Absent in simple instrument panels
** Absent in simple instrument panel On/Off
*** On request extension cables can be delivered, so
that the gas train can be fitted on the opposite side to
the instrument panel, thermostat pocket and the flow.
6. REGULATION AND SAFETY EQUIPMENT
6.1 General
The remeha Gas 3c is supplied with electronic control
and safety equipment with flame detection.
6.2 Instrument panel
The remeha Gas 3c is supplied with an instrument panel
that is fitted in the front of the boiler, either left or right.
The instrument panel can be delivered in three models:
- simple instrument panel On/Off;
- simple instrument panel High/Low;
- complete instrument panel High/Low.
All connections are pre-wired and fitted with plugs. The
capillaries from the control panel should be fitted in the
pocket of the boiler, wich is fitted in the top front of the
end section.
The instrument panel, pocket and the flow should
always be fitted at one side of the boiler either left or
right and standard on the same side as the gas
train.***
Fig. 05 Layout of the complete instrument panel
B
D
E
C
A
1
3
5
4
2
6
8
7
9
11
10
The modules contain:
Module A
1. Control thermostat
Setting between 35
°
-95
°
C
2. Hour run meter total running hours*
Module B
3. High-Low thermostat
Setting between 35
°
-95
°
C**
4. Hour run meter full load*
Module C
5. High-limit thermostat 110
°
C (locking)
6. Operating switch (On/Off with optical display)*
7. Switch for circulating pump*
Manual/Off/Automatic
8. Switch for domestic hot water storage pump*
Manual/Off/Automatic
Module D
9. Warning light*
10. Analogue thermometer water temperature
Module E
11. Option for
rematic
®
weather compensating boiler
control*