Boiler Control Instruction & Operation Manual
Page 3
3
of
68
Setup & Tuning
Parameter Adjustment
System Menu Continued
Factory
Setting
Range /
Choices
Parameter and Description
76
9 Character
Maximum
Supervisor Password
Allows for custom password to be set. Must be 9 characters or less. Only allows
adjustment of supervisor password (supervisor default: 76). Cannot change Factory
password.
Must enter current installer password.
Must enter new password and press enter.
Must re-enter new password and press enter.
NOTE
:
Can be reset to supervisor default 76 if accessed with the Factory level password (86).
Disabled
Enable/Disable
Warm Weather Shutdown Enable
Disable
Warm Weather Shutdown (WWSD) is not used.
Enable
A central heat boiler start is prevented if the outside temperature is
greater than the WWSD setpoint. WWSD is initiated as soon as outside
air temperature is above WWSD Setpoint. The control does not require
call for heat to be satisfied before entering WWSD.
The boiler will still start in response to a Domestic Hot Water call for heat.
70°F
20 to100 (ºF)
Warm Weather Shutdown Setpoint
The Warm Weather Shutdown (WWSD) Setpoint used to shutdown the boiler when
enabled by the
“WWSD Enable” parameter.
xx/xx/xxxx
NA
System Date
Date used by display Alarm History screen. A battery is provided to maintain the system date
and time while the display is powered down.
xx:xx:xx
NA
System Time
Time used by display Alarm History screen. A battery is provided to maintain the system date
and time while the display is powered down.
Enabled
Enable/Disable
Auto Jump to Home Page
Enable
After 15 minutes of no use, the display will automatically return to the Home
Page.
Disable
Display will not change screens to Home Page after 15 minutes.