background image

e-mail: 

[email protected]   

voice: 

360.854.9559   

fax: 

866.783.1742

7

VAD-4 Installation and Operation Manual

INSTALLATION

Each input has a four-position configuration header and two jumpers. You can refer to the
jumper layout in the appendix for a detailed view.  Each jumper is labeled (JPx, where x is
the status/logic input) and the header pins 1,2,3,4 are used to configure for WET or DRY
operation.  The factory default configuration is for a DRY input (Switch, relay contact, open
collector) with jumpers between 1 & 2 and 3 & 4.  In the DRY configuration, the “A” ter-
minal is ground while the “B” terminal is the cathode of the opto-isolator diode pulled up
to 5 volts through a 2.2K resistor.

If an output that you are interfacing with the VAD-4 provides its own voltage then you will
need to configure the corresponding input for the WET (floating) configuration. In the WET
configuration 
the VAD-4’s opto-isolated inputs can be triggered by an input voltage from 5 VDC to 24
VDC. To change a status/logic input to WET (floating), remove both jumpers for the input’s
configuration header (labeled JPx) and place ONE jumper over pins 2 & 3. You may then
connect the positive voltage to the input’s “A” terminal (anode) and ground or minus volt-
age to the input’s “B” terminal (cathode).

NOTE:  Please refer to the appendix for configuration examples and observe proper
polarity.

Silence Sensor input:

The stereo 10 k ohm unbalanced inputs are summed together and monitored for silence.
BOTH channels MUST go silent to trip an alarm.  The alarm threshold is -25dBu.  Connect
your unbalanced source equipment to either or both inputs (SS-L) and/or (SS-R) and tie the
ground to the GND terminal.  If your source equipment is balanced, use the "+" and GND
terminal from the source.  Your source equipments "-" (negative) terminal should never be
grounded.  Shields should be tied to the “Chs Gnd” terminal.  

The SS LED is illuminated when you have audio applied to the inputs. If no audio is pres-
ent or the audio is below the alarm threshold the SS LED will not be lit.  When the SS is in
an alarm condition, the SS LED will flash.

Power Failure input:  

Connect a user supplied 6 to 12 volts DC coaxial (2.1mm/ID, 5.5mm/OD, center positive)
power source to the power failure input connector labeled PF.  An inexpensive 6 to 12 volt
DC wall transformer of any 
current of 50mA or more will do.  NOTE:  The primary (120 VAC) of the wall transformer
should be connected to the utility company side of your service.  An UPS is suggested to
power the VAD-4 during power outages. 

Temperature Probe inputs:

Insert the optional temperature probes (25 foot cable) stereo mini (3.5mm) plug in to either
or both of the rear panel jacks labeled “TEMP” 1 – 2 (-40°F to +190°F/ -40°C to +85°C).
Extension cables may be used if more reach is needed. It is recommended that you limit the
total length of each cable to 50 feet.   

NOTE:  Probes should only be installed or removed when power is disconnected from
the VAD-4.

Содержание VAD-4

Страница 1: ...f Broadcast Tools Inc Copyright 1989 2013 by Broadcast Tools Inc All rights reserved No part of this document may be reproduced or distributed without permission Visit www broadcasttools com for impor...

Страница 2: ...atus inputs 6 Silence sensor input 7 Power failure input 7 Temperature probe inputs 7 Telephone Caller line output 8 Power supply input 8 Telephone line RJ11 jack 8 DTMF Tone detection jumper 8 DIP sw...

Страница 3: ...rding your product or you need assistance please con tact your distributor from whom you purchased this equipment If you would like more information about Broadcast Tools products you may reach us at...

Страница 4: ...sor with remote telco audio monitoring Power failure alarm input port Balanced telco caller audio output port Front panel LED indicators for most operational activities Front panel USB programming ser...

Страница 5: ...ringing is detected on line green HK LED Indicates that the VAD 4 has seized the line and is off hook green PGM LED Indicates that the VAD 4 is in programming mode green ALM LED Lit when an alarm is t...

Страница 6: ...The terminals accommodate wire sizes from 18 28 AWG solid or stranded wire TB1 Top Row K3NO K3CM K3NC K4NO K4CM K4NC K1NO K1CM K1NC K2NO K2CM K2NC TB1 Bottom Row TB2 Top ST4A ST4B K5NO K5CM K5NC GND...

Страница 7: ...ilence Sensor input The stereo 10 k ohm unbalanced inputs are summed together and monitored for silence BOTH channels MUST go silent to trip an alarm The alarm threshold is 25dBu Connect your unbalanc...

Страница 8: ...be installed on one RA 1 rack shelf kit filler panel is provided Jumper Settings JP3 DTMF Tone detection jumper Guard time The VAD 4 is equipped with a 4 position jumper labeled JP3 on its PCB This is...

Страница 9: ...s FTDI USB Serial Virtual COM port drivers do not automatically install they may be downloaded here http www ftdichip com Drivers VCP htm 2 Start a serial terminal application like PuTTY Tera Term or...

Страница 10: ...of numbers are dialed for a selected input alarm Each input channel can be edited individually using the following 1 4 is used for Status Input Alarms ST 1 4 S for Silence Sensor Alarm SS P for Power...

Страница 11: ...rings required before the VAD 4 answers an incoming phone call Enter 0 to disable the automatic answer feature or 1 9 for the desired number of rings Default value 2 4 Repeat Count RPT The repeat coun...

Страница 12: ...me a valid DTMF tone decoded Once there is no more activity the VAD 4 will hang up after the hang up time has elapsed Default value 2 Pager Number and Data String Menu When 4 is selected from the PGM...

Страница 13: ...ult status inputs 1 4 are the only alarms enabled 1 enabled 0 disabled Example To enable the silence sensor alarm type 5 to select the silence sensor SIL fol lowed by 1 to enable the alarm ALARM EN DI...

Страница 14: ...5 Input1 Description 63 10 Input 2 Description 64 10 Silence Description 65 10 Power Description 66 10 Temp Alarm Desc 67 10 Greeting Message 68 10 Call out ID 69 10 On 70 2 5 Off 71 2 5 Enabled 72 2...

Страница 15: ...ory The lap and repeat memories are global for ALL alarms If another alarm is generated while the VAD 4 is off hook the VAD 4 will wait until the current session is finished disconnect and then dial o...

Страница 16: ...d 10 Relay 1 1 second pulse 1 Relay 1 latched 1 Relay 1 un latched 21 Enable Input 2 alarm 22 Disable Input 2 alarm 23 Poll Input 2 Enable Status 27 Poll Input 2 State Status 28 Poll Relay 2 29 Steady...

Страница 17: ...ail Alarm 72 Disable Power Fail Alarm 73 Poll Enable State of Power Fail Alarm 77 Poll Power Fail Alarm 81 Enable Temperature Input 1 Alarm 82 Disable Temperature Input 1 Alarm 83 Poll Enable State of...

Страница 18: ...ensors with 25 foot cables and 3 5mm T R S plugs optional 40 F to 190 F 40 C to 85 C Stereo Silence Sensor Stereo unbalanced 10K ohm inputs Trip level 25dBu Silence sensor level to Telco adjustable Ba...

Страница 19: ...HER WARRANTIES OR REMEDIES TO THE MAXIMUM EXTENT PERMITTED BYAPPLICABLE LAW BROADCAST TOOLSAND ITS SUPPLIERS DISCLAIMALL OTHER WARRANTIES EITHER EXPRESS OR IMPLIED INCLUDING BUT NOT LIMITED TO IMPLIED...

Страница 20: ...e mail support broadcasttools com voice 360 854 9559 fax 866 783 1742 Product_Name Installation and Operation Manual 20 APPENDIX...

Страница 21: ...e mail support broadcasttools com voice 360 854 9559 fax 866 783 1742 Product_Name Installation and Operation Manual 21 APPENDIX Front and Rear Panel Silkscreen Views...

Страница 22: ...e mail support broadcasttools com voice 360 854 9559 fax 866 783 1742 Product_Name Installation and Operation Manual 22 APPENDIX...

Отзывы: