background image

IX.

LIQUID LINE STRAINERS

The liquid line strainers (to protect metering devices) are made of
wire mesh and are located in the liquid lines on the inlet side of the
metering devices.

X.

HIGH FLOW VALVES

High flow valves are located on the compressor hot gas and
suction tubes. Large black plastic caps distinguish these valves
with O-rings located inside the caps. These valves can not be
accessed for service in the field. Ensure the plastic caps are in
place and tight or the possibility of refrigerant leakage could occur.

XI.

TIME-DELAY RELAY

The Time-Delay Relay (TDR) is a solid-state control, recycle
delay timer which keeps indoor blower operating for 60 sec. after
thermostat is satisfied. This delay enables blower to remove
residual cooling in coil after compression shutdown, thereby
improving efficiency of system. The sequence of operation is that
on closure of wall thermostat and at end of a fixed on delay of 1

sec., fan relay is energized. When thermostat is satisfied, an off
delay is initiated. When fixed delay of 60± 5 sec. is completed, fan
relay is de-energized and fan motor stops. If wall thermostat closes
during this delay, TDR is reset and fan relay remains energized.
TDR is a 24-v device that operates within a range of 15-v to 30-v
and draws about 0.5 amps. If the blower runs continuously instead
of cycling off when the fan switch is set on AUTO, the TDR is
probably defective and must be replaced.

XII.

LOSS OF CHARGE SWITCH

The loss of charge switch is located on the outdoor liquid line. This
switch contains a Schrader core depressor. This switch opens at 7
psig and closes at 22 psig. No adjustment is necessary.

NOTE:

Because these switches are attached to refrigeration

system under pressure, it is not advisable to remove this device for
troubleshooting unless you are reasonably certain that a problem
exists. If switch must be removed, remove and recover all system
charge so that pressure gauges read 0 psi. Never open system
without breaking vacuum with dry nitrogen.

XIII.

CHECK DEFROST THERMOSTAT

There is a liquid header with a brass distributor and feeder tube
going into outdoor coil. At the end of 1 of the feeder tubes, there
is a 3/8-in. OD stub tube approximately 3 in. long (See Fig. 36).
The defrost thermostat should be located on this stub tube. Note
that there is only 1 stub tube used with liquid header, and on most
units it is the bottom circuit.

XIV.

DEFROST THERMOSTAT

Defrost thermostat signals heat pump that conditions are right for
defrost or that conditions have changed to terminate defrost. It is
a thermally actuated switch clamped to outdoor coil to sense its
temperature. Normal temperature range is closed at 30° +/- 3°F
and open at 80° +/- 5°F.

NOTE:

The defrost thermostat must be located on the liquid side

of the outdoor coil on the bottom circuit and as close to the coil as
possible.

TROUBLESHOOTING

Refer to the Cooling and Heating Troubleshooting Chart (Table
11) for troubleshooting information.

START-UP CHECKLIST

Use the Start-Up Checklist to ensure proper start-up procedures are
followed.

SUCTION LINE PRESSURE (KILOP

ASCALS)

SUCTION LINE PRESSURE (PSIG)

-7

-1

4

10

16

21

27

SUCTION LINE TEMPERATURE (

°

F)

SUCTION LINE TEMPERATURE (

°

C)

689

620

551

483

414

345

276

207

100

90

80

70

60

50

40

30

(060) 60HZ CHARGING CHART

20.0

30.0

40.0

50.0

60.0

70.0

80.0

OUTDOOR TEMP
     

°

 F

°

 C

115

46

125

52

45

7

55

13

65

18

75

24

95

35

105

41

85

29

50JS500093

C00032

Fig. 28—Cooling Charging Chart, 601A060 Units

—22—

Содержание 030-060

Страница 1: ...ntrols and wiring 20 Refrigerant circuit 20 Indoor airflow 20 Metering device 20 Liquid line strainers 22 High Flow Valves 22 Time delay relay 22 Loss of charge switch 22 Check defrost thermostat 22 Defrost Thermostat 22 TROUBLESHOOTING 22 START UP CHECKLIST 22 NOTE TO INSTALLER READ THESE INSTRUCTIONS CAREFULLY AND COMPLETELY before installing this unit Also make sure the Owner s Manual and Servi...

Страница 2: ...rb is critical for a watertight seal Install gasketing material supplied with the roof curb Improperly applied gasketing also can result in air leaks and poor unit performance Curb should be level to within 1 4 in See Fig 6 This is necessary for unit drain to function properly Refer to accessory roof curb installation instructions for additional information as required B SLAB MOUNT Place the unit ...

Страница 3: ...02 991 1 19 5 495 3 13 7 348 0 15 0 381 0 601A036 208 230 3 60 460 3 60 291 132 0 37 02 940 3 19 5 495 3 13 7 348 0 13 0 330 2 601A042 208 230 3 60 460 3 60 323 146 5 37 02 940 3 19 7 500 4 14 0 355 6 13 0 330 2 602A030 208 230 3 60 320 145 2 37 02 940 3 19 7 500 4 14 0 355 6 17 6 447 0 602A036 208 230 3 60 460 3 60 328 148 8 37 02 940 3 19 7 500 4 14 0 355 6 16 5 419 1 C00137 3 ...

Страница 4: ...8 990 2 19 9 505 5 15 7 398 8 17 0 431 8 601A060 208 230 3 60 460 3 60 418 189 6 38 98 990 2 19 9 505 5 15 7 398 8 17 0 431 8 602A042 208 230 3 60 460 3 60 350 158 8 40 98 1040 9 19 9 505 5 15 7 398 8 16 6 421 6 602A048 208 230 3 60 460 3 60 315 170 1 40 98 1040 9 19 9 505 5 15 7 398 8 18 0 457 2 602A060 208 230 3 60 460 3 60 428 194 1 42 98 1091 7 19 9 505 5 15 7 398 8 17 6 447 0 C00136 4 ...

Страница 5: ...nto ductwork and cause serious injury or death Install a 90 degree turn in the return ductwork between the unit and the conditioned space If a 90 degree elbow cannot be installed then a grille of sufficient strength and density should be installed to prevent objects from falling into the conditioned space Units with electric heaters require 90 degree elbow in supply duct 1 All units should have fi...

Страница 6: ...bracket must also be used when required by code for hurricane or seismic conditions This bracket is available through Micrometl C00076 Gasket around outer edge Insulated deck pan Gasket around duct S A R A HVACunit base Gasketing outer flange Flashing field supplied Roofing mater ial field supplied Cant strip field supplied Provided with roofcurb Roof Duct wo rk field supplied Insulation field sup...

Страница 7: ...ts on the compressor end of the unit Condensate water can be drained directly onto the roof in rooftop installations where permitted or onto a gravel apron in ground level installa tions Install a field supplied condensate trap at end of condensate connection to ensure proper drainage Make sure that the outlet of the trap is at least 1 in lower than the drain pan condensate connection to prevent t...

Страница 8: ...8 602A060 NOMINAL CAPACITY ton 2 1 2 3 3 1 2 4 5 OPERATING WEIGHT lb 320 328 350 375 428 COMPRESSOR QUANTITY 1 TYPE SCROLL COMPRESSOR REFRIGERANT R 22 REFRIGERANT METERING DEVICE AccuRater Refrigerant R 22 Quantity lb 6 4 7 0 10 8 10 1 12 3 ORIFICE ID in 0 073 0 076 0 080 0 088 0 093 ORIFICE OD in 0 043 2 0 040 2 0 052 2 0 057 2 0 063 2 OUTDOOR COIL Rows Fins in Face Area sq ft 2 17 10 3 2 17 10 3...

Страница 9: ... Do not damage internal components when drilling through any panel to mount electrical hardware con duit etc A HIGH VOLTAGE CONNECTIONS The unit must have a separate electrical service with a field supplied waterproof disconnect switch mounted at or within sight from the unit Refer to the unit rating plate NEC and local codes for maximum fuse circuit breaker size and minimum circuit amps ampacity ...

Страница 10: ...Fig 12 Wiring Schematics 208 230 3 60 C00134 10 ...

Страница 11: ...Fig 13 Wiring Schematics 460 3 60 C00135 11 ...

Страница 12: ... 0 11 3 15 0 15 0 19 9 10 4 12 0 20 8 24 1 31 3 36 1 41 6 48 0 20 2 20 2 33 2 35 2 46 3 50 3 59 3 65 3 72 2 80 2 25 25 40 40 50 60 60 70 80 90 460 3 60 414 506 6 7 45 0 8 1 8 5 10 15 20 0 6 0 12 0 18 0 24 1 11 0 18 5 26 0 33 5 41 0 15 20 30 35 45 048 208 230 3 60 187 253 14 1 105 1 5 3 5 3 8 5 0 7 5 10 0 11 3 15 0 15 0 20 0 10 4 12 0 20 8 24 1 31 3 36 1 41 6 48 0 22 6 22 6 35 7 37 7 48 7 52 7 61 7...

Страница 13: ...59 4 68 3 74 3 81 2 89 2 35 35 50 50 60 60 70 80 90 90 460 3 60 414 506 9 0 62 0 9 3 2 5 10 15 20 6 12 18 24 1 15 4 22 9 30 4 37 9 45 4 20 25 35 40 50 452 5 v 457 7 v 455 2 v LEGEND FLA Full Load Amps LRA Locked Rotor Amps MCA Minimum Circuit Amps MOCP Maximum Overcurrent Protection RLA Rated Load Amps NOTES 1 In compliance with NEC National Electrical Code requirements for multimotor and combinat...

Страница 14: ...tage is 208 v rewire transformer primary as described in Special Procedures for 208 v Operation section E SPECIAL PROCEDURES FOR 208 V OPERATION 1 Disconnect the yellow primary lead from the transformer See unit wiring label See Fig 12 2 Connect the yellow primary lead to the transformer terminal labeled 200 v Indoor blower motor speeds may need to be changed for 208 v operation Refer to indoor ai...

Страница 15: ... 6 Each unit system has 2 Schrader type ports one low side Schrader fitting located on the suction line and one high side Schrader fitting located on the compressor dis charge line Be sure that caps on the ports are tight 7 High flow valves are located on the compressor hot gas and suction tubes These valves can not be accessed for service in the field Ensure the plastic caps are in place and tigh...

Страница 16: ...charge to nameplate amount This information may be obtained from the physical data table also IMPORTANT When evaluating the refrigerant charge an indi cated adjustment to the specified factory charge must always be very minimal If a substantial adjustment is indicated an abnormal condition exists somewhere in the cooling system such as insuf ficient airflow across either coil or both coils C REFRI...

Страница 17: ...lles are open free from obstructions and adjusted properly Airflow can be changed by changing the lead connection of the blower motor Unit 601A and 602A three speed motors except 602A030 are factory wired for low speed operation Unit 602A030 is factory wired for medium speed For 208 230 v Motors The motor leads are color coded as follows 3 SPEED Black high speed Blue medium speed Red low speed To ...

Страница 18: ...mproper and dangerous operation Label all wires prior to disconnecting when servicing The minimum maintenance requirements for this equipment are as follows 1 Inspect air filter s each month Clean or replace when necessary 2 Inspect indoor coil drain pan and condensate drain each cooling season for cleanliness Clean when necessary 3 Inspect blower motor and wheel for cleanliness each cooling seaso...

Страница 19: ... or bends 2 If fan needs to be removed remove screws holding outdoor air intake grille and remove grille 3 Loosen the setscrew and slide the fan off the motor shaft 4 When replacing fan blade position blade so that the hub is 1 8 in See Fig 19 away from the motor end 1 8 in of motor shaft will be visible TABLE 7 WET COIL AIR DELIVERY UNIT 601A 030 060 DEDUCT 10 PERCENT FOR 208 V UNIT MOTOR SPEED E...

Страница 20: ...en and free from obstructions and that the air filter is clean When necessary refer to Indoor Airflow and Airflow Adjustments section to check the system airflow VIII METERING DEVICE Refrigerant metering devices are fixed orifices and are located in the inlet header to the indoor and outdoor coils TABLE 8 WET COIL AIR DELIVERY UNIT 602A 030 060 DEDUCT 10 PERCENT FOR 208 V UNIT MOTOR SPEED EXTERNAL...

Страница 21: ... 55 13 65 18 75 24 95 35 105 41 85 29 50JS500090 C00029 Fig 25 Cooling Charging Chart 601A036 Units SUCTION LINE PRESSURE KILOPASCALS SUCTION LINE PRESSURE PSIG 7 1 4 10 16 21 27 SUCTION LINE TEMPERATURE F SUCTION LINE TEMPERATURE C 689 620 551 483 414 345 276 207 100 90 80 70 60 50 40 30 042 60HZ CHARGING CHART 20 0 30 0 40 0 50 0 60 0 70 0 80 0 OUTDOOR TEMP F C 115 46 125 52 45 7 55 13 65 18 75 ...

Страница 22: ...justment is necessary NOTE Because these switches are attached to refrigeration system under pressure it is not advisable to remove this device for troubleshooting unless you are reasonably certain that a problem exists If switch must be removed remove and recover all system charge so that pressure gauges read 0 psi Never open system without breaking vacuum with dry nitrogen XIII CHECK DEFROST THE...

Страница 23: ...S SUCTION LINE PRESSURE PSIG 20 0 7 27 21 16 10 4 1 80 0 70 0 60 0 50 0 40 0 30 0 50JX500220 030 60 Hz CHARGING CHART OUTDOOR TEMP F C 125 52 115 46 105 41 95 35 85 29 75 24 65 18 55 13 45 7 SUCTION LINE TEMPERATURE DEG C SUCTION LINE TEMPERATURE DEG F C99032 Fig 29 Cooling Charging Chart 602A 030 Units 689 100 0 30 0 40 0 50 0 60 0 70 0 80 0 90 0 207 276 345 414 483 551 620 SUCTION LINE PRESSURE ...

Страница 24: ... 0 00 0 00 0 00 0 02 0 04 0 06 0 07 0 09 0 10 0 11 15 kW 0 00 0 00 0 00 0 02 0 04 0 06 0 08 0 10 0 12 0 14 0 16 0 18 20 kW 0 00 0 00 0 02 0 04 0 06 0 08 0 09 0 11 0 13 0 15 0 17 0 19 LARGE CABINET STATIC CFM 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500 5 kW 0 00 0 00 0 00 0 01 0 02 0 03 0 04 0 05 0 06 0 07 0 08 0 09 0 10 0 11 0 12 10 kW 0 00 0 00 0 01 0 02 0 03 0 04 0...

Страница 25: ...r Replace and determine cause Insufficient line voltage Determine cause and correct Blocked outdoor coil Determine cause and correct Defective run start capacitor overload or start relay Determine cause and replace Defective thermostat Replace thermostat Faulty outdoor fan motor or capacitor Replace Damaged reversing valve Determine cause and correct Restriction in refrigerant system Locate restri...

Страница 26: ...tor has failed IFM operation is intermittent Water dripping into motor Verify proper drip loops in connector wires Connectors not firmly sealed Gently pull wires individually to be sure they are crimped into the housing IFM Indoor Fan Motor START UP CHECKLIST REMOVE AND STORE IN JOB FILE I PRELIMINARY INFORMATION Model No Serial No Date Technician Job Location II PRE START UP ____ Verify that all ...

Отзывы: