Form: 2405
Universal Communication Gateway Reference Manual
Date: 01-25-2019
Revision: 8
Bryan Steam LLC, 783 North Chili Avenue, Peru, IN 46970
Web:
Phone:
765.473.6651
Fax:
765.473.3074
E-mail:
23
4
SETUP UCG
4.1
DEVICES AND POINT COUNT
AVAILABILITY
•
The total number of devices
attached to UCG (RER) cannot
exceed 1500 Modbus registers for
BACnet MS/TP, BACnet/IP, Modbus
TCP/IP or Metasys N2.
•
The total number of devices
attached to UCG (LER) cannot
exceed 1000 Modbus registers for
LonWorks
Devices Point Count
SOLA
28
RWF40 15
LMV5... 32
RM7800 37
LMV3… 9
PD765
32
Table 2 - Modbus Registers
4.2
UCG PROTOCOL SETUP
4.2.1
CONFIGURE THE DIP
SWITCHES
DIP switches on the ProtoNode, located
inside UCG, may need to be set for the
appropriate devices and communication
settings. These DIP switches are factory
preset when the field device and protocol
are known at the time of ordering. If
needed, remove the cover of the
ProtoNode located inside the UCG.
Note: If the DIP switches need to be
changed then the power to the unit will
need to be shut off before proceeding.
4.2.1.1
BMS PROTOCOL (DIP SWITCH S0
– S3)
The S bank of DIP switches (S0 – S3) are
used to select BACnet MS/TP, BACnet IP,
Modbus TCP, or Metasys N2 configurations
on the UCG (RER). The “S0 – S3” bank of DIP
switches on the UCG (LER) (LonWorks) are
disabled. See Table 2 below and set S bank
Dip switches to the desired configuration.
Figure 20 - S Bank DIP Switches
UCG RER
S Bank DIP Switches
Profile
S0 S1 S2 S3
BACnet IP
Off Off Off Off
BACnet MSTP
(multi-node)
On Off Off Off
BACnet MSTP
(single node)
Off Off On Off
Metasys N2
Off On Off Off
Modbus TCP/IP On On Off Off
Table 3 - BMS Protocol Selection
4.2.1.2
SETTING THE SERIAL BAUD RATE
DIP Switches B0 – B3 can be used to set the
serial baud rate to match the baud rate
provided by BMS. See Table 4 for B bank
configurations.
Figure 21 - B Bank DIP Switches