Electrical life:                    

 150,000 ops at rated load 

Dielectric voltage:               2kV AC (rms) IEC 60947-1 
Rated impulse 
 withstand voltage:              4kV (1.2 / 50

µ

S) IEC 60664 

          

     

 

                  Max. DC Load Breaking Capacity                   Electrical Endurance 

 
Housing:                       Flame retardant Lexan 
Protection:                     IP55 / IP20 (rear) 
Weight:                       

 600g 

Mounting:                     Panel mounting. Cut-out = 91 x 91mm (

±

 0.5mm) 

Max. panel thickness:          12mm 
 
Terminal type: 

UL94-V0 rated pluggable and re-wireable female 
connectors comprising: 

                                2-way (Power supply 

1, 2

                                6-way (Relay contacts 

3….8

                                8-way (Phase current and neutral inputs 

9….16

)

 

 

Terminal conductor size:      0.05 - 2.5mm

2

 (30 - 12AWG) 

Recommended tightening 
 torque:                        4.4in lb (0.5Nm) 
Wire stripping length:         0.24 – 0.30in (6 – 7.5mm) 
 
Approvals:                     Conforms to IEC. CE and       and RoHS Compliant. 

 EMC: Immunity: EN/IEC 61000-6-2 

       Emissions: EN/IEC 61000-6-4 

Generic: IEC 60255-26 (EMC), IEC 255-3, IEC 

60255-151 

 

( ) Bold digits in brackets refer to terminal numbers on the rear of the unit. 

 
Options: 
 

 

The P9600 range also includes individual Overcurrent or Earth fault relays 

available with either IDMT or DT characteristics. Please refer to separate data 
sheets. 

 

 

 
 
 
 
 
 
 
 
 
    

 

 

 

TECHNICAL SPECIFICATION 

 
Aux. Supply voltage Un (

1, 2

):  85 – 265VAC/85 - 370VDC

1

 

                                  18 – 55VAC/18 – 72VDC* 
                               

  (Voltage range should be specified at time of        

                                   ordering) 

Rated frequency:                50/60Hz (AC Supplies) 
Isolation:                         Over voltage cat. III 
Rated impulse  
 withstand voltage:             

1

4kV (1.2 / 50

µ

S) IEC 60664 

Power consumption:            3W max. 

* If connecting a fuse externally, a Time Delay type is recommended with a rating of 0.5A or 
higher. 

 

Rated current input In:          5A (directly connected) 
Rated frequency:                50/60Hz 
Burden:                          <0.4VA @ In 
Overload:                       4 x In (continuous) 

 

External CT’s (

9……16

):       Class P recommended. (with 5A secondary) 

Maximum CT primary 
 current rating:                   6000A  

 

Overcurrent settings: 
 Low-set trip (I>):               0.50 – 10.00A (10 – 200%) 
 Low-set time multiplier (k>):  0.05 – 1.00 
 Low-set definite time (t>):     0.05 – 100s 
 High-set trip (I>>):            0.5 – 100A (10 – 2000%) or disable 
 High-set definite time (t>>):  0.05 – 2.5s 

 

Earth fault settings: 
 Low-set trip (I

o

>):              0.10 – 5.00A (2 – 100%) 

 Low-set time multiplier (k

o

>): 0.05 – 1.00 

 Low-set definite time (t

o

>):    0.05 – 100s 

 High-set trip (I

o

>>):           0.10 – 50.00A (2 – 1000%) or disable 

 High-set definite time (t

o

>>): 0.05 – 2.5s 

 

Pick up value:                    +2% of trip setting 
Accuracy: 
 Protection thresholds:         

±

 5% 

 Time delay (DT):              

±

 5% (with a minimum of 50mS) 

 Time delay (IDMT): 

±

 5% (with a minimum of 50mS and I > 1.2 x 

set-trip) 

 Actual phase current:          

±

 1% of rated current In 

 Actual Earth fault current:      

±

 1% of rated current In 

Display update time:            <1 sec. 
Repeat accuracy:               

±

 0.5% @ constant conditions 

 

Ambient temperature:          -10 to +60

°

Relative humidity:               +95% 

 

Output: 
 (RL1 - 

3, 4, 5

):                  1 x SPDT relay 

 (RL2 - 

6, 7, 8

):                  1 x SPDT relay 

Output rating:                   AC1  250V 8A (2000VA) 
                                  AC15  250V 5A (1250VA) 
                                  DC1 25V 8A (200W) 

 

CONNECTION DIAGRAM

 

 

L1

L2

L3

N

A1

A2

RL1

RL2

Aux.

1 2

3

4

5 6

7

9

8

10 11 12 13 14

16

15

I

L1

I

L2

I

L3

I

N

 

 

DIMENSIONS

 

 

 

 

96

96

   

MADE IN U.K.

10

100

89.5

96

 

           Front view                                                          Side view 

   

  All dimensions are in mm.

 

 

   

 

 

Содержание P9680

Страница 1: ...or both Overcurrent and Earth fault detection The time current characteristic of the low set units are selectable between Normal Inverse curve 3 10 Normal Inverse curve 1 3 10 Long Time Inverse curve Very Inverse curve Extremely Inverse curve Extremely Inverse 0 65 curve and Definite Time High set units are the Definitive Time type Instantaneous tripping is possible by setting the time to minimum ...

Страница 2: ...occurred continued on next page INSTALLATION BEFORE INSTALLATION ISOLATE THE SUPPLY THIS PRODUCT IS DESIGNED TO CONNECT TO SEVERAL TYPES OF CIRCUITS ENSURE ALL ARE ISOLATED Remove the P9680 P9680 P9680 P9680 from the packaging Lift the raised part of the side clip in order to withdraw from the housing Carry this out on each side Insert the P9680 P9680 P9680 P9680 into the panel cut out and fit the...

Страница 3: ...TTING Default setting for Relay 2 is linked to O C E F and energising at the end of the time out period Resetting mode is Auto Setting of Relay 2 is carried out in a similar manner as Relay 1 however it is necessary to assign the relay to either energise at the start S or end E of the time out period Actual LCD presentation when adjustable parameters are displayed Press and hold the button to set ...

Страница 4: ...further button presses are made If a trip condition occurs whilst in this mode the screen will automatically change to display the information relating to the current status As described in Section 8 use the to gain access to the Last Tripped Information screen The display will show the most recent trip information as follows If more than one trip event is stored use the and buttons to select the ...

Страница 5: ...een cleared The LCD reverts back to displaying the normal system currents and the red Tripp Tripp Tripp Tripped ed ed ed LED stops flashing If either relay is set for Auto resetting then they would have de energised after the fault had cleared The corresponding relay ident i e R1 and or R2 on the display would also disappear Pressing the RESET RESET RESET RESET button will only clear the LCD If ei...

Страница 6: ...0 05 t t t t s s s s 10 1 0 1 0 01 t t t t s s s s Normal Inverse 3 10 Normal Inverse 3 10 Normal Inverse 3 10 Normal Inverse 3 10 NI 3 10 NI 3 10 NI 3 10 NI 3 10 t t t t s s s s k k k k 1 0 0 9 0 8 0 7 0 6 0 5 0 4 0 3 0 2 0 1 0 05 10 1 0 1 1 10 20 I I I I I I I I Long Time Inverse Long Time Inverse Long Time Inverse Long Time Inverse LTI LTI LTI LTI 200 100 10 1 0 1 k k k k 1 0 0 9 0 8 0 7 0 6 0 ...

Страница 7: ...e Un 1 2 85 265VAC 85 370VDC1 18 55VAC 18 72VDC Voltage range should be specified at time of ordering Rated frequency 50 60Hz AC Supplies Isolation Over voltage cat III Rated impulse withstand voltage 1 4kV 1 2 50µS IEC 60664 Power consumption 3W max If connecting a fuse externally a Time Delay type is recommended with a rating of 0 5A or higher Rated current input In 5A directly connected Rated f...

Отзывы: