Be sure to inspect the unit before proceeding with these steps. Start with problem 1, then problem 2 and so on.

Table 1 – Troubleshooting

Problem:

S

Possible causes:

S

You should try this:

1

Infinity Air Purifier power indicator light

located on the door is off.

S

Power switch is not in the on (closed) position.

S

Make sure the switch is on and using a
multimeter check to see that 115 Volt power is

available.

S

Door is not closed. A magnet in the door is used
to activate safety reed switches in the power

supply when the door is installed.

S

The door magnet is missing or has fallen out.

S

Re-cement loose door magnet with a suitable
adhesive.

S

The door safety reed switches may be defective.

S

If the unit switch is on and 115 Volt power is
available through the service cord, a door

magnet moved in close proximity of the power
supply will cause the reed switches to audibly
click and the power supply will turn on.

S

Furnace blower is not operating. Power will not
be supplied from the furnace control’s EAC

terminals unless the blower is running

.

S

Make sure the furnace blower is operating.

S

Bent pins or loose connection in the molex plug
of the service cord.

S

Replace Service cord or replace entire power
supply / field enhancement module assembly if

required.

S

The power supply may be defective.

S

Replace entire power supply / field enhancement
module assembly.

S

The light pipe transferring the light from the
LED’s on the power supply to the door may be

broken.

S

Replace access door.

2

Power Indicator light cycles on and off

intermittently.

S

Overload condition activating the safety
circuitry

S

S

Unit is wet. (Water may be entering the unit from
a source such as condensate or dripping from a

frozen evaporator coil.)

S

Remove the access door and the air purifier
cartridge. Power the unit then use a spare door

magnet or “service” magnet to activate the air
purifier power supply. Turn out the lights and
observe for arcing.

S

Grounding paths in the unit are interrupted due
to breakage , corrosion or loose contact.

S

Make sure all three grounding clips (FEM to
cabinet, safety screen to cabinet, cartridge to

cabinet on the leaving air side) are securely in
place and making clean contact.

S

Arcing to ground (such as unit cabinet ) is
occurring.

S

Make sure the safety screen is clear and remove
debris.

S

Arcing to ground is occurring due to debris
lodged in the safety screen or across ionization

grid.

S

Make sure the ionization grid is secured in place
with all four clips and centered in the FEM

housing.

S

Ionization grid is not centered or is loose and not
clipped in place, possibly touching the air

purifier cartridge or safety screen.

S

Verify that the ionization grid is clean and intact.

S

Electrode wire is loose and making contact with
the enhancement module wall.

S

Make sure the field electrode wire is wound
through the spools on the enhancement module

with sufficient tension and tied to itself at the end
termination. If it is loose rewind and retie it.

S

Field electrode wire is damaged or nicked

.

S

If the field electrode wire is damaged or nicked,
replace entire power supply / field enhancement

module assembly.

3

Air Purifier Cartridge has smallsinge or char

marks on the frame.

S

The cartridge is installed backwards

S

Turn off the unit and remove the access panel.

S

Replace the air purifier cartridge with Factory
Authorized Replacement Cartridge and ensure

airflow direction arrows are correct.

4

The wall control will not work.

S

The wire in the wall OR the wall control may be
defective.

S

Remove the wall control and test it right beside
the unit using another shorter wire. If the wall

control works there, change the wire. If it does
not, change the wall control.

S

The wires may be in reverse position.

S

Ensure that the color coded wires have been
connected to their appropriate places.

S

The wires may be broken.

S

Inspect every wire and replace any that are
damaged.

S

There may be a short-circuit.

S

With the help of a multimeter, check for
continuity.

5

The 20-minute lighted push- button switch

doesn’t work OR its indicator light doesn’t

stay on.

S

The switch may be defective.

S

Jump the OL and OC terminals. If the unit
switches to high speed, then the wires are not the

problem. Replace the push-button.

S

The wires may be defective OR may not be
connected properly.

S

Ensure that the color-coded wires have been
connected to their appropriate places.

GAP

A

A

Содержание 1625

Страница 1: ... les risques de choc electrique et A06054 Fig 1 GAPAA UNIT SAFETY CONSIDERATIONS Improper installation adjustment alteration service maintenance or use can cause explosion fire electrical shock or other conditions which may cause death personal injury or property damage Consult a qualified installer service agency or your distributor or branch for information or assistance The qualified installer ...

