6.4.3 Setting mode (with dot)
Various settings can be changed as required in the set-
ting mode.
a. on user level
- Select the setting mode by pressing the 'mode'-key
until 1. appears in the 'code' read-out display.
- Now select the required code, using the 'step'-key.
Code
Description
Setting
Preset
1.
Required flow temperature
- 2 0 - 9 0 ˚C
8 0
2.
Pump setting
- 0 0 pump operation 10 sec.
0 5
0 1 - 1 5 pump operation in minutes
9 9 continuous pump operation
3.
D.H.W. setting
- 2 0 - 6 5 ˚C (with sensor)
6 5
A.
Boiler control operation
- 1 X central heating modulating (or on/off)
1 1
( X = don't care)
- 2 X central heating high/low
- X 0 central heating off, D.H.W. off
- X 1 central heating on, D.H.W. on
- X 2 central heating on, D.H.W. off
- X 3 central heating off, D.H.W. on
b. on service level for the heating contractor
- Select the service code C 1 2 (see para. 6.4.9)
- Select the setting mode by pressing the 'mode'-key
until 1. appears in the 'code'-read-out display.
- Now select the required code, using the 'step'-key.
Code
Description
Setting
Preset
6.
Fan speed at full load
- 1 0 - 6 0 hundreds
4 9
7.
Fan speed at full load
- 0 0 - 9 9 units
0 0
8.
Fan speed at part load
- 1 0 - 6 0 hundreds
3 0
9.
Fan speed at part load
- 0 0 - 9 9 units
0 0
b.
D.H.W. cut-in temp. differential
- 0 1 - 0 5 ˚C
0 5
0 6 = 10 ˚C
0 7 = 15 ˚C
0 8 = 20 ˚C
C.
Max. fan speed D.H.W.
- 1 0 - 6 0 hundreds
4 9
d.
Max. fan speed D.H.W.
- 0 0 - 9 9 units
0 0
E.
Reserve
F.
Monitoring fan speed LD2
- May not be changed !!!
4 5
G.
Forced part load after start
- 0 0 - 1 5 minuten
0 0
H.
Fan speed at start
- May not be changed !!!
3 5
I.
Max. flow temperature at D.H.W.
- 7 0 - 9 0 ˚C
8 0
J.
D.H.W. control
- 0 0 three-way valve
0 0
- 0 1 D.H.W. pump
- 0 2 inverted three-way valve
n.
Heating cut-in temp differential
- 0 5 - 2 0 ˚C
1 0
P.
Security type
- May not be changed !!!
1 4