Boiler Control Instruction & Operation Manual
Page
30 of 68
Setup & Tuning
Manual Operation
The Firing rate may be adjusted manually using the Operation screen. The user may select Low or High
speeds, or adjust firing rate anywhere between low and high;
Figure 17: Operating Screens
Bar Graph & Trend
Active Sensor, Active Setpoint & Modulation
Auto/Manual
After selecting Manual Mode the User may adjust
modulation manually. Menu also allows for switching of
units from % (default) to RPM.
Rate
Select Manual modulation to enable user adjustment of
firing rate. The factory default is Automatic mode.
High/Low
After selecting Manual Mode the High or Low buttons
drives firing rate to High and Low fire position for
combustion testing.
Service Trend
Service Trend screen shows; boiler temps, firing rate &
demand statuses.
Tune
Tune screen allows for adjustment of parameters related
to the rate of boiler response. This includes PID
settings, Ramp rates and more. For more details on
the Tune Screen see Tune Screen in Adjustable
Parameters Section.
Manual Pump Exercise
Allows the pumps to be set to either ON or Automatic.
When ON is selected pump will run. W hen Automatic is
selected, pump will follow settings assigned in Pump
Adjust Menu.
NOTE:
Manual control mode locks firing rate to a fixed speed. The control stays in manual even through a power
cycle. Select Automatic when commissioning is complete.