11
6.0 CONFIGURATION AND PARAMETER
SETTINGS
To configure the system and set parameters follow these
steps:
1.
Set NT-1 Sensor IDs
2.
Set NC-6 Sensor IDs
3.
Installer Parameters
4.
Set Networker Parameters
6.1 Standard ZonePlus (1x NC-6 and 3x NT-1)
Important Notes:
•
All NC-6 Networker Controllers come configured as ‘Master’
devices by default, with the sensor identification pre-set to
“n01”
•
There can be only one Master Controller set to
“n01”
in a
ZonePlus system
•
All NT-1 Remote Temperature Sensors come configured as
‘Slave’ devices by default, with sensor identification pre-set
to
“n02 ID00:2”
•
Zones sensors must be assigned to dampers; see 6.4.4,
p.15
Table 3:
Standard 4-Zone System Configuration
Zone ID
Sensor
Type
Sensor
ID
Factory
Setting
Sensor
ID
System
Setting
To modify
Sensor ID
System
Setting
Zone A
NC-6
“n01”
“n01”
n/a
Zone B
NT-1
“n02”
“n02”
n/a
Zone C
NT-1
“n02”
“n03”
Jumper “S3”
Zone D
NT-1
“n02”
“n04”
Jumper “S4”
Always set and record all parameters in the Appendix.
Содержание ZonePlus B061006
Страница 35: ...32 Notes ...