Form: 2405
Universal Communication Gateway Reference Manual
Date: 01-25-2019
Revision: 8
Bryan Steam LLC, 783 North Chili Avenue, Peru, IN 46970
Web:
Phone:
765.473.6651
Fax:
765.473.3074
E-mail:
36
5.2
SEIMENS RWF55 MODBUS RTU MAPPINGS TO BACNET, METASYS N2 AND
LONWORKS
See Siemens RWF55 device manual for more information.
FPC-N34
FPC-N35
Point Name
BACnet
Data
Type
BACnet
Object
Id
N2
Data
Type
N2 Point
Address
Lon Name
Lon SNVT Type
Com Status
BI
1
DI
1
nvoComStatus_XXX SNVT_switch
Analog Input InP1
AI
1
AI
1
nvoInP1_XXX
SNVT_count_inc_f
Analog Input InP2
AI
2
AI
2
nvoInP2_XXX
SNVT_count_inc_f
Analog Input InP3
AI
3
AI
3
nvoInP3_XXX
SNVT_count_inc_f
Actual Setpoint
AI
4
AI
4
nvoActSP_XXX
SNVT_count_inc_f
Setpoint 1
AV
5
AO
5
nvi/nvoSP_1_XXX
SNVT_count_inc_f
Setpoint 2
AV
6
AO
6
nvi/nvoSP_2_XXX
SNVT_count_inc_f
Analog Input InP3
AI
7
AI
7
nvoInP3Unfil_XXX
SNVT_count_inc_f
Actual Angular Positioning
AI
8
AI
8
nvoActAngPos_XXX SNVT_count_inc_f
Burner Alarm
AI
9
AI
9
nvoBrnrAlm_XXX
SNVT_count_inc_f
Activation Remote Operation
AV
10
AO
10
nvi/nvoREM_XXX
SNVT_count_inc_f
Controller Off In Remote
Setpoint
AV
11
AO
11
nvi/nvorOFF_XXX
SNVT_count_inc_f
Switch-On Threshold Remote
AV
12
AO
12
nvi/nvorHYS1_XXX
SNVT_count_inc_f
Switch-Off Threshold Down
Remote
AV
13
AO
13
nvi/nvorHYS2_XXX
SNVT_count_inc_f
Switch-Off Threshold Up
Remote
AV
14
AO
14
nvi/nvorHYS3_XXX
SNVT_count_inc_f
Setpoint Remote
AV
15
AO
15
nvi/nvoSPr_XXX
SNVT_count_inc_f
Burner Release Remote
Operation
AV
16
AO
16
nvi/nvoRK1_XXX
SNVT_count_inc_f
Relay K2 Remote Operation
AV
17
AO
17
nvi/nvoRK2_XXX
SNVT_count_inc_f
Relay K3 Remote Operation
AV
18
AO
18
nvi/nvoRK3_XXX
SNVT_count_inc_f
Relay K6 Remote Operation
AV
19
AO
19
nvi/nvoRK6_XXX
SNVT_count_inc_f
Step-By-Step Control Rem
Operation
AV
20
AO
20
nvi/nvorStEP_XXX
SNVT_count_inc_f
Angular Pos Output Remote
Operation
AV
21
AO
21
nvi/nvorY_XXX
SNVT_count_inc_f
Switch-On Threshold Remote
AV
22
AO
22
nvi/nvorHYS4_XXX
SNVT_count_inc_f
Switch-Off Threshold Down
Remote
AV
23
AO
23
nvi/nvorHYS5_XXX
SNVT_count_inc_f
Switch-Off Threshold Up
Remote
AV
24
AO
24
nvi/nvorHYS6_XXX
SNVT_count_inc_f