TABLE 42
Default temperature thresholds for modules and fan speeds for Brocade MLXe devices (continued)
Fan speed
Low temperature threshold
High temperature threshold
Medium-high
37 ° C
50 ° C
Medium
27 ° C
40 ° C
Low
-1 °
30 ° C
High-Speed Switch fabric module
High
6 2° C
1 00° C
Medium-high
57 ° C
70 ° C
Medium
5 3° C
6 5° C
Low
-1 °
60 ° C
For information about checking the current low and high temperature threshold settings for modules and fan speeds, refer to
temperature thresholds for modules and fan speeds
NOTE
Adjusting fan controls out of the default setting can negatively affect the efficient cooling of blades and may cause a blade to
overheat and shutdown.
You can change the default low and high temperature thresholds for a particular module and fan speed. For example, to change the low
and high thresholds of the medium fan speed for the management modules to 56 ° C and 72 ° s C, respectively, enter the following
command at the global CONFIG level of the CLI.
device(config)# fan-threshold mp med 56 72
Syntax:
fan-threshold l
module
[
low
high-threshold
] [
med
low-threshold high-threshold
][
med-hi
low-threshold high-threshold
][
high
low-
threshold high-threshold
]
For the
module
parameter, you can specify the following:
•
lp - Changes low and high temperature thresholds for Gen 1 interface modules
•
lp2 - Changes low and high temperature thresholds for Gen 2 interface modules
•
mp - Changes low and high temperature thresholds for management modules
•
mp-cpu - Changes low and high temperature thresholds for the management module CPU
•
switch-fabric - Changes low and high temperature thresholds for non-high-speed switch fabric modules
•
switch-fabric-g2 - Changes low and high temperature thresholds for high speed switch fabric modules (hSFM)
For the
low-threshold
and
high-threshold
parameters, you can specify any temperature in Centigrade. However, when changing low and
high temperature thresholds for module fan speeds, remember that the low temperature threshold of a higher fan speed must be lower
than the high temperature threshold of the lower fan speed. Brocade has established this guideline to ensure fan speed stability.
For example, if you are changing the temperature thresholds for a management module high and medium-high fan speeds, the system
will accept the following values because the low temperature threshold for the high speed (79 ° C) is lower than the high temperature
threshold (82 ° C) for the medium-high speed.
Fan speed
Low temperature threshold
High temperature threshold
High
79 ° C
87 ° C
Medium-high
69 ° C
82 ° C
Managing the cooling system
Brocade NetIron MLXe Series Hardware Installation Guide
53-1004203-04
213
Содержание NetIron MLXe Series
Страница 8: ...Brocade NetIron MLXe Series Hardware Installation Guide 8 53 1004203 04...
Страница 12: ...Brocade NetIron MLXe Series Hardware Installation Guide 12 53 1004203 04...
Страница 20: ...Brocade NetIron MLXe Series Hardware Installation Guide 20 53 1004203 04...
Страница 192: ...Brocade NetIron MLXe Series Hardware Installation Guide 192 53 1004203 04...
Страница 270: ...Brocade NetIron MLXe Series Hardware Installation Guide 270 53 1004203 04...
Страница 286: ...Brocade NetIron MLXe Series Hardware Installation Guide 286 53 1004203 04...
Страница 292: ...Brocade NetIron MLXe Series Hardware Installation Guide 292 53 1004203 04...