2009-09-30
Data Sheet 70.3041
Page 4/10
Technical data
Thermocouple input
Input for resistance thermometer
Input for standard signals
Logic inputs
Measuring circuit monitoring
In the event of a fault, the outputs move to a defined (configurable) status.
Designation
Measuring range
Measuring accuracy
Ambient
temperature error
Fe-Con L
Fe-Con J
Fe-Con U
Cu-Con T
NiCr-Ni K
NiCr-Con E
NiCrSi-NiSi N
Pt10Rh-Pt S
Pt13Rh-Pt R
Pt30Rh-Pt6Rh B
W5Re-W26Re C
W3Re-W25Re D
W3Re-W26Re
EN 60584
EN 60584
EN 60584
EN 60584
EN 60584
EN 60584
EN 60584
EN 60584
-200 to + 900°C
-200 to +1200°C
-200 to + 600°C
-200 to + 400°C
-200 to +1372°C
-200 to +1000°C
-100 to +1300°C
0 to 1768°C
0 to 1768°C
0 to 1820°C
0 to 2320 °C
0 to 2495 °C
0 to 2400 °C
≤
0.25%
≤
0.25%
≤
0.25%
≤
0.25%
≤
0.25%
≤
0.25%
≤
0.25%
≤
0.25%
≤
0.25%
≤
0.25% in the range 300 to 1820°C
≤
0.25%
≤
0.25%
≤
0.25%
100 ppm /°C
100 ppm /°C
100 ppm /°C
100 ppm /°C
100 ppm /°C
100 ppm /°C
100 ppm /°C
100 ppm /°C
100 ppm /°C
100 ppm /°C
100 ppm /°C
100 ppm /°C
100 ppm /°C
Cold junction
Pt100, internal
Designation
Connection
Measuring range
Measuring accuracy
Ambient
temperature error
3-/4-wire
2-wire
Pt100
EN 60751 (factory setting)
2-wire / 3-wire / 4-wire
-200 to +850°C
≤
0.05%
≤
0.4%
50 ppm / °C
Pt500
EN 60751
2-wire / 3-wire / 4-wire
-200 to +850°C
≤
0.2%
≤
0.4%
100 ppm /°C
Pt1000
EN 60751
2-wire / 3-wire / 4-wire
-200 to +850°C
≤
0.1%
≤
0.2%
50 ppm /°C
KTY11-6
2-wire
-50 to +150°C
≤
2.0%
50 ppm /°C
Sensor lead resistance
max. 30
Ω
per lead for 3-wire or 4-wire circuit
Measuring current
approx. 250µA
Lead compensation
Not required for 3-wire or 4-wire circuit. With a 2-wire circuit, the lead resistance can be
compensated in software by a correction of the process value.
Designation
Measuring range
Measuring
accuracy
Ambient
temperature error
Voltage
0(2) — 10V
0 — 1V
Input resistance R
IN
> 100k
Ω
≤
0.05%
≤
0.05%
100 ppm / °C
100 ppm / °C
Current
0(4) — 20mA, voltage drop
≤
1.5V
≤
0.05%
100 ppm / °C
Heating current
0 — 50mA AC
≤
1%
100 ppm / °C
Resistance transmitter
min. 100
Ω
, max. 4k
Ω
±4
Ω
100 ppm / °C
Floating contacts
Sensor
Overrange /
underrange
Probe or lead short-circuit
Probe or lead break
Thermocouple
•
-
•
Resistance thermometer
•
•
•
Voltage
2 — 10V
0 — 10V
0 — 1V
•
•
•
•
-
-
•
-
-
Current
4 — 20mA
0 — 20mA
•
•
•
-
•
-
Resistance transmitter
-
-
•
• = recognized - = not recognized