background image

6. Label format information 

6.1 Round label 

 

 

6.1.1 All QR code  

URN:LWDP:58A0CB0000210000:58A0CBFFFFFEFFFF:TBMS100915:4D4483B1. 

  

The total maximum resulting character sentence is 72 alphanumeric characters long. 

 

6.1.2 JoinEUI  

900MHz: 58A0CB0000210000. (US/AU/AS923/BR) 
800MHz: 58A0CB0001500000. (EU/IN/RU) 

Uses a hexadecimal representation resulting in 16 characters. 

 

6.1.3 DevEUI 

58A0CBFFFFFEFFFF. 

 

Uses a hexadecimal representation resulting in 16 characters 

 

6.1.4 Model number 

 

 

Non-reserved characters(except ":" and space) with a maximum length of 20 
characters. 
 

 

© 2019 Browan Communications Inc. All rights reserved.

 

 

Содержание TABS TBMS100-868

Страница 1: ...Motion Sensor Reference Manual TBMS100 915 TBMS100 868 ...

Страница 2: ...PE Bag Back Label Label Barcode 9 7 Important Product Safety Instructions 10 8 Warnings 11 9 Notices 12 10 Cautions 12 11 Regulatory 13 Appendix Configuration Downlink Command 14 Appx 1 Payload 14 Appx 2 Configuration Command 15 Appx 2 1 Payload 15 Appx 2 2 Command Description 16 Appx 3 Response Content 16 1 Description The Motion Sensor utilizes LoRaWAN connectivity to communicate the presence or...

Страница 3: ... 3 Radio Frequency 863 870MHz for EU 902 928MHz for North America Tx Power US 19dBm EU 17dBm Rx Sensitivity 135dBm Antenna Gain 2dBi Peak 5dBi Avg 2 4 Certifications and Conformity FCC ID 2AMUGTBSP100 IC 22980 TBSP100 CE ROHS REACH 2 5 Power Source 3 6V 1 2 AA Li SOCl2 1200mAh battery Maximum Voltage 3 6V Minimum Voltage 3 1V Current 135mA maximum 100uA minimum 2 6 User Interface LEDs One blue LED...

Страница 4: ...ration While in default operation the device will immediately send a status change message once there is a transition from vacant to occupied state or vice versa Additionally the device will send a status message every 10 minutes while in the occupied state and every 1 hour while in the vacant state 2019 Browan Communications Inc All rights reserved 3 ...

Страница 5: ...send a message immediately 3 While the occupied state continues send a message every 10 minutes 4 When the device didn t trigger by the occupied state again within 5 minutes from the last message status changes from occupied to free mode and send a message 4 1 2 Payload Port 102 Payload Length 8 bytes Bytes 0 1 2 3 4 5 6 7 Field Status Battery Temp Time Count 2019 Browan Communications Inc All rig...

Страница 6: ...as measured by on board NTC Bits 6 0 Bit 7 unsigned value τ range 0 127 temperature in C τ 32 RFU measurement range 32 to 95 C Time Time elapsed since the last event triggered Bits 15 0 unsigned value in minutes range 0 65 535 Note little endian format Count Total count of event triggered Bits 23 0 unsigned value range 0 16 777 215 Note little endian format Note This value is not stored persistent...

Страница 7: ...ry or battery pack subjected to extremely low air pressure may also result in an EXPLOSION or leakage of flammable liquid or gas Discard used batteries according to the manufacturer s instructions CAUTION The unit is provided with a battery powered circuit There is a danger of explosion if the battery is incorrectly replaced Replace only with the same or equivalent type recommended by the manufact...

Страница 8: ...ers long 6 1 2 JoinEUI 900MHz 58A0CB0000210000 US AU AS923 BR 800MHz 58A0CB0001500000 EU IN RU Uses a hexadecimal representation resulting in 16 characters 6 1 3 DevEUI 58A0CBFFFFFEFFFF Uses a hexadecimal representation resulting in 16 characters 6 1 4 Model number Non reserved characters except and space with a maximum length of 20 characters 2019 Browan Communications Inc All rights reserved 7 ...

Страница 9: ... Label Barcode PE Bag Label Back Label Definition of Back Label and PE Bag Barcode Label GS1 DataMatrix The GS1 Application Identifier 21 indicates that the GS1 Application Identifier data field contains a serial number The GS1 Application Identifier 92 assigned to the company s internal information is DevEUI 2019 Browan Communications Inc All rights reserved 8 ...

Страница 10: ...ld Do not allow children or pets to play with products Observe proper precautions when handling batteries Batteries may leak or explode if improperly handled Observe the following precautions to avoid a sensor explosion or fire Do not drop disassemble open crush bend deform puncture shred microwave incinerate or paint the sensors Hub or other hardware Do not insert foreign objects into any opening...

Страница 11: ...ry leaking do not allow the liquid to come in contact with the skin or eyes If contact has been made wash the affected area with copious amounts of water and seek medical advice Do not use any charger other than that specifically provided for use with the equipment Observe the plus and minus marks on the battery and equipment and ensure correct use Do not use any which is not designed for use with...

Страница 12: ...oducts Do not use detergent or abrasive materials to clean the Tabs products as this may damage the sensors 10 Cautions CAUTION Disposal of a battery or battery pack into a fire or a hot oven or mechanically crushing or cutting of a battery or battery pack can result in an EXPLOSION Leaving a battery or battery pack in an extremely high temperature surrounding environment that can result in an EXP...

Страница 13: ...n For the full FCC IC Compliance Statements and EU declaration of conformity visit www browan com Contact This symbol means that according to local laws and regulations your product should be disposed of separately from household waste When this product reaches its end of life take it to a collection point designated by local authorities Some collection points accept products for free The separate...

Страница 14: ...Config PIR Sensor Configuration Bits 4 0 Bit 5 Bits 8 6 Bits 10 9 Bits 12 11 Bits 16 13 Bits 24 17 Bits 31 25 RFU 0 use band pass filter 1 use low pass filter Default 0 use BPF RFU unsigned value ω range 0 3 window time in sec ω 1 4 Default 0 4 sec unsigned value ρ range 0 3 pulse counter threshold ρ 1 Default 0 1 pulse unsigned value β range 0 15 blind time in sec β 1 0 5 Default 15 8 sec detecti...

Страница 15: ...default value 0 value range 0 65535 0x05 Set PIR parameters default value please see 4 2 1 Config Configuration 0 4 bytes See the table as follows Cmd Command Description Config Length 0x00 Get Sensor Configuration Only for unconfirmed downlink 0 bytes 0x00 reporting interval in sec Note little endian format Must be lesser than keep alive time 2 bytes 0x02 Occupied interval in sec Note little endi...

Страница 16: ...ied status 05 00148101 PIR parameter 0x01811400 Example Desk Occupied 0500148101 Room Occupied 0500e02100 Appx 3 Response Content Only for unconfirmed downlink Port 204 Payload Length 16 bytes Payload Content Response content Ex 00100e 025802 0305 040000 0500148101 00 100e reporting interval 0x0e10 3600 sec 02 5802 Occupied override 0x0258 600 sec 03 05 Free detection time 0x05 5 min 04 0000 Trigg...

Отзывы: