11 CHIMNEY AND SMOKE PIPE CONNECTION
Chimney and smoke pipe connection design must be in accordance with DIN 18160.1; dimensions must be
calculated according to DIN EN 13384. For calculations, please consider that with open doors (when stoking
wood) a significantly increased air volume must be led away safely.
Connection of multiple heating devices to one single chimney is permitted for various stove types, when
approved by a qualified chimney sweep.
When using a steel smoke pipe as connecting piece between additional heating surfaces and chimney, the
pipe wall thickness must be at least 2 mm. The connecting piece must be connected directly to the chimney.
For a safe operation a soot fire resistant chimney T400 is required.
All smoke pipe connections must be sealed tightly! Remember to provide access for cleaning!
12 INITIAL OPERATION
Check the correct position of the fireplace parts. The baffle plate (not Iron Dog 06) must touch the back wall.
Up to the first reaching of the maximum operating temperature, the paint keeps hardening. This may cause
some smoke and smell nuisances. Therefore it is important to ensure sufficient room ventilation. Open doors
and windows. Don’t stay in the room longer than necessary.