GUIDE SPECIFICATIONS

General

System Description

Furnish a ______________________ (upflow) gas--fired

condensing furnace for use with natural gas or propane (factory--
authorized conversion kit required for propane); furnish cold air

return plenum; furnish external media cabinet for use with

accessory media filter or standard filter.

Quality Assurance

Unit will be designed, tested and constructed to the current ANSI

Z 21.47/CSA 2.3 design standard for gas--fired central furnaces.
Unit will be third party certified by CSA to the current ANSI Z
21.47/CSA 2.3 design standard for gas--fired central furnaces.

Unit will carry the CSA Blue Star

R

and Blue Flame

R

labels.

Unit efficiency testing will be performed per the current DOE test

procedure as listed in the Federal Register.
Unit will be certified for capacity and efficiency and listed in the
latest GAMA Consumer’s Directory of Certified Efficiency

Ratings.
Unit will carry the current Federal Trade Commission Energy

Guide efficiency label.

Delivery, Storage, and Handling

Unit will be shipped as single package only and is stored and
handled per unit manufacturer’s recommendations.

Warranty (for inclusion by specifying engineer)

U.S. and Canada only. Warranty certificate available upon

request.

Equipment

Blower Wheel and ECM Blower Motor
Galvanized blower wheel shall be centrifugal type, statically and

dynamically balanced. Blower motor of ECM type shall be

permanently lubricated with sealed ball bearings, of _______hp,
and have infinitely variable speed from 300--1300 RPM

operating only when 24--VAC motor inputs are provided. Blower
motor shall be direct drive and soft mounted to the blower scroll

to reduce vibration transmission.
Filters
Furnace shall have reusable--type filters. Filter shall be ______ in.

(X) ________ in. An accessory highly efficient Media Filter is
available as an option. _____________ Media Filter.
Casing
Casing shall be of .030 in. thickness minimum, pre--painted
galvanized steel.

Preferred

t

Plus 95i

Two--Stage/Variable Speed Gas Furnace

355BAV

ECM Inducer Motor
ECM Inducer motor shall be variable speed design, soft mounted
to assembly to reduce vibration transmission.
Primary Heat Exchangers
Primary heat exchangers shall be 3--Pass 20 gauge corrosion--

resistant aluminized steel of fold--and--crimp sectional design and

applied operating under negative pressure.
Secondary Heat Exchangers
Secondary heat exchangers shall be of a flow--through design
having a patented interior laminate coating of polypropylene for

greater corrosion resistance with fold--and--crimp design and

applied operating under negative pressure.
Controls
Controls shall include a micro--processor--based integrated
electronic control board with at least 16 service troubleshooting

codes displayed via diagnostic flashing LED light on the control,
a self--test feature that checks all major functions of the furnace,

and a replaceable automotive--type circuit protection fuse.

Multiple operational settings available, including separate blower
speeds for low heat, high heat, low cooling, high cooling and

continuous fan. Continuous fan speed may be adjusted from the
thermostat. Cooling airflow will be selectable between 350 or 400

CFM per ton of air conditioning. Features will also include

temporary reduced airflow in the cooling mode for improved
dehumidification when a Thermidistat is selected as the

thermostat.

Operating Characteristics

Heating capacity shall be _________________ Btuh input;

______________ Btuh output capacity.
Fuel Gas Efficiency shall be 95% AFUE.
Air delivery shall be ________________ cfm minimum at 0.50

in. wc. external static pressure.
Dimensions shall be: depth_________in.; width __________in.;

height___________in. (casing only). Height shall be

_________in. with A/C coil and _________________in. overall
with plenum.

Electrical Requirements

Electrical supply shall be 115 volts, 60 Hz, single--phase
(nominal). Minimum wire size shall be ________AWG;

maximum fuse size of HACR--type designated circuit breaker
shall be _________ amps.

Special Features

Refer to section of the product data identifying accessories and

descriptions for specific features and available enhancements.

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

E

Bryant Heating & Cooling Systems 7310 W. Morris St. Indianapolis, IN 46231

Printed in U.S.A.

Edition Date: 09/10

Replaces: PDS355B.40.1

Catalog No. PDS355B.40.2

355B

A

V

Содержание 355BAV Plus 95i

Страница 1: ...ic air cleaner and humidifier S adjustable blower off time S LED fault code display to aid in servicing S selectable airflow to match cooling unit S emergency heat setting S setting to increase airflo...

Страница 2: ...quiet heating Motors and electronic controls are covered by a 5 year limited warranty Sealed Combustion System This furnace brings in combustion air from outside the furnace which results in especial...

Страница 3: ...DIA 13 mm THERMOST AT ENTRY 2 IN 51 mm VENT CONN DIMPLE LOCATORS FOR HORIZONTAL HANGING 14 1 2 TYP SIDE INLET 9 7 16 TYP 26 15 16 TYP CONDENSATE DRAIN LOCATION UPFLOW 30 1 2 9 16 TYP CONDENSATE DRAIN...

Страница 4: ...0 70 High 35 65 40 70 35 65 45 75 45 75 Certified Ext Static Pressure ESP in wc Heating 0 12 0 15 0 15 0 20 0 20 Cooling 0 50 0 50 0 50 0 50 0 50 Airflow CFM Heating Low 635 700 860 945 880 970 1105 1...

Страница 5: ...Kit KGAHT0101CFP X X X X X Germicidal Air Purifier Model GAPA X X X X X Condensate Neutralizer Kit obtained thru RCD P908 0001 X X X X X Electronic Air Cleaner Model EACA X X X X X Mechanical Air Cle...

Страница 6: ...HK52EA123 X X X Gas Orifice Kit Size 42 Qty 50 KGAHA0150N42 See Installation Instructions for model altitude and heat value usages Gas Orifice Kit Size 43 Qty 50 KGAHA0250N43 Gas Orifice Kit Size 44...

Страница 7: ...ogrammable T2 PAC For use with 1 speed Air Conditioner _F _C Auto Changeover 5 2 Programmable T2 PRH For use with two stage applications _F _C Auto Changeover 7 Day Programmable T2 PRH For multi use s...

Страница 8: ...10 1110 1110 1110 1110 1110 1110 1110 High Heat 1525 0 1 0 1525 1525 1525 1525 1525 1525 1525 1510 1495 1470 2 Ton A C Cooling 700 0 0 50 700 690 690 690 690 2 1 2 Ton A C Cooling 875 0 0 50 835 845 8...

Страница 9: ...ntric 1 1 2 42 12 8 37 11 2 32 9 8 27 8 2 22 6 7 17 5 2 2 70 21 3 70 21 3 70 21 3 70 21 3 70 21 3 70 21 3 80 000 2 Pipe or 2 In Concentric 1 1 2 25 7 6 20 6 1 15 4 6 10 3 0 5 1 5 NA 2 70 21 3 70 21 3...

Страница 10: ...7 7 56 17 1 51 15 5 46 14 0 100 000 2 Pipe or 2 In Concentric 2 27 8 2 22 6 7 17 5 2 12 3 7 7 2 1 NA 2 1 2 62 18 9 60 18 3 58 17 7 56 17 1 55 16 8 53 16 2 120 000 2 Pipe or 3 In Concentric 3 one disk...

Страница 11: ...60120 20_F 6 7_C 3 49 14 9 70 21 3 70 21 3 70 21 3 70 21 3 0_F 17 8_C 3 26 7 9 51 15 5 58 17 7 70 21 3 70 21 3 20_F 28 9_C 3 15 4 6 35 10 7 40 12 2 50 15 2 59 18 0 Pipe length ft m specified for maxim...

Страница 12: ...RMOSTAT TERMINALS FIELD SUPPLIED FUSED DISCONNECT CONDENSING UNIT FURNACE COM R W C Y R G GND GND FIELD 24 VOLT WIRING FIELD 115 208 230 460 VOLT WIRING FACTORY 24 VOLT WIRING FACTORY 115 VOLT WIRING...

Страница 13: ...RANCE TO COMBUSTIBLES LIT TOP A09681 TYPICAL INSTALLATIONS COMBUSTION AIR PIPE A C COIL OUTDOOR UNIT VENT PIPE HUMIDIFIER GAS FIRED WATER HEATER ELECTRONIC AIR CLEANER AIRFLOW FRONT OF FURNACE A06511...

Страница 14: ...e vibration transmission Primary Heat Exchangers Primary heat exchangers shall be 3 Pass 20 gauge corrosion resistant aluminized steel of fold and crimp sectional design and applied operating under ne...

Отзывы: