Appendix. Configuration Downlink Command
Port
204
Payload Length
1~9 bytes
*Note: Only for unconfirmed downlink.
Appx. 1 Payload
Bytes
0
0~2
Field
Cmd
Config
Appx. 2 Command Description
Cmd
Command Description
Config Length
0x00
Get sensor configuration.
0 byte
0x00
Set keep-alive interval, in seconds.
Range: 15~65535 seconds.
Default: 3600 seconds.
*Note: little-endian format.
2 bytes
0x01
Set the sensor’s monitor interval, in seconds.
Range: 15~65535 seconds.
Default: 300 seconds.
*Note: little-endian format.
2 bytes
0x02
Set delta value to trigger uplink, in lux.
Range: 0~65535 lux.
Default: 100 lux.
*Note: little-endian format.
2 bytes
Example:
00100E
012C01
026400
00 100E
→
Keep-alive interval: 0x0E10
→
3600 sec
01 2C01
→
Monitor interval: 0x012C
→
300 sec
02 6400
→
Trigger delta value: 0x0064
→
100 lux