRH For multi use s...

Страница 8: ...10 1110 1110 1110 1110 1110 1110 1110 High Heat 1525 0 1 0 1525 1525 1525 1525 1525 1525 1525 1510 1495 1470 2 Ton A C Cooling 700 0 0 50 700 690 690 690 690 2 1 2 Ton A C Cooling 875 0 0 50 835 845 8...

Страница 9: ...ntric 1 1 2 42 12 8 37 11 2 32 9 8 27 8 2 22 6 7 17 5 2 2 70 21 3 70 21 3 70 21 3 70 21 3 70 21 3 70 21 3 80 000 2 Pipe or 2 In Concentric 1 1 2 25 7 6 20 6 1 15 4 6 10 3 0 5 1 5 NA 2 70 21 3 70 21 3...

Страница 10: ...7 7 56 17 1 51 15 5 46 14 0 100 000 2 Pipe or 2 In Concentric 2 27 8 2 22 6 7 17 5 2 12 3 7 7 2 1 NA 2 1 2 62 18 9 60 18 3 58 17 7 56 17 1 55 16 8 53 16 2 120 000 2 Pipe or 3 In Concentric 3 one disk...

Страница 11: ...60120 20_F 6 7_C 3 49 14 9 70 21 3 70 21 3 70 21 3 70 21 3 0_F 17 8_C 3 26 7 9 51 15 5 58 17 7 70 21 3 70 21 3 20_F 28 9_C 3 15 4 6 35 10 7 40 12 2 50 15 2 59 18 0 Pipe length ft m specified for maxim...

Страница 12: ...RMOSTAT TERMINALS FIELD SUPPLIED FUSED DISCONNECT CONDENSING UNIT FURNACE COM R W C Y R G GND GND FIELD 24 VOLT WIRING FIELD 115 208 230 460 VOLT WIRING FACTORY 24 VOLT WIRING FACTORY 115 VOLT WIRING...

Страница 13: ...RANCE TO COMBUSTIBLES LIT TOP A09681 TYPICAL INSTALLATIONS COMBUSTION AIR PIPE A C COIL OUTDOOR UNIT VENT PIPE HUMIDIFIER GAS FIRED WATER HEATER ELECTRONIC AIR CLEANER AIRFLOW FRONT OF FURNACE A06511...

Страница 14: ...e vibration transmission Primary Heat Exchangers Primary heat exchangers shall be 3 Pass 20 gauge corrosion resistant aluminized steel of fold and crimp sectional design and applied operating under ne...

Отзывы: