 Chimney Requirements

 

 
This appliance must not be fitted into a chimney serving another heating appliance. It is 
most important that there is no obstruction in the flue or chimney. Please ensure that 
any existing chimney is clear of obstruction and swept clean immediately before 
installation of the new stove. If the chimney has been used for an open fire it is 
recommended that it be swept for a second time having been used for a month 
following installation. 

 

 

A flue draught minimum of 12 Pascals to a maximum 18 Pascals is required for 
satisfactory appliance performance. A properly built masonry or factory constructed 
chimney (with a minimum vertical height of 5 metres) should ensure a consistent 
draught (draw). 45° bends can be used in the flue run (maximum of four bends) you will 
need to add an extra 1 metre of vertical flue height for each bend. 

 

 

The flue draught should be checked under fire at high output and if it exceeds the 
recommended maximum, a draught stabiliser must be fitted so that the rate of burning 
can be controlled, and to prevent over firing (See section “Warning Notes”). If you have 
any doubts about the suitability of your chimney, consult your local dealer/stockist or 
engineer. If your flue draft is below the minimum recommendation then it may be 
necessary to increase the vertical chimney height, add additional flue insulation or 
possibly add a special cowl to the top of the chimney (e.g. anti down draft cowl to 
eliminate wind induced down draft). 

 

 

The outlet from the chimney should be above the roof of the building in accordance with 
the provisions of Building Regulations Approved Document J.

 

 

If installation is into an existing chimney then it must be sound and have no cracks or 
other faults which might allow fumes into the house. Older properties, especially, may 
have chimney faults or the cross section may be too large i.e. more than 230 mm x 230 
mm. Remedial action should be taken, if required, seeking expert advice, if necessary. If 
it is found necessary to line the chimney then a flue liner suitable for solid fuel must be 
used in accordance with Building Regulations Approved Document J.

 

 

If there is no existing chimney then either a prefabricated block chimney in accordance 
with Building Regulations Approved Document J or a twin walled insulated stainless 
steel flue to BS 4543 can be used. These chimneys must be fitted in accordance with 
the manufacturer’s instructions and Building Regulations.

 

 

If a flexible liner is required the liner diameter must not be less than 6” / 150mm.

 

 

Any bend in the chimney or connecting fluepipe should not exceed 45°. 90° bends are 
not permitted. . For top flue installations it is possible to sweep through the appliance by 
removing the internal baffle however it is recommended that you provide adequate 
access (e.g. easily accessible soot door). For rear flue connection we recommend the 
use of a tee section, the bottom of the tee should be capped to catch soot and debris.

 

 
 

Содержание Hereford 5

Страница 1: ...stallation Operating Instructions Covering Models Ignite 5 6 7 Desire 5 6 7 Q5 Q6 Q7 Standard Log Store Multifuel Stoves Tested to EN 13240 These appliances must be installed and commissioned by a HET...

Страница 2: ...tion Controls Layout 14 Controls Explained 15 Air wash System 15 Ash Pan 15 Recommended Fuels 16 Lighting the Stove Kindling Stage 17 Burning Wood Burning Coal 18 Warning Notes 19 Maintenance Door Adj...

Страница 3: ...elaws and other specifications or regulations as they affect the installation of the stove It should be noted that the Building Regulations requirements may be met by adopting the relevant recommendat...

Страница 4: ...e taken to avoid the possibility of personal injury CO Alarms Building regulations require that whenever a new or replacement fixed solid fuel or wood biomass appliance is installed in a dwelling an a...

Страница 5: ...1 81 1 83 4 Weight Kg Ignite 5 71 Ignite 5 LS 85 Desire 5 68 Desire 5 LS 82 Ignite 6 78 Ignite 6 LS 93 Desire 6 74 Desire 6 LS 90 Ignite 7 84 Ignite 7 LS 101 Desire 7 80 Desire 7 LS 97 Flue Diameter m...

Страница 6: ...Mar 14 GB Issue 3 6 Dimensions Ignite 5 Desire 5 Q5 Ignite 5 Desire 5 Log Store Q5 Log Store...

Страница 7: ...Mar 14 GB Issue 3 7 Dimensions Ignite 6 Desire 6 Q6 Ignite 6 Desire 6 Log Store Q6 Log Store...

Страница 8: ...Mar 14 GB Issue 3 8 Dimensions Ignite 7 Desire 7 Q7 Ignite 7 Desire 7 Log Store Q7 Log Store...

Страница 9: ...the stove for fuel to fall out a fender must be fitted if the hearth is flush with the carpet Clearances The stove requires the following clearances around it to ensure the heat is released into the...

Страница 10: ...ibly add a special cowl to the top of the chimney e g anti down draft cowl to eliminate wind induced down draft The outlet from the chimney should be above the roof of the building in accordance with...

Страница 11: ...g regulations approved document J for further information There must not be an extractor fan fitted in the same room as the stove as this can cause the stove to emit fumes into the room It is necessar...

Страница 12: ...to 1 To refit the internals follow the numbered sequence from 1 7 The firebricks should be fitted with the fibre paper on the LHS RHS and rear components the fibre paper should be sandwiched between...

Страница 13: ...ly It is possible to remove the stove from the store Log store versions this may be necessary for transport purposes The diagram below shows the locations of the fixings 4x bolts labelled 1 which hold...

Страница 14: ...ove is fitted with two air controls which need to be correctly operated in order to light and maintain a fire Both controls are situated below the ash lip of the stove as indicated on the diagram belo...

Страница 15: ...ake is adjustable throughout the area of travel in to out to control the total amount of air required for suitable combustion The Secondary air intake is used at initial start up and to control the bu...

Страница 16: ...smoke control areas Do NOT burn House coal or any other coal which are intended for use on open fires Suitable coal needs to be designed for use on closed appliances Open fires send a large amount of...

Страница 17: ...using the newspaper then add a generous amount of dry kindling in a criss cross pattern as shown below Stage 2 Ignite the paper underneath using a match or suitable fire lighter Allow the paper and ki...

Страница 18: ...ntrolled once again by the secondary control If you no longer want to keep the fire going simply allow it burn out Burning Coal With kindling complete you are now ready to add your approved coal Stage...

Страница 19: ...a flue pipe thermometer so that you can monitor how much heat you are sending up the chimney this will both enable efficient operation of your stove and also give a good indication if you are over fi...

Страница 20: ...n seal anticlockwise to loosen seal on both the top and bottom hinge this ensures that the door seal will compress or loosen evenly Re fit the door back onto the hinges and tighten the locking nut ins...

Страница 21: ...lint free cloth is normally sufficient however for stubborn build ups we would recommend using a very fine wire wool Chimney Sweeping It is essential that your chimney flue is swept at least once a y...

Страница 22: ...ce with regard to installing a Flue Draught Stabiliser The stove has been recessed into the existing fireplace and a lot of heat is being absorbed by the surrounding fireplace walls rather than being...

Страница 23: ...____________ Address _______________________________________________________________ Telephone Inc area code _________________________________________________ HETAS Registration Number _______________...

Страница 24: ...LHS and RHS baffle plate set 3 Rear Baffle 4 Top Baffle 5 Cast Grate 6 Cast grate front 7 Ash pan 8 Latch 9 Air box 10 Coal Slider 11 Wood Slider 12 Door Handle 13 Steel Door 14 Glass 15 Steel door G...

Страница 25: ...mpletion date SERVICE ENGINEER REG No COMPANY NAME COMPANY ADDRESS POSTCODE CONTACT NUMBER 4TH YEAR SERVICE completion date SERVICE ENGINEER REG No COMPANY NAME COMPANY ADDRESS POSTCODE CONTACT NUMBER...

Страница 26: ...its Replaced parts or components will become the property of Broseley Fires Should you wish to claim under the warranty please contact the supplier dealer from whom you purchased the appliance Do not...

Отзывы: