Bryan Boilers HE-CLM Series Скачать руководство пользователя страница 1

Quality Construction Features

A.

  Heavy steel boiler frame, built and stamped in accordance 

with the ASME Boiler Code, Section IV.

B.

  Large  volume  water leg  down comers  promote  rapid internal 

circulation, temperature equalization and effi cient heat transfer.

C.

  Bryan bent water tubes are fl exible, individually replaceable with-

out welding or rolling. Never more than two tube confi gurations. 

D.

  Boiler  tube  and  furnace  area  access panel: heavy gauge 

steel casing with 2" high temperature ceramic  fi ber and insulation, 
bolted and tightly sealed to boiler frame.

E.

  Jacket access panels make the interior of the boiler easily 

accessible for service and inspection.

F.

  Steel boiler jacket with 16 gauge rust-resistant zinc coating 

and attractive enamel fi nish,  insulated with 1½" fi berglass to insure 
exceptionally cool outer surface.

G.

  Minimum sized fl ue vent. 

H.

 Forced draft, fl ame retention head type burner. Effi cient 

combustion and quiet operation. 

I.

   All controls, gauges, relief valve(s) are factory installed and 

wired and easily accessible for servicing.

J.

  Electrical box: all controls installed and connected to terminal 

strip.

K .

  Water side interior accessible for cleanout and inspection, 

front and rear openings, upper and lower drums.

L.

  Steel plate boiler base with lightweight, high temperature 

insulating fi rebrick combustion chamber, designed for maximum 
combustion effi ciency.

Form No. 6700

(Rev. 5/07)

Guaranteed 85% 
 effi ciency

•   With HE-CLM Series Boilers,  
 

you get a guaranteed 85%  

 combustion 

effi ciency result- 

 

ing from a uniquely designed  

 

integrated extended surface  

 heat 

extractor.

•   What's more, HE-CLM Boilers  
 

offer high operating 

 effi ciency—at all normal  
 operation 

temperatures— 

 

 

without the complications 

 

of condensation concerns.

Bryan HE-CLM Series Boiler Specifi cations

Bryan “Flexible Water Tube”

HE-CLM Series Water Boilers

900,000 to 3,000,000 BTUH

Forced draft gas fi red

Originators of the “Flexible Water Tube” design

Model HE-CLM300-W-FDG

 BOILER            INPUT            OUTPUT @ 85% EFFICIENCY

(1)

    HTG.SURFACE    APPROX. SHIP

 MODEL         MBH (KW)            MBH (KW) 

   HP (KW)          SQ.FT.(M

2

)            LBS. (KG)

HE-CLM90

          900 (264) 

765 (224) 

  23 (224) 

   171 (15.9)           2,110 (957) 

HE-CLM120

       1,200 (352)           1,020 (299)  

  30 (299) 

    227 (21.1)           2,400 (1,089) 

HE-CLM150

       1,500 (440)           1,275 (374)  

  38 (374) 

    282 (26.2)           2,860 (1,297) 

HE-CLM180

       1,800 (527)           1,530 (448)  

  46 (448) 

    338 (31.4)           3,200 (1,452)

HE-CLM210

       2,100 (615)           1,785 (523) 

  53 (523) 

    394 (36.6)           3,740 (1,697) 

HE-CLM240

       2,400 (703)           2,040 (598)  

  61 (598) 

    451 (41.9)           4,200 (1,905) 

HE-CLM270

       2,700 (791)           2,295 (672)  

  69 (672) 

    506 (47.0)           4,740 (2,150) 

HE-CLM300

       3,000 (879)           2,550 (747)  

  76 (747) 

    564 (52.4)           5,175 (2,348) 

NOTES : (1) Output and horsepower based on an average natural gas combustion effi ciency of 85%.