Flash Code
Type
Amber LED Description
Reset
Time
Mode
Possible Causes
Actions
82
System
Malfunction
SUCTION OVER TEMP
LOCKOUT
(Elevated from fault code
72 after 3 occurrences)
4 Hours
Both
Incorrect refrigerant
charge
Check refrigerant amount
Cool
Uninsulated vapor
line
Insulate the vapor line
Cool
Indoor TXV opera-
tion
Troubleshoot TXV
Heat
Outdoor EXV opera-
tion
Troubleshoot EXV
Both
Reversing valve by-
pass
troubleshoot reversing valve
83
System
Malfunction
LOW PRESSURE LOCK-
OUT FOR 4 HOURS
(Elevated from fault code
32 after 3 occurrences)
4 Hours
Cool
Cooling in Low Am-
bient region (55 ° F
and below) with
”Low Ambient Cool-
ing Control” dis-
abled
Enable ”Low Ambient Cooling” via user
interface
Cool
Outside Normal Op-
erating Range (e.g.
improper load cal-
culation, system
match issue, outside
cooling range etc.)
Consult Application Guidelines
Cool
Service Valve left
closed (Liquid or
Vapor)
Ensure Service Valves are open
Cool
Undercharged Sys-
tem
Check system subcooling to determine
charge status, if low add charge using
Charging Mode (follow proper charging
procedures)
Cool
Indoor Airflow too
low or off
Check Indoor for clogging (ice or debris)
and clean or de---ice if necessary; Trou-
bleshoot Indoor fan motor and make sure
it is working; follow Indoor Airflow trou-
bleshooting instruction
Cool
Restriction in Filter
Drier plus Long Line
Application and filter
drier on Indoor Unit
Clean System (refer to application guide-
line) and replace filter drier
Cool
Restriction due to
debris
Clean System (refer to application guide-
line) and replace filter drier
Cool
Restriction in Cir-
cuits or Tubing
Check kinks and straighten or replace cir-
cuits
Heat
Troubleshoot EXV (see guide below)
Heat
Outside Normal Op-
erating Range (e.g.
improper load cal-
culation, system
match issue, outside
heating range etc.)
Consult Application Guidelines
Heat
Service Valve left
closed (Liquid Ser-
vice Valve)
Ensure Liquid Service Valve is open
Heat
Outdoor Airflow too
low or off
Check Outdoor for clogging (ice or de-
bris) and clean or de---ice if necessary;
Troubleshoot Outdoor fan motor and
make sure it is working; follow Outdoor
Airflow troubleshooting instruction
Heat
Undercharged Sys-
tem
Check charge in cooling (if in Cooling
Charge Mode Ambient Range), if low add
charge using Charging Mode (follow
proper charging procedures); if outside
cooling charge mode range, pull out
charge, weigh in using heating charge
mode
Heat
Restriction due to
debris
Clean System (refer to application guide-
line) and replace filter drier
Both
Restriction in Filter
Drier plus filter drier
on Outdoor Unit
Clean System (refer to application guide-
line) and replace filter drier
Both
Expansion Device
Restriction
If short lineset (less than 15 ft.) Trou-
bleshoot TXV (see guide below); replace
if necessary