Instruction Manual 

FAC20  

Rev 0 

 

 

 

   

 

 

Introduction 

Read and retain carefully for as long as the product is being used. It contains vital information 
on the operation and installation of your controller FAC20. The leaflet should be regarded as 
part of the product. 

If you are just installing the unit, the manual MUST be given to the homeowner and to any 
subsequent user. 

1.1 

Features 

 

Remote test, locate and silence hardwired interconnected smoke/heat/CO Alarms 

 

Microprocessor based unit. 

 

Requires only 3 wires: Active, Neutral and interconnect utilising the standard easi-fit 
base supplied with the mains power Alarms. 

 

Flush or surface mount. 

 

Supervised opto-isolated input, triggered by voltage free contact to externally drive 
the sounders of the interconnected Alarms. 

 

Connected in a centralised location to any Alarm in the system, not required to be 
installed as the first device in the interconnected circuit. 

 

Fully concealed printed circuit board, only plug-in terminals are accessible.  

 

Conforms to AS/NZS 62368.1:2018.  

1.2 

Product Description 

Smoke Alarms are designed to detect smoke particles in the air and may cause false alarms. 
However,  other  airborne  particles,  i.e.  steam,  cooking  fumes,  dust,  etc.  can  also  cause 
smoke Alarms to generate false alarms. With interconnected smoke/heat/CO Alarms, when 
one Alarm senses smoke / heat  /CO, all Alarms will sound. The FAC20 is a three button 
Alarm  Controller  intended  to  provide  the  occupant  with  a  full  control  over  a  hardwired 
interconnected Alarm system.  

Alarm Controller buttons functions: 

 

Locate

: silences all Alarms in a hardwired interconnected system except the Alarm 

sensing smoke, heat or CO.   

 

Silence

:  when  the  source  of  the  active  Alarm  is  located, 

pressing  the  “Silence” 

button will silence active Alarm(s) in the system for 10 minutes same as the HUSH 
feature  in  the  Smoke  Alarm.  New  alarm  from  non-active  Alarms  will  activate  all 
Alarms including the one in silence mode. 

 

Test

: provides an easy method to test all hardwired interconnected Alarms.   

The  FAC20  also  provides  an  isolated  supervised  input  to  trigger  the  sounders  in  all 
interconnected Alarms from an external N/O contact e.g. sprinkler flow switch input, panic 
input, etc. The input circuit supervises for open circuit fault condition whilst short circuit will 
behave as a triggered condition and activate all the interconnected Alarms. 

The FAC20 is not a battery backed device. It is not functional without mains voltage supply. 

Up to 2 x FAC20 can be connected in the same interconnected Alarm circuit, provided all the 
Alarms are of EIB3000 series. For EIB140RC series and EIB160e series, only one controller 
can be used for each interconnected circuit. 

 

 

Содержание FAC20

Страница 1: ...Instruction Manual FAC20 Rev 0 FIRE ALARM CONTROLLER FAC20 MA455 Mar 2022...

Страница 2: ...This page has deliberately been left blank...

Страница 3: ...Locate the source Alarm s 9 3 3 Silence the source Alarms s 10 3 4 Fault Indications 11 4 GUARANTEE 12 5 REVISION HISTORY 13 Table of figures Figure 1 Fire Alarm Controller front and rear view 3 Figur...

Страница 4: ...o generate false alarms With interconnected smoke heat CO Alarms when one Alarm senses smoke heat CO all Alarms will sound The FAC20 is a three button Alarm Controller intended to provide the occupant...

Страница 5: ...44RC EIB141RC EIB160e Series EIB166e EIB161e 1 5 Specifications On Board Power Supply 230V AC 50Hz 20mA Operating Temperature 10 to 40 degree C Dimensions 117 5H x 75W x 30D mm see Figure 2 Interconne...

Страница 6: ...Instruction Manual FAC20 Rev 0 4 The rear and side view of the controller are shown in Figure 2 below Figure 2 Dimensions of FAC20...

Страница 7: ...controller to any non compatible Alarms apart from those listed above or to any other device produced by another manufacturer Doing so may risk damage and malfunction to the interconnected devices and...

Страница 8: ...nnect FAC20 to the next Alarm in the circuit 5 If the external clean contact is required to activate the sounders of the Alarms e g sprinkler system N O contact Panic input etc connect the N O contact...

Страница 9: ...th Do not use an Earth wire for the Interconnect line The interconnect wire must be treated as a mains powered conductor It should be suitably rated and double insulated Earthing of the FAC20 controll...

Страница 10: ...as shown in Figure 5 below and all Alarms will sound 2 Press and hold TEST button for approximately 3 seconds to terminate the test the TEST LED will extinguish and all the Alarms in the system will s...

Страница 11: ...FAC20 if additional FAC20 is used in the circuit Figure 7 Second FAC20 indication 3 2 Locate the source Alarm s When one Alarm activates all the Alarms in the system will sound and the LOCATE LED will...

Страница 12: ...SILENCE button as shown in Figure 9 below after a delay the Alarm s will stop sounding The SILENCE LED will turn on RED for 10 minutes to indicate the source Alarm s will be silenced for 10 minutes Th...

Страница 13: ...n open circuit fault is detected on the External Trigger Input wiring to the FAC20 Contact a licensed electrician to check the wiring Note The monitoring resistor is 4 7K ohm Figure 10 Wiring fault of...

Страница 14: ...careless handling or where repairs have been made or attempted by others No other guarantees written or verbal are authorised to be made on behalf of Brooks All other conditions and warranties whether...

Страница 15: ...Instruction Manual FAC20 Rev 0 13 5 Revision history Issue Date Description Written By Checked By 0 28 7 21 Initial revision BC AS HN...

Страница 16: ...9 71 Victoria Crescent Abbotsford VIC 3067 Ph 03 9879 5294 SA P O Box 101 Woodville SA 5011 729A Port Road Woodville SA 5011 Ph 08 8347 0000 QLD P O Box 511 Archerfield QLD 4108 2 49 Boyland Ave Coope...

Отзывы: