Activating the Sign - 

Sign

Which sign (+, -, or + -) is to be represented can be set.  If for example the plus sign (+) is
disabled, plus sign is not displayed with positive values, however the minus sign (-) is still
displayed with negative values.

Setting the Transmission Rate - 

bAUd

The transmission rate for the serial port can be set to 300, 600, 1200, 2400, 4800, 9600,
19200, or 57600 bits per second (baud).

Note: The delivery state for the transmission rate is 9600 baud.

Setting the Transmission Protocol - 

ProT

The most used transmission protocols with 7 or 8 data bits and none (

n

), even (

E

) and odd

(

0

) parity and 1 or 2 stop bits for the serial interface can be set.

Representation Example:  

7.E.1

Note: The delivery state is 

7

 data bits, even parity (

E

) and 

1

 stop bit.

Setting the Communication Address - 

Adr.

The address for the serial interface at which the instrument is to be addressed can be set.
The address 0 disables the addressing of the serial interface, or when a fieldbus is itegrated
only broadcast messages are processed.

Note: The delivery state for the address is 0.  

Note: Changes to settings for 

bAUd

Prot

, or 

Adr

 come into effect only after reset is

carried out and have no effect on the BCD bus or if there is no serial interface.  
A reset is triggered by interrupting the supply voltage until the display is dark and con-
necting the supply voltage or switching on again.

Setting Brightness of Display - 

HeL.

The brightness of display can bet changed in the range from 0 = verry light to 5 = verry
dark.

Note: The delivery state for the brightness is 2.

Manual PM984

10

State July 2002 - All subject to change without notice

Содержание PM 984

Страница 1: ...Instruction manual PM 984 for version P0 90 bis P0 99 Manual PM984 State July 2002 All subject to change without notice 1...

Страница 2: ......

Страница 3: ...ng of Display SCAL 8 Setting the Zero Point Assignment null 8 Setting the Full Scale Assignment FS 8 Assigning the Zero Value of Analog Output A nul 8 Assigning the End Value of Analog Output A FS 8 L...

Страница 4: ...ing 14 Wiring Principle 14 RS 485 Interface with Measurement Bus Protocol 14 Description of Commands for Interfaces 15 General 15 Number Representation 15 Priorities 15 Reading Setting the Operating M...

Страница 5: ...Examples Transmission Display 1 2345 1 2345 1 AB CD 1 Ab CD 123 45 123 45 123 123 1 8 8 8 8 Test 123 45 Err 2 Error the sign cannot be represented Measured Value Processing Mode In this mode the inst...

Страница 6: ...regulations of the national standards for electrical engineering Scope of Delivery The scope of delivery includes Data sheet PM 984 Slave displaying instrument PM 984 Screw clips clamping devices loc...

Страница 7: ...the instrument with the screws to the switch panel Screwdriver can be used to tighten screw clips Note Screw clamp assignment for the connections e g power supply is obtained from the data sheet Atten...

Страница 8: ...ividual menu items 6 The display flashes and can be changed by turning 7 Numeric settings such as limit values are carried out dynamically i e the quicker the turn ing the larger the numeric steps 8 T...

Страница 9: ...ed mode with code 98 Normal mode with code 1234 Service mode with code 12049 Note Only the menus and are active CODE SAVE Service Mode Protected Mode Press the turn press switch with screwdriver Turn...

Страница 10: ...set Only positive values are possible For a failure free limit monitoring the value shall never be greater than the measuring range or half of the toler ance range see Setting the Relay Function rEL 1...

Страница 11: ...ge value is displayed Decimal Point Switching dP When the function dP is activated edge triggering the decimal point switches to the second decimal point level making it possible to change the decimal...

Страница 12: ...data bits even parity E and 1 stop bit Setting the Communication Address Adr The address for the serial interface at which the instrument is to be addressed can be set The address 0 disables the addre...

Страница 13: ...it value can be set The relay returns to rest position only after the mea sured value has risen above the low limit value and the amount of the hysteresis Maintaining the Tolerance Range Go1 Go2 As lo...

Страница 14: ...tput setting remains unchanged therefore should be adjusted first Leaving the Sublevel of SYS Menu EndE Execute EndE to leave the sublevel for settings and to return to menu SYS starting posi tion Det...

Страница 15: ...trol lines CTS with RTS and DTR with DSR as shown in Fig 2 Attention On the unit side CTS and RTS shall not be bridged as RTS reflects the current interface status and is not static Normal Operation...

Страница 16: ...ed to the reception line of the next instrument as shown in Fig 3 All received characters are de livered delayed by one character from every unit This way all characters of the computer go through the...

Страница 17: ...rs Therefore the response to several read commands in one command line are several answers When several write set commands are in one com mand line only the acknowledgement for the command line is out...

Страница 18: ...nstrument operates in hexadecimal display mode see chapter Brief De scription Only limited interface commands are available Mode 1 In this mode the instrument operates in numerical measured value proc...

Страница 19: ...measured value max over 3 3 million values The values are replied in ASCII format with sign followed by decimal point In addition the possibility to set and reset the values is given in order to rest...

Страница 20: ...and relay ON 1 Note Make sure that the response of the relay is carried out just as with the limit moni toring If the relays are to respond exclusively via the interface then the corresponding relay...

Страница 21: ...points zero value and limit value are assigned to the display values The display value is given as digit without decimal point the decimal posi tions are given separately Example Scaling to 0 mA 0 A...

Страница 22: ...lue must be stepped under or stepped over before the relay returns to rest position All values are given in their basic scaling without decimal point Example Limit value pair 2 should give alarm at a...

Страница 23: ...relay always active when instrument is on 2 activates when limit value 1 is reached 3 activates when limit value 2 is reached 4 activates when limit value 1 is stepped under 5 activates when limit va...

Страница 24: ...and This command serves the identification of instrument the version of instrument and soft ware is returned Example Read instrument version Computer Instrument PM984H V1 10 Manual PM984 22 State July...

Страница 25: ...a check sum therefore it can only be transmitted in unchanged form Note The first partial blocks have to be marked as block at transmission i e they are to end with end of block 17h and not with end...

Страница 26: ...he latest valid legal regulations for hazardous waste when disposing of the instru ment Technical Data Technical data is obtained from data sheet Guarantee Defects that occur within one year as of del...

Отзывы: