ENGLISH
USER MANUAL
BRITEQ
®
3/30
PD-63SH
FUNCTIONS
A. GENERAL CIRCUIT BREAKER:
protects ALL outputs, including the 63A output to the next unit. In case
of emergency all 3 phases AND the neutral are disconnected. With the phase indicators you can easily
check if all 3 phases are available.
B. RESIDUAL CURRENT CIRCUIT BREAKER:
this is a vital security device of the power distributor!
When someone accidentally touches one of the mains conductors, a current leak through the body of
this person could result in a lethal (deadly) shock. As soon as such current leakage in the installation is
detected, the power distributor outputs will be disconnected. The maximum allowable current leakage is
set to 30mA. Under normal working conditions the lever on the right should be in upward position.
Important:
the functions of this device should be tested every 30days by pushing the test button on top:
as a result the outputs should be immediately disconnected from the mains.
C. INDIVIDUAL CIRCUIT BREAKERS:
each of the 3 phases is secured by two C16 automatic circuit
breakers. Under normal working conditions the lever should be in upward position.
D. VOLT & AMPERE METERS:
each of the 3 phases (L1, L2 & L3) have their individual meters.
E. 63A INPUT:
1,5m long mains input cable (3x 63A, 5wire), equipped with CEE (3P+N+E) inlet plug.