EVAPORATORS 

Only for specialist personnel 

The only maintenance the evaporators require is proper cleaning. This has to be done with the machine stopped and once the ice that may be 
present on the fins has melted or once defrosting has been done  by operating the controls. This process may be accelerated by using  warm 
water, NEVER using hard or sharp objects. 

In order to clean the coil or the casing, DO NOT use chemical de-greasers with acid compounds or bleach, chlorine, ammonia or salts as all 
these products aggressively attack copper and aluminium. Only water with well-diluted neutral detergents should be used or products especially 
designed for cleaning the evaporators of refrigerated units. The cleaner the unit, the greater the energy saving

 

AUTOMATIC EVAPORATION TRAY 

Only for specialist personnel 

The majority of the units are equipped with an automatic evaporation tray for the situations where an external outlet is not available to collect the 
defrosted water from the evaporators. If this tray is not included, the drainage tubes have to be connected directly to the appropriate device or a 
receptacle should be positioned in order to collect the water. 

The defrost water can also cause breakdowns as the piping that brings the heat necessary for the water to evaporate can be punctured or the 
electrical resistance can deteriorate. 

The duration and number of defrosts the refrigerating equipment is regulated at the factory. The user should not change this regulation. 

Attention should be given to this tray and regular cleaning is recommended. 

 

 

DOOR SEALS 

The rubber door seals are designed to ensure the closure of the doors to the cold chambers and to guarantee the sealing of the doors against 
external elements. 

A magnetic strip is housed on the inside of the rubber seal, which adheres it to the frame of the unit. Over time granular particles can become 
stuck in the seal due to the effect of the magnet and these can rust and cause stains. 

It is recommended that these door seals are kept free from foreign bodies that can cause rust, as well as fatty deposits which, over a long period 
of time, can affect the rubber of the door seal. 

Clean them with water, using neutral soap and a damp cloth. DO NOT USE DETERGENTS OR ABRASIVE PRODUCTS

 

 

 

9. OPERATINAL TEST 
 

 

CHECKS IN TE EVENT OPERATIONAL FAILURE 

In  some  situations,  operational  failure  can  arise  due  to  simple  causes  that  users  themselves  can  solve,  which  is  why  prior  to  requesting  the 
intervention of a specialised technician, we recommend that you carry out the following checks. 

The appliance does not work 
- Check that it is correctly plugged in. 
- Check that electricity reaches the power outlet. 

- Check that general switch is in the  

I/ON

 position. 

The internal temperature is too high 
Check that there is no heat source nearby. 
- Check that the grill is not obstructed. 
- Check the Set-point. 
- Check that the product loaded is perfectly distributed, without blocking the interior air ventilation exits and that the time elapsed since loading 
has been sufficient to chill the products. 
Check if the evaporator has ice. 
- Check that the condenser is not obstructed. 
- Check that the appliance is functioning normally. 
In the event of strange or excessive noises 
- Check the levelling of the unit as this may cause vibrations. 
- Check that there is no object rubbing against any movable element of the refrigerated unit. 

Содержание DD0150CG

Страница 1: ...USER MANUAL...

Страница 2: ...CAL CHARACTERISTICS AND CONDITIONS OF USE 5 START UP 6 RECOMMENDATIONS 7 PRECAUTIONS 8 MAINTENANCE 9 OPERATIONAL TESTS 10 DECOMMISSIONING 11 ELECTRIC SHEME 12 COLD SHEME ANNEX NORMATIVE INICIAL NOTICE...

Страница 3: ...pply in accordance with the current standards and sufficient for the consumption and safety of the unit Material necessary to clean the unit Water point or drainage outlet as necessary for the install...

Страница 4: ...he unit is equipped with drain cleaning we recommend connecting it directly to the appropriate device or a receptacle should be positioned in order to collect the water FIRST CLEANING First of all rem...

Страница 5: ...f the unit must be selected taking into account the following points Type of product for refrigeration or conservation Ambient temperature Frequency with which the doors are opened According to UNE EN...

Страница 6: ...ts are installed in a row each one must be connected independently to the power supply avoiding the use of extension leads or multiple plugs The manufacture disclaims all liability in the event that a...

Страница 7: ...h the observation described in the above point The units designed for the storage of frozen foods are suitable for the conservation of frozen foods and not for freezing the product The environmental o...

Страница 8: ...is uniformly distributed For this reason sitting or leaning on the drawers is not allowed Do not remove the protection from the movable components without having previously disconnected the power supp...

Страница 9: ...door seals are designed to ensure the closure of the doors to the cold chambers and to guarantee the sealing of the doors against external elements A magnetic strip is housed on the inside of the rub...

Страница 10: ...ollective system make possible If the rules are violated specific sanctions established autonomously according to the laws of each state belonging to the EC and conformally linked to all who are subje...

Страница 11: ...11 ELECTRIC SCHEME 12 COLD SCHEME Models DD0150SG DD0200SG Models DD0150CG DD0200CG Models DD0250SG DD0300SG Models DD0250CG DD0300CG...

Страница 12: ......

Отзывы: