Broyce Control Ltd., Pool Street, Wolverhampton, West Midlands WV2 4HN. England
Tel: +44 (0) 1902 773746 Fax: +44 (0) 1902 420639 Email: [email protected] Web: www.broycecontrol.com
The information provided in this literature is believed to be accurate (subject to change without prior notice); however, use of such information shall be entirely at the user’s own risk
.
P9680-3-A
7
7
7
7
012376
Electrical life:
≥
150,000 ops at rated load
Dielectric voltage: 2kV AC (rms) IEC 60947-1
Rated impulse
withstand voltage: 4kV (1.2 / 50
µ
S) IEC 60664
Max. DC Load Breaking Capacity Electrical Endurance
Housing: Flame retardant Lexan
Protection: IP55 / IP20 (rear)
Weight:
≈
600g
Mounting: Panel mounting. Cut-out = 91 x 91mm (
±
0.5mm)
Max. panel thickness: 12mm
Terminal type:
UL94-V0 rated pluggable and re-wireable female
connectors comprising:
2-way (Power supply
1, 2
)
6-way (Relay contacts
3….8
)
8-way (Phase current and neutral inputs
9….16
)
Terminal conductor size: 0.05 - 2.5mm
2
(30 - 12AWG)
Recommended tightening
torque: 4.4in lb (0.5Nm)
Wire stripping length: 0.24 – 0.30in (6 – 7.5mm)
Approvals: Conforms to IEC. CE and and RoHS Compliant.
EMC: Immunity: EN/IEC 61000-6-2
Emissions: EN/IEC 61000-6-4
Generic: IEC 60255-26 (EMC), IEC 255-3, IEC
60255-151
( ) Bold digits in brackets refer to terminal numbers on the rear of the unit.
Options:
The P9600 range also includes individual Overcurrent or Earth fault relays
available with either IDMT or DT characteristics. Please refer to separate data
sheets.
•
TECHNICAL SPECIFICATION
Aux. Supply voltage Un (
1, 2
): 85 – 265VAC/85 - 370VDC
1
18 – 55VAC/18 – 72VDC*
(Voltage range should be specified at time of
ordering)
Rated frequency: 50/60Hz (AC Supplies)
Isolation: Over voltage cat. III
Rated impulse
withstand voltage:
1
4kV (1.2 / 50
µ
S) IEC 60664
Power consumption: 3W max.
* If connecting a fuse externally, a Time Delay type is recommended with a rating of 0.5A or
higher.
Rated current input In: 5A (directly connected)
Rated frequency: 50/60Hz
Burden: <0.4VA @ In
Overload: 4 x In (continuous)
External CT’s (
9……16
): Class P recommended. (with 5A secondary)
Maximum CT primary
current rating: 6000A
Overcurrent settings:
Low-set trip (I>): 0.50 – 10.00A (10 – 200%)
Low-set time multiplier (k>): 0.05 – 1.00
Low-set definite time (t>): 0.05 – 100s
High-set trip (I>>): 0.5 – 100A (10 – 2000%) or disable
High-set definite time (t>>): 0.05 – 2.5s
Earth fault settings:
Low-set trip (I
o
>): 0.10 – 5.00A (2 – 100%)
Low-set time multiplier (k
o
>): 0.05 – 1.00
Low-set definite time (t
o
>): 0.05 – 100s
High-set trip (I
o
>>): 0.10 – 50.00A (2 – 1000%) or disable
High-set definite time (t
o
>>): 0.05 – 2.5s
Pick up value: +2% of trip setting
Accuracy:
Protection thresholds:
±
5%
Time delay (DT):
±
5% (with a minimum of 50mS)
Time delay (IDMT):
±
5% (with a minimum of 50mS and I > 1.2 x
set-trip)
Actual phase current:
±
1% of rated current In
Actual Earth fault current:
±
1% of rated current In
Display update time: <1 sec.
Repeat accuracy:
±
0.5% @ constant conditions
Ambient temperature: -10 to +60
°
C
Relative humidity: +95%
Output:
(RL1 -
3, 4, 5
): 1 x SPDT relay
(RL2 -
6, 7, 8
): 1 x SPDT relay
Output rating: AC1 250V 8A (2000VA)
AC15 250V 5A (1250VA)
DC1 25V 8A (200W)
•
CONNECTION DIAGRAM
L1
L2
L3
N
A1
A2
RL1
RL2
Aux.
1 2
3
4
5 6
7
9
8
10 11 12 13 14
16
15
I
L1
I
L2
I
L3
I
N
•
DIMENSIONS
96
96
MADE IN U.K.
10
100
89.5
96
Front view Side view
All dimensions are in mm.