Страница 2: ...ion should be done at every change of the air purifier cartridge minimum annually HIGH VOLTAGE HAZARD Failure to follow this warning could result in personal injury or death This air purifier utilizes high voltage If you notice water running into or around the air purifier water stains on the purifier cartridge or on the Enhancement Module walls or cabinet shut off the air purifier and call your s...

Страница 3: ...ifier should be readily accessible Enough room should be provided for periodic replacement of the air purifier cartridges ELECTRIC SHOCK AND UNIT DAMAGE HAZARD Failure to follow this warning could result in personal injury or death Only a trained experienced service person should install the purifier A thorough check of the unit installation should be completed before unit operation Before perform...

Страница 4: ...low Furnace Note When transitioning between two different sized components furnace purfier the minimum transition angle at the larger of the two components must be no less than 45 degrees A09022 Fig 4 Perfect Air Purifier Cabinet Orientation with Transition Furnace Adapters x2 Return Duct Adapters x4 Return Duct Furnace Adapters x2 Return Duct Adapters x4 Return Duct Top Mount Bottom Mount Side Mo...

Страница 5: ...d be used to connect the upstream side of the air purifier cabinet to the return air duct see Fig 7 g Install foam tape between the furnace and the air purifier cabinet h Mounting holes are provided for ductwork and furnace at tachment Note Slip S cleats onto flanges on air return duct side A05277 Fig 7 Use of Return Duct Adapters UNIT DAMAGE HAZARD Failure to follow this caution may result in uni...

Страница 6: ...r supply e Attach the quick connect terminals to the furnace EAC 1 and EAC 2 spade connections Attach the ground ring to furnace chassis ground NOTE The purifier is to be powered by 115v 60 Hz NOTE The purifier should only be powered when airflow is present The furnace control EAC spade connections provide power only when the furnace blower is operating If EAC connections are not available an alte...

Страница 7: ...he off position Remove the purifier door Slide out the old air purifier cartridge and discard Install the new air purifier cartridge Make sure the power cord is flexed out of the way to avoid damage to the air purifier cartridge pleats during insertion NOTE Verify that the air purifier cartridge is installed correctly Make sure that the arrows on the air purifier cartridge point toward the fan coi...

Страница 8: ...E SHARP BE VERY CAREFUL DURING CLEANING Tip of point with residue Tip of point after cleaning A06671 Fig 11 Removal of Deposits from Ionization Pins TROUBLESHOOTING SAFETY HAZARD Failure to follow this caution may result in personal injury or equipment damage The following instructions are for use by qualified personnel only CAUTION ELECTRICAL SHOCK HAZARD Failure to follow this warning could resu...

Страница 9: ...o cabinet cartridge to cabinet on the leaving air side are securely in place and making clean contact S Arcing to ground such as unit cabinet is occurring S Make sure the safety screen is clear and remove debris S Arcing to ground is occurring due to debris lodged in the safety screen or across ionization grid S Make sure the ionization grid is secured in place with all four clips and centered in ...

Страница 10: ...FM 1600 2000 Efficiency MERV 15 MERV 15 Replacement Cartridge GAPCCCAR1625 GAPCCCAR2025 Pressure Drop Maximum Airflow 25 InH20 25 InH20 Dimensions GAPAAXBB1625 GAPAAXBB2025 A 18 3 8 in 466 7mm 21 7 8 in 555 6mm B 15 1 8 in 384 1mm 18 5 8 in 473 1mm C 11 1 8 in 282 6mm 11 1 8 in 282 6mm D 17 1 2 in 444 5mm 21 in 533 4mm E 22 1 8 in 562mm 22 1 8 in 562mm F 25 1 4 in 642 4mm 25 1 4 in 642 4mm 7 16 11...

Страница 11: ...s and exclusions listed below and on the reverse if any of this document OWNER OCCUPIED RESIDENTIAL APPLICATIONS This warranty is to the original purchasing owner and is transferable only to the extent and as stated in the Warranty Conditions and below The warranty period in years depending on the part and the claimant is as shown in the chart below Limited Warranty Years Product Original Owner Su...

Страница 12: ...IMPLIED WARRANTY OR CONDITION LASTS SO THE ABOVE MAY NOT APPLY TO YOU THE EXPRESS WARRANTIES MADE IN THIS WARRANTY ARE EXCLUSIVE AND MAY NOT BE ALTERED ENLARGED OR CHANGED BY ANY DISTRIBUTOR DEALER OR OTHER PERSON WHATSOEVER THIS WARRANTY DOES NOT COVER 1 Labor or other costs incurred for diagnosing repairing removing installing shipping servicing or handling of either defective parts or replaceme...

Отзывы: