Load Capacity Input Voltage Factor
The acceptable AC input range for the SRG series is between 130V and 260V, inside this the SRG is
able to stabilize the output power to 230V +/- 5% to provide a stabilized pure sine AC power. Note
that when the input voltage drops signi
fi
cantly the SRG must draw more current to provide the voltage
boost to keep the 230V output, this results in reduced power capacity as low as 50% of the rated
maximum. When voltages in these lower ranges are expected then it is necessary to size your SRG
larger to be able to meet the capacity demands of your attached equipment.