PROGRAMMING 

 
Programming/setting of the 

P9680

P9680

P9680

P9680

 is carried out using the 3 buttons located 

behind the transparent cover.  

 

 

 

The 

 button selects the required parameter to be changed. The 

 

 

buttons either increment or decrement a value accordingly.  

Any adjustments made are stored by the pressing and holding of the 

 button 

until the LCD shows the word “Saved!

Saved!

Saved!

Saved!” See Section 7. SAVING OF SETTINGS. 

 

Please read the 

“Notes during programming”

 before commencing with the 

following.

 

 

1A. TOROID RATIO  

Setting the Toroid Ratio will allow the “actual” Phase currents (IL1, IL2, IL3) and 

Neutral current (Io) displayed on the LCD to represent that of the currents flowing 
through the external CT’s. If no CT’s are used, the parameter should be set to 5/5 
(i.e. 1:1). The setting applies to all CT’s. 

Default setting is “5/5” 

 

 

Press and hold the 

 button. The LCD displays a screen showing the 

characters “User Settings

User Settings

User Settings

User Settings” then the following screen appears…

 

 
 
 
 
 

 

 

Press either 

 or 

to set the primary value of the external CT’s. 

 

 

The digit after the forward slash “/” cannot be changed. 

 

1B. NETWORK FREQUENCY 

Default setting is “50Hz” 

 

 

Whilst in the same screen as that for the Toroid Ratio (see 1A.), press  

 

the 

 button to display the options for NETWORK FREQUENCY

NETWORK FREQUENCY

NETWORK FREQUENCY

NETWORK FREQUENCY. 

 
 
 
 
 

 

 

Press either 

 or 

to select between 50Hz or 60Hz. This should be 

set to suit the frequency of the network being monitored. 

 

Press and hold the 

 button to set the options for “Relay 1” 

“Relay 1” 

“Relay 1” 

“Relay 1” as described 

in the next section. 

 
2. RELAY 1 SETTING 

Default setting for Relay 1 is linked to “O/C & E/F”. Resetting mode is Manual. 

 

 

The LCD displays the following screen. The options under 

“1:”

 are displayed 

and the default setting highlighted.

 

 
 
 
 
 

 
 

 

Press either 

 or 

to select how Relay 1 is assigned to tripping.

 

 

Press the 

 button and the options under “2:

2:

2:

2:” for resetting are displayed 

and the default setting highlighted.

 

 
 
 
 
 

 

Actual LCD presentation when adjustable parameters are displayed. 

 
 
 

 

Press either 

 or 

to select between AUTO

AUTO

AUTO

AUTO resetting or MAN

MAN

MAN

MANUAL 

resetting (after a fault has occurred).

 

 

                             

continued on next page… 

 

INSTALLATION 

 
 
 
 
 

 

BEFORE INSTALLATION, ISOLATE THE SUPPLY. THIS PRODUCT IS 
DESIGNED TO CONNECT TO SEVERAL TYPES OF CIRCUITS. 
ENSURE ALL ARE ISOLATED^

 

 

Remove the

    P9680 

P9680 

P9680 

P9680 

from the packaging. 

 

Lift the raised part of the side clip in order to withdraw from the housing. 
Carry this out on each side.  

 

Insert the 

P9680

P9680

P9680

P9680

 into the panel cut-out and fit the side clips back on to the 

housing.

 

 

Slide the clips towards the front of the unit until they come in to contact with 
the reverse of the panel. The unit is now secured in place.

 

 

Wire the supplied female pluggable connectors as required.

 

 

Plug the connectors into the relevant sockets on the rear of the unit.

 

 

The 

P9680

P9680

P9680

P9680

 is now ready for powering and programming. 

 

 

The front window of the P9680 is supplied with a clear protective film which can be 

removed as and when necessary. 

 

 

^ When carrying out future maintenance on the product or application and it 
becomes necessary to disconnect the connectors from the product, ensure for 
the Current Transformer connector, they do not remain open circuit

they do not remain open circuit

they do not remain open circuit

they do not remain open circuit. This can 

lead to high voltages being present on this connector. 

 

 

NORMAL OPERATION 

 

 

Apply power to the unit and the green 

“Power supply”

 LED will illuminate. 

 

 

The LCD will momentarily display a welcome screen as shown…

 

 
 
 
 
 

 
 
 
 
 

 

….then after a short delay reverts to indicating the following information:

 

 
 
 
 
 
 

 

 

TEST MODE 

 
 

 

Press and hold the

 

 button and both relays will energise. The LCD will 

display the characters 

“TEST”

 and the product part number (as below). The 

LCD backlight and red 

“Trip”

 LED will flash.

 

 
 
 
 
 

 
 
 

 

Release the 

 button and the relay(s) will remain energised if set to Manual 

reset or de-energise if set to Auto reset.

 

 
 
 
 

 

Press the 

 to de-energise relay(s) which are set to Manual reset. The 

LCD will revert back to Normal operation. The LCD backlight and red 

“Trip

” LED will stop flashing. 

 

Testing should be carried out on a regular basis to check the integrity of the 

P9680. 
 

DO NOT use this product to provide a means of isolating circuits in 
order to work on when placed in the “TEST”

“TEST”

“TEST”

“TEST” mode. This should only be 

done by means of operating isolators, circuit breakers or other 
methods of removing power in this application. 

 

 

 

I

L1

 

 

0.00

A

 

I

L2

 

 

0.00

A

 

I

L3

 

 

0.00

A    

 

I

O

 

  

0.00

A    

 

Installation work must be carried

out by qualified personnel.

 

Actual phase 
currents 

Actual Earth 
fault current 

 
 
 

TEST

 

TYPE: P9680 

Ver: X.X

 

TOROID RATIO 
 

5 / 5 

 

RELAY 

1

 CONFIGURATION 

 
  1:            
  O/C           
  E/F           
 

O/C & E/F 

 

Digits which 
can be adjusted 

TYPE: P9680

 

Ver: X.X 

 

Model No. 

 
 

Version 

 

TOROID RATIO 
 

5 / 5 

 

NETWORK FREQUENCY 

 

50Hz 

60Hz 

 

RELAY 

1

 CONFIGURATION 

 
  1:           2: 
  O/C          AUTO 
  E/F         

MAN

 

 

O/C & E/F 

 

Содержание P9680

Страница 1: ...or both Overcurrent and Earth fault detection The time current characteristic of the low set units are selectable between Normal Inverse curve 3 10 Normal Inverse curve 1 3 10 Long Time Inverse curve Very Inverse curve Extremely Inverse curve Extremely Inverse 0 65 curve and Definite Time High set units are the Definitive Time type Instantaneous tripping is possible by setting the time to minimum ...

Страница 2: ...occurred continued on next page INSTALLATION BEFORE INSTALLATION ISOLATE THE SUPPLY THIS PRODUCT IS DESIGNED TO CONNECT TO SEVERAL TYPES OF CIRCUITS ENSURE ALL ARE ISOLATED Remove the P9680 P9680 P9680 P9680 from the packaging Lift the raised part of the side clip in order to withdraw from the housing Carry this out on each side Insert the P9680 P9680 P9680 P9680 into the panel cut out and fit the...

Страница 3: ...TTING Default setting for Relay 2 is linked to O C E F and energising at the end of the time out period Resetting mode is Auto Setting of Relay 2 is carried out in a similar manner as Relay 1 however it is necessary to assign the relay to either energise at the start S or end E of the time out period Actual LCD presentation when adjustable parameters are displayed Press and hold the button to set ...

Страница 4: ...further button presses are made If a trip condition occurs whilst in this mode the screen will automatically change to display the information relating to the current status As described in Section 8 use the to gain access to the Last Tripped Information screen The display will show the most recent trip information as follows If more than one trip event is stored use the and buttons to select the ...

Страница 5: ...een cleared The LCD reverts back to displaying the normal system currents and the red Tripp Tripp Tripp Tripped ed ed ed LED stops flashing If either relay is set for Auto resetting then they would have de energised after the fault had cleared The corresponding relay ident i e R1 and or R2 on the display would also disappear Pressing the RESET RESET RESET RESET button will only clear the LCD If ei...

Страница 6: ...0 05 t t t t s s s s 10 1 0 1 0 01 t t t t s s s s Normal Inverse 3 10 Normal Inverse 3 10 Normal Inverse 3 10 Normal Inverse 3 10 NI 3 10 NI 3 10 NI 3 10 NI 3 10 t t t t s s s s k k k k 1 0 0 9 0 8 0 7 0 6 0 5 0 4 0 3 0 2 0 1 0 05 10 1 0 1 1 10 20 I I I I I I I I Long Time Inverse Long Time Inverse Long Time Inverse Long Time Inverse LTI LTI LTI LTI 200 100 10 1 0 1 k k k k 1 0 0 9 0 8 0 7 0 6 0 ...

Страница 7: ...e Un 1 2 85 265VAC 85 370VDC1 18 55VAC 18 72VDC Voltage range should be specified at time of ordering Rated frequency 50 60Hz AC Supplies Isolation Over voltage cat III Rated impulse withstand voltage 1 4kV 1 2 50µS IEC 60664 Power consumption 3W max If connecting a fuse externally a Time Delay type is recommended with a rating of 0 5A or higher Rated current input In 5A directly connected Rated f...

Отзывы: