VAD-4 Installation and Operation Manual
PROGRAMMING
Dial-Out Numbers
When (1) is selected from the PGM Menu, the Dial-Out Numbers list will be displayed.
The Dial-Out Numbers are the phone numbers that can be dialed when alarms are generated.
Up to 32 digits can be used in each phone number along with a comma (,) for one second
and a semi-colon (;) for 5 second pauses.
DIAL OUT NBRS:
1-3608549559
2-
3-
4-
ENTER 1-4:
Dial-Out List Menu
When (2) is selected from the PGM Menu, the Dial-Out List is displayed. This is where
you determine what combination of numbers are dialed for a selected input alarm. Each
input channel can be edited individually using the following: 1-4 is used for Status Input
Alarms (ST) 1-4, S for Silence Sensor Alarm (SS), P for Power Fail Alarm (PF) and T for
Temperature Alarm (TA).
Example: To configure the Status Input 1 alarm to call dial-out phone number 1, followed
by dial-out phone number 2 you would type first type “1” to start editing the dial list for
status 1 and then type “12” followed by a carriage return to add dial-out numbers 1 and 2
and finish editing the status 1 dial list.
ST DIAL LIST:
1-12
2-12345
3-21
4-5
PF, SS AND TEMP DIAL LIST:
PF-1234
SS-2
TA-1
ENTER 1-4 FOR STATUS INPUTS, P FOR PF, S FOR SS, T FOR TEMP
ALARM:
THEN DIAL-OUT NBRS 1-4 OR 5 FOR PAGE