Appendix. Configuration Downlink Command
Port
204
Payload Length
3 bytes
Appx. 1 Payload
Bytes
0
1
2
Field
Cmd
Config
Cmd
Command
1 byte
Bit [3:0]
0x00 –
Set
keep alive interval.
default : 3600 sec. (min: 15 sec)
0x01 –
Set
sensor detection interval.
(Must be lesser than “keep-alive interval”)
default : 60 sec. (min: 15 sec)
0x02 – Temperature trigger value.
default : 2
°C
.
0x03 – Humidity trigger value.
default : 5 %RH.
Config
Configuration
1 or 2 bytes
See the table as follows:
Command
Command Description
Data Length
0x00(1byte)
Set
kee- alive interval.
*Note: little-endian format.
2 bytes
0x01(1byte)
Set the
sensor detection interval.
*Note: little-endian format.
*Note: fewer than “keep-alive time”.
2 bytes
0x02(1byte)
Set temperature trigger value.
1 byte
0x03(1byte)
Set humidity trigger value.
1 byte
Payload
Content
Command content
Ex:
00100E ||
013C00
||
0202
||
0305
00
100E
=> Keep alive interval : 0x0E10 -> 3600 (sec)
01 3C00
=>
Monitor time
interval : 0x003C -> 60 (sec)
02
02
=>
Temperature trigger value
: 0x02 -> 2 (
°C
)
03
05
=>
Humidity trigger value :
0x05 -> 5 (%RH)
© 2019 Browan Communications Inc. All rights reserved.
